A limited-combustible material is, in the United States model-code scheme described in the 2008 NFPA Fire Protection Handbook, a construction material that is not noncombustible but contains little fuel and spreads flame little. It may therefore be used in some places where noncombustible materials are otherwise required. In that scheme, it must have a potential heat of no more than 8,141 kJ/kg (3,500 Btu/lb) in the NFPA 259 test. It must also either have a thin surfacing of limited flame spread over a noncombustible base, or have a flame spread index of no more than 25 throughout its thickness.[1] The category was intended to recognise materials with limited amounts of combustible content, such as paper-faced gypsum wallboard, in noncombustible building types. Its heat limit is somewhat less than half the heat content of untreated wood.[2]
In the handbook's account, limited-combustible materials are permitted alongside noncombustible ones for the structural elements of Type I and Type II construction, and in other fire protection rules that refer to these classes.[2][3] Other countries use different classes for related purposes. The European classes A1 and A2 and the New Zealand term "limited combustible" are defined by other tests.[4][5]
Definition
The handbook gives three linked definitions for the United States construction types. A noncombustible material is one that, in the form in which it is used and under the conditions anticipated, will not ignite, burn, support combustion or release flammable vapours when exposed to fire or heat. Materials reported as passing ASTM E136, a test in a vertical tube furnace at 750 °C, are considered noncombustible.[1] A combustible material is one that will ignite and burn, and that meets neither of the other two definitions.[1] The idea of combustibility therefore has three levels in this system, not two.
A limited-combustible material sits between them. It does not comply with the definition of noncombustible material. In the form in which it is used, it has a potential heat value not exceeding 8,141 kJ/kg (3,500 Btu/lb) when tested to NFPA 259, Standard Test Method for Potential Heat of Building Materials.[1] In addition it must meet one of two conditions. The first covers materials with a structural base of noncombustible material and a surfacing no thicker than 3.2 mm (1/8 in) with a flame spread index not greater than 50.[1] The second covers materials that, in the form and thickness used, have a flame spread index of no more than 25 and no evidence of continued progressive combustion. This must also hold for surfaces exposed by cutting through the material on any plane, in the tunnel test of NFPA 255.[1]
A last clause deals with durability. Materials whose combustibility or flame spread index may rise above these limits through age, moisture or other atmospheric conditions are considered combustible.[1] The definition therefore looks at the product over its service life, not only as delivered. In the SFPE Handbook, Kodur and Harmathy (2002) use only two groups, burnable (combustible) and nonburnable (noncombustible) building materials. They note that burnable structural materials may become fuel and add to the severity of a fire.[6]
Purpose and history
In United States construction classification, Types I and II are the noncombustible construction types, and Types III, IV and V the combustible ones. This scheme follows recommendations completed in 1980 by a committee of the Board for the Coordination of the Model Codes (BCMC).[7] In Type I construction, only noncombustible or limited-combustible materials are permitted for the structural elements. Gore Willse (2008b) notes that this rule appears in practically every modern building code. If combustible structural materials were allowed in noncombustible building types, the whole concept of their allowed height and area would become meaningless.[2]
For practical reasons, codes still permit some combustible materials in Type I and II buildings for parts that are not structural. Roof coverings, some insulating materials and limited amounts of interior finish and flooring do not add significantly to the fire hazard if they are properly regulated and qualified by fire tests.[2] Some codes went further and accepted materials with a relatively low fuel content and low surface burning characteristics. The purpose was to recognise materials or assemblies with limited amounts of combustible content, such as gypsum wallboard, which is covered with paper but is used as a fire-resistive material.[2] The resulting alternative definitions combined a limit on flame spread rating (NFPA 255) with a limit on heat content (NFPA 259).[2]
Gore Willse (2008b) also records a more fundamental alternative. Instead of complicating the definition to accommodate particular materials, the limited uses and combustibility characteristics of materials acceptable in Type I and II buildings can be defined directly. This approach was followed in the National Building Code of Canada and in the BCMC recommendations.[3] The National Building Code of Canada itself recognises only two basic types of construction, combustible and noncombustible.[1]
Older city codes contained similar rules. The 1968 Building Code of the City of New York allowed materials that were not noncombustible in non-bearing elements under two conditions. The first was a noncombustible base with a surface no more than 1/8 in (3.2 mm) thick and a flame spread rating of no more than 50. Alternatively, the material had to reach no more than 25 in the code's flame spread test, including on cut surfaces.[8] The same code allowed Fire-retardant-treated wood meeting its own requirements in some of these elements.[8]
Test methods
The definitions described in the 2008 handbook use three United States tests. In ASTM E136 the specimen is placed in a furnace at 750 °C (1,380 °F). Minor surface burning, for example of paint, is allowed in the first 30 seconds. The material fails if the furnace temperature rises by more than 30 °C (54 °F) or if the specimen loses more than half of its initial mass.[9] NFPA 259 measures the potential heat of a building material. The handbook groups it with ASTM E136, ASTM D5865 and the international tests ISO 1182 and ISO 1716 under potential heat, heat of combustion and noncombustibility.[10]
The third test is the Steiner tunnel test of NFPA 255 (ASTM E84), which gives the flame spread index used in both branches of the definition. It runs for 10 minutes and compares the specimen with red oak flooring, assigned 100, and a cementitious board, assigned 0.[11] The limit of 25 in the second branch equals the upper bound of Class A for interior wall and ceiling finish under NFPA 101, as described in the 2008 handbook.[12]
The potential heat test had become less used by 2008. The handbook says that NFPA 259 was then rarely specified, while values of effective heat of combustion were more commonly measured with the cone calorimeter (ASTM E1354).[13] For plastics, Benedetti and Colonna (2008) regard potential heat as of little significance in fire protection engineering. The rate at which heat is liberated matters more, because it governs the intensity of the fire.[14] Van Rossum (2027) makes the same point conceptually. A material that releases much energy while needing little energy for pyrolysis burns faster and with a higher heat release rate.[15]
The heat content limit
The limit of 3,500 Btu/lb converts to 8,141 kJ/kg, or about 8.1 MJ/kg. The handbook gives the nominal heat of combustion of wood as about 18,600 kJ/kg.[16] The ratio 8,141/18,600 is 0.44, which matches the statement that the limit is somewhat less than half the heat content of untreated wood.[2]
A worked example shows what the limit allows. Glass-fibre insulation is often coated with a combustible resin binder. When it is used as insulation, the amount of binder is such that the product is considered limited-combustible.[17] One glass-fibre blanket in a series of Underwriters Laboratories tests reported in the handbook contained 6 percent resin by weight.[18]
The binder type is not stated. Calorific values in the International Fire Engineering Guidelines range from 15 MJ/kg for urea formaldehyde to 29 MJ/kg for phenol formaldehyde.[19] The glass fibre itself does not burn. Assuming only the binder contributes, a simple mass balance gives about 0.06 × 15 = 0.9 MJ/kg to 0.06 × 29 = 1.7 MJ/kg of product. This screening estimate is below the 8.1 MJ/kg limit, but is not a measured NFPA 259 result or a product classification.[17]
The same simple mass balance gives an upper bound for one combustible component in an otherwise inert product. Assuming the heat contributions simply add up, a wood-like component of 18.6 MJ/kg could make up at most 8.1/18.6 = 44 percent of the mass. For polyethylene, with a calorific value of 44 MJ/kg, the bound falls to about 18 percent.[19] These are only screening values. A product also has to meet the flame spread conditions of the definition, and the potential heat must be measured in the form in which the material is used.[1]
Use in codes and standards
The class appears throughout the United States construction types described in the 2008 handbook. Type II construction has structural elements made entirely of noncombustible or limited-combustible materials, either protected with a fire resistance of 1 or 2 hours or unprotected.[3] In Type III construction, interior structural elements may be noncombustible, limited-combustible or approved combustible. The handbook also requires a fire resistance rating for Type III exterior walls, subject to the applicable code.[20] Fire barrier walls may be built of noncombustible, limited-combustible or protected combustible materials.[21] The full scheme is described under Building construction types and Noncombustible construction.
Other sources summarise the scheme slightly differently. A NUREG-1805 appendix, quoting Nolan (2000), states that only noncombustible materials are permitted in Type I and that Type II elements are noncombustible or limited combustible. The same appendix labels Type III "Limited Combustible (Ordinary)".[22] Its glossary defines fire resistive construction as construction with noncombustible or limited-combustible structural members having the ratings of NFPA 220.[23] The wording of the class therefore depends on the code edition and on the author summarising it.
The 2008 handbook gives several fire protection rules that use the class as a threshold. Grease duct enclosures in commercial kitchens need no clearance to noncombustibles, 76 mm (3 in) to limited combustibles and 457 mm (18 in) to combustibles unless protected under NFPA 96.[24] NFPA 13, as described in the handbook, does not require sprinklers in bathrooms of residential occupancies of no more than 5.1 m² (55 ft²) built of noncombustible or limited-combustible materials.[25] Exhibition booths should be constructed of noncombustible, limited-combustible or fire-retardant-treated materials.[26] At sea, cargo ship accommodation may use limited combustible materials with sprinklers and smoke detection, or with area-wide detection, but only the noncombustible method is accepted for United States flag vessels.[27]
Typical candidate materials include paper-faced gypsum board, which the alternative definitions were meant to recognise, and glass-fibre insulation with a resin binder.[2][17] Shaw (2008) names fire-retardant-treated wood as a material that could be classified under a "limited combustibility classification" based on heat release rate, then being considered by ASTM and ISO.[28] He also warns that promoting pressure-impregnated wood where noncombustible materials are absolutely required is a misuse, because even the best treatment cannot eliminate some contribution of fuel and smoke.[28]
Related classes in other countries
In Europe, the two highest classes of the Euroclass system described by Hirschler (2008a), A1 and A2, cover similar ground with other tests. Class A1 requires, in the EN ISO 1182 furnace test, a temperature rise of no more than 30 °C, a mass loss of no more than 50 percent and no sustained flaming. It also requires a gross calorific potential (PCS) of no more than 2.0 MJ/kg for the product in EN ISO 1716.[4] Class A2 allows a rise of 50 °C and up to 20 s of flaming, or a gross calorific potential of up to 3.0 MJ/kg for homogeneous products. A2 products must also pass the single burning item test with a fire growth rate index of no more than 120 W/s.[4] The A2 heat limit of 3.0 MJ/kg is less than 40 percent of the United States limit of 8.1 MJ/kg, although the two tests and the quantities they measure are not the same.
New Zealand uses the term itself. In Verification Method C/VM2 (second edition, 2025), a limited combustible material is one that is not non-combustible and meets the criteria in Section 8.1 of the separate Building Product Specifications. A combustible material is one that is neither non-combustible nor limited combustible.[5][29] Under that verification method, external wall cladding less than 1.0 m from a relevant boundary must be non-combustible, limited combustible or a Type A material.[30] For the external vertical fire spread scenario applying to multilevel buildings over 10 m, the whole cladding system must be non-combustible or limited combustible, or pass specified test criteria.[31] For linings, Group Number 1 includes non-combustible materials and materials with limited combustibility, such as plasterboard.[32]
The commentary to the first edition of C/VM2 (2013) adds two practical points. Materials classified non-combustible in AS 1530.1 or ISO 1182 may be assigned Group Number 1 without further testing.[33] Because these tests are severe, a non-combustible material can be assumed not to ignite at heat fluxes up to 30 kW/m², whereas ordinary timber cladding ignites within 15 minutes at that flux.[34]
Limitations and misconceptions
A low flame spread index does not by itself make a product limited-combustible. Benedetti and Colonna (2008) warn that a flame spread classification of 25 or less does not ensure limited combustibility in concealed or flue-like spaces, such as inside walls or above suspended ceilings. Nor can it be assumed that automatic sprinklers will control the hazard there.[35] The definition requires both a low potential heat and limited flame spread, and both must persist with age and moisture.[1]
The word "limited combustible" is also used for things other than building materials. In the needed fire flow method of the Insurance Services Office (ISO), described by Wenzel (2008b), occupancies are placed in combustibility classes C-1 to C-5. Class C-2, "limited combustible", has an occupancy factor of 0.85, against 0.75 for noncombustible and 1.00 for combustible occupancies.[36] Its examples include apartments, churches, hospitals and hotels. This classifies the contents and use of a building, not the combustibility of its construction materials.[36]
Finally, the class describes the fuel content and surface burning of a material, not its rate of heat release. Potential heat says nothing about how fast the heat is released, and by 2008 effective heats of combustion were more commonly measured in the cone calorimeter.[13][14] Shaw (2008) reports that a classification based on heat release rate was then under consideration in ASTM and ISO.[28]
See also
Notes
- ↑ 1.00 1.01 1.02 1.03 1.04 1.05 1.06 1.07 1.08 1.09 Gore Willse (2008b), p. 19-5.
- ↑ 2.0 2.1 2.2 2.3 2.4 2.5 2.6 2.7 Gore Willse (2008b), pp. 19-6–19-7.
- ↑ 3.0 3.1 3.2 Gore Willse (2008b), p. 19-7.
- ↑ 4.0 4.1 4.2 Hirschler (2008a), p. 6-52.
- ↑ 5.0 5.1 Ministry of Business, Innovation and Employment (2025b), p. 66.
- ↑ Kodur and Harmathy (2002), p. 1-157.
- ↑ Gore Willse (2008b), pp. 19-4–19-5.
- ↑ 8.0 8.1 Grill and Johnson (2005b), p. 53.
- ↑ Carino et al. (2005), p. 6.
- ↑ Hirschler (2008a), p. 6-38.
- ↑ Hirschler (2008b), p. 18-26.
- ↑ Hirschler (2008b), p. 18-27.
- ↑ 13.0 13.1 Babrauskas (2008a), p. 6-283.
- ↑ 14.0 14.1 Benedetti and Colonna (2008), p. 6-227.
- ↑ Van Rossum (2027), §4.3.
- ↑ Cholin (2008c), p. 6-69.
- ↑ 17.0 17.1 17.2 Davis (2008b), p. 19-54.
- ↑ Benedetti and Colonna (2008), p. 6-226.
- ↑ 19.0 19.1 National Research Council of Canada et al. (2005), p. 3.3-6.
- ↑ Gore Willse (2008b), p. 19-8.
- ↑ Gore Willse (2008b), p. 19-15.
- ↑ Nolan (2000), as cited in Iqbal and Salley (2004), p. B-37.
- ↑ Iqbal and Salley (2004), p. F-28.
- ↑ Demers (2008b), p. 10-79.
- ↑ Huggins (2008), p. 16-44.
- ↑ Miller and Roether (2008), p. 20-89.
- ↑ Eberly (2008), p. 21-169.
- ↑ 28.0 28.1 28.2 Shaw (2008), p. 6-138.
- ↑ Ministry of Business, Innovation and Employment (2025b), p. 62.
- ↑ Ministry of Business, Innovation and Employment (2025b), p. 46.
- ↑ Ministry of Business, Innovation and Employment (2025b), p. 48.
- ↑ Ministry of Business, Innovation and Employment (2025b), p. 52.
- ↑ Ministry of Business, Innovation and Employment (2013), p. 142.
- ↑ Ministry of Business, Innovation and Employment (2013), p. 23.
- ↑ Benedetti and Colonna (2008), p. 6-229.
- ↑ 36.0 36.1 Wenzel (2008b), pp. 15-25–15-26.
References
- Babrauskas, V. (2008a). Tables and charts. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-269–6-294). National Fire Protection Association.
- Benedetti, R. P., & Colonna, G. R. (2008). Polymeric materials. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-209–6-231). National Fire Protection Association.
- Carino, N. J., Starnes, M. A., Gross, J. L., Yang, J. C., Kukuck, S. R., Prasad, K. R., & Bukowski, R. W. (2005). Passive fire protection (NIST NCSTAR 1-6A). National Institute of Standards and Technology.
- Cholin, J. M. (2008c). Wood and wood-based products. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-61–6-74). National Fire Protection Association.
- Davis, R. J. (2008b). Structural integrity during fire. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 19-29–19-57). National Fire Protection Association.
- Demers, D. P. (2008b). Ventilation of commercial cooking operations. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 10-77–10-89). National Fire Protection Association.
- Eberly, R. (2008). Marine vessels. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 21-151–21-185). National Fire Protection Association.
- Gore Willse, P. J. (2008b). Types of building construction. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 19-3–19-27). National Fire Protection Association.
- Grill, R. A., & Johnson, D. A. (2005b). Fire protection and life safety provisions applied to the design and construction of WTC 1, 2, and 7 and post-construction provisions applied after occupancy (NIST NCSTAR 1-1D). National Institute of Standards and Technology.
- Hirschler, M. M. (2008a). Concepts and protocols of fire testing. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-35–6-60). National Fire Protection Association.
- Hirschler, M. M. (2008b). Interior finish. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 18-23–18-42). National Fire Protection Association.
- Huggins, R. (2008). Automatic sprinkler systems. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 16-29–16-53). National Fire Protection Association.
- Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.
- Kodur, V. K. R., & Harmathy, T. Z. (2002). Properties of building materials. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 1-155–1-181). National Fire Protection Association; Society of Fire Protection Engineers.
- Miller, G., & Roether, E. (2008). Assembly occupancies. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 20-85–20-95). National Fire Protection Association.
- Ministry of Business, Innovation and Employment. (2013). Commentary for Building Code clauses C1–C6 and Verification Method C/VM2.
- Ministry of Business, Innovation and Employment. (2025b). Verification Method C/VM2: Framework for fire safety design (2nd ed.).
- National Research Council of Canada, International Code Council, Department of Building and Housing, & Australian Building Codes Board. (2005). International fire engineering guidelines (2005 ed.). Australian Building Codes Board.
- Shaw, J. R. (2008). Fire-Retardant and flame-resistant treatment of cellulosic materials. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-129–6-139). National Fire Protection Association.
- Van Rossum, E. (2027). Introduction to Fire Safety Engineering. Fire Safety Academy.
- Wenzel, L. J. (2008b). Water supply requirements for public supply systems. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 15-23–15-33). National Fire Protection Association.