Fse-elevator-recall-v4.svg (SVG file, nominally 1,000 × 1,390 pixels, file size: 7 KB)

Summary

Hoistway pressurisation against the lobby: about 87 Pa (0.35 in. of water) gives about 125 N on each landing door panel, enough to stop power-operated doors from closing in three typical scenarios. Based on Donoghue (2008), pp. 10-59 and 10-60.

Original illustration for Elevator recall.

  • Alt text: Plan of a pressurised hoistway pushing on a landing door panel, with three scenarios where doors cannot close

Licensing

New drawing by Fire Safety Academy. © Fire Safety Academy.