Fse-escalator-fire-protection-v1.svg (SVG file, nominally 1,000 × 1,290 pixels, file size: 9 KB)

Summary

Sprinkler draft curtain method: a 457 mm (18 in.) deep draft stop under the floor to which the escalator ascends, with a row of sprinklers outside it, not more than 1.83 m (6 ft) apart and 152 to 305 mm (6 to 12 in.) from the draft stop. Based on Donoghue (2008), p. 10-65.

Original illustration for Escalator fire protection.

  • Alt text: Section and plan of an escalator opening ringed by a 457 mm draft stop with sprinklers at most 1.83 m apart just outside it