The same 9,084 MJ of furniture in a room of 4 m by 5 m by 3 m gives 454 MJ/m² per unit floor area but 97 MJ/m² per unit total surface area. Based on National Research Council of Canada et al. (2005), p. 2.4-2 and Australian Building Codes Board (2020a), Data Sheet B3, p. 40.

Original vector illustration for Fire load density, level 2 Intermediate.

  • Source basis: National Research Council of Canada et al. (2005), p. 2.4-2 (equation per floor area); Australian Building Codes Board (2020a), Data Sheet B3, p. 40 (conversion q_t,d = q_f,d × A_f / A_t); Van Rossum (2027), §4.4 (calorific values); Iqbal and Salley (2004), p. F-26 (both reference areas in use)
  • Alt text: Two drawings of the same furnished room: left the floor is shaded, right all walls, floor and ceiling are shaded, with the two resulting values.