Summary

Design emitted radiation from unprotected areas in C/VM2 (second edition, 2025) for three fire load energy density bands, unsprinklered and sprinklered. Based on Ministry of Business, Innovation and Employment (2025b), p. 44.

Original vector illustration for Fire spread between buildings, level 2 Intermediate.

  • Source basis: Ministry of Business, Innovation and Employment (2025b), p. 44 (Paragraph 4.5.1.6)
  • Alt text: Grouped bar chart of emitted radiation: 83, 103 and 144 kW/m² unsprinklered against 58, 72 and 101 kW/m² sprinklered.