Tensile membrane action is the carrying of load by tension in a floor or structural member that has deflected far beyond its normal range, once its bending capacity has been exceeded.[1][2] In the one-way form that NIST studied in the World Trade Center towers, a sagging floor acts as a tensile structure, a behaviour called catenary action.[1] Milke notes that in frames with many members, membrane action may let a heated steel member keep its integrity at temperatures above those usually associated with failure.[2]
The tension does not disappear, however. It has to be anchored at the supports, where it pulls inward on columns and walls.[3] In the twin towers, pull-in forces from sagging floors bowed the exterior walls inward before the towers collapsed.[1] In a full-scale fire test at Cardington in England, on the other hand, a floor sagged 0.64 m over a 9 m span without any reported structural failure.[4] Membrane action can therefore keep a floor up at large deflections, but only if the connections and the surrounding structure can carry the tension.[2][3]
From bending to tension
At normal temperatures, a floor carries its load by bending between its supports. In a fire, the steel loses stiffness and strength, and the floor starts to sag.[5] In its analysis of the World Trade Center floors, NIST listed three causes of sagging between supports. These were the loss of stiffness and strength of the steel trusses and the concrete slab at high temperature, and the yielding or buckling of the truss web members needed for bending. Failure of the connections between slab and trusses, which removes composite action, was the third.[5]
When the bending capacity is exhausted, the floor can still carry load as a hanging cable. NIST defines catenary action as the combined action that results when the bending capacity of the truss is exceeded and additional load is carried by the floor acting as a tensile structure.[1] Part of the load may still be carried by bending, through the residual moment capacity of the deformed floor.[1] For a floor strip under a uniform load, NIST approximated the tension from this combination of bending and catenary behaviour as follows:[6][3] At midspan, where , the first term in the numerator becomes the familiar maximum bending moment of a simply supported beam. Midspan is also where the worked example below applies the formula. The expression then reduces to:
| Symbol | Description | Unit |
|---|---|---|
| horizontal tension in the floor strip | kN | |
| uniform load per unit length of the strip | kN/m | |
| span between supports | m | |
| distance from the support | m | |
| sag of the floor at distance | m | |
| residual moment capacity of the deformed floor | kN·m |
The formula shows the two features that matter most. The tension equals the part of the bending demand that the floor can no longer resist, divided by the sag. A floor that sags less must therefore develop a larger tension to carry the same load. The supports provide vertical reactions of half the total load each, as in ordinary bending, plus the horizontal pull of the tension.[6]
Worked example
The long-span floor trusses of the World Trade Center towers spanned nominally 60 ft (18.3 m) between the exterior walls and the core.[7] In NIST's model of a single long-span truss under assumed fire temperatures, the floor sagged by about 42 in. (1.07 m) after its web diagonals had buckled.[6] The sag was thus about one seventeenth of the span.
If the floor keeps no residual moment capacity, the midspan formula gives a tension of 18.3 / (8 × 1.07) = 2.14 times the total load on the span.[6] Each support then has to resist a horizontal pull about twice as large as the whole load that the floor carries. If the floor keeps a residual moment of a quarter of , the tension falls to 1.61 , and with half to 1.07 .
The sag has an even stronger effect. With no residual moment, a sag of one fortieth of the span requires a tension of 5.0 , and a sag of one tenth only 1.25 . A floor can thus reduce the pull on its supports by sagging further, as long as it does not fail. This one-way calculation is a simplification. NIST used it to approximate the tensile forces in the floor system of the towers.[3] It treats the floor as a strip spanning in one direction and leaves out any action of the slab in the second direction.
Development during a fire
Membrane action is usually the last stage of a longer sequence. Early in a fire, heated members expand, and restrained thermal expansion increases the loads in the heated elements.[6] In the twin towers, the floors expanded in the early stages of the fires. As their temperatures rose, they sagged and began to pull inward on the exterior walls instead.[8]
NIST's model of a single long-span truss shows this sequence in detail. In the model, assumed steel temperatures were raised from 20 °C to 700 °C in 30 minutes and by a further 200 °C in the next 10 minutes.[9] The shear studs on the spandrel failed below 275 °C, and the top chords yielded above 300 °C because steel and concrete expand by different amounts.[9] At 565 °C, four compression diagonals buckled and the floor sagged into a catenary shape.[10]
The connections then carried the tension until they too began to fail. The interior seat bolts sheared at 566 °C, and the gusset plate fractured and the exterior seat bolts sheared at around 680 °C.[10] At 730 °C, the truss walked off its exterior seat.[10] By the time catenary action develops, steel in fire has lost much of its stiffness and strength, so the reserve of the floor lies mainly in its ability to hang between its supports.[5][1]
Demands on supports and connections
The tension in a sagging floor becomes an inward pull on whatever supports it. NIST found that substantial sagging of the tower floors produced pull-in forces at the column connections and led to inward bowing of the exterior wall.[3] A floor with tensile forces at its connections does not restrain the exterior wall from bowing inward.[3] In the global analyses, floors with a large sag likewise did not restrain the exterior columns against buckling.[1]
Sagging can also overload the supports of the floor itself. NIST noted that floor sagging between supports may cause tensile failure of the truss seats, or tensile forces that pull the columns inward.[5] Other fires show the same weakness at connections. In the 1970 fire at One New York Plaza, steel beams were deflected by several inches and their connecting bolts sheared off. No floors collapsed, but there were connection failures and distortion of the floor beams.[11] In World Trade Center 5, bolts tore out of fire-weakened beam webs at field-bolted connections, and large sections of floor failed.[11]
Membrane action is therefore closely tied to the question of progressive collapse. In a frame, load transfer lets stronger members carry loads that heated members can no longer carry, and membrane action may let heated members keep their integrity.[2] If the connections cannot hold the resulting forces, however, the failure of one floor can spread to the columns and walls that support it.[3][11]
Evidence from tests and fires
The most detailed full-scale evidence in the NIST reports comes from the Cardington test building of the Building Research Establishment in England. This eight-storey steel braced frame was completed in 1993 to represent a typical office building, with simple shear connections and bays of 9.0 m along its length.[12] Seven fire tests were carried out in it.[12]
In Test No. 6, office furniture with a fire load of 46 kg/m² burned in a test area of 135 m².[4] Gas temperatures exceeded 900 °C within 10 minutes and reached just over 1200 °C within 40 minutes, and the heat release rate peaked at 58 MW.[4] No structural failures were reported, but the floor sagged by up to 0.64 m in a span of 9 m, about one fourteenth of the span.[4] In Test No. 3, with compartment temperatures of about 960 °C, the largest floor beam deflection was 428 mm, also in a 9 m span.[11]
NIST cites the tests as a comparison with other building fires. It does not analyse how the Cardington floors carried their load at such deflections.[12] Milke's general statement explains the possibility: in frames with many members, load transfer or membrane action may let steel members keep their integrity at temperatures above those normally associated with failure.[2]
Modelling and its limits
Tensile membrane action cannot be captured by checking members one at a time. Milke notes that a frame analysis is needed to capture load transfer, and that available frame analyses range from algebraic methods to finite element models.[2] Predicting membrane action is therefore a task for structural fire engineering analysis of whole floors or frames. Milke also cites a review that found important simplifications in the finite element models for structural fire protection available at the time. These included perfect composite action between steel and concrete and the neglect of torsion, and large displacements were not accurately modelled.[2] Large displacements are exactly what membrane action relies on.
The NIST investigations show what a model needs to include. In the truss model of the towers, the concrete slab was given different strengths in tension and compression. At the interior end of the slab, separate break elements represented the temperature-dependent tensile capacity of its steel reinforcement.[9] The model of the WTC 7 floor likewise included the contribution of the welded wire fabric to the tensile capacity of the slab.[13] The behaviour of concrete in fire in tension, and of its reinforcement, therefore becomes as important as the behaviour of the steel members.
The NIST studies describe one-way catenary action and full-scale observations, but they give no design method for membrane action in floor slabs. The worked example shows the scale of the forces involved rather than a design check. Both Milke and NIST treat membrane action as a property of the whole floor system, with its supports and connections, rather than of single members.[2][3]
See also
- Finite element analysis
- Critical steel temperature
- Fire resistance
- Strength reduction at elevated temperatures
Notes
- ↑ 1.0 1.1 1.2 1.3 1.4 1.5 1.6 Zarghamee, Kitane, et al. (2005), p. 310.
- ↑ 2.0 2.1 2.2 2.3 2.4 2.5 2.6 2.7 Milke (2002a), p. 4-235.
- ↑ 3.0 3.1 3.2 3.3 3.4 3.5 3.6 3.7 Gross and McAllister (2005), p. 296.
- ↑ 4.0 4.1 4.2 4.3 McAllister et al. (2008), p. 337.
- ↑ 5.0 5.1 5.2 5.3 Gross and McAllister (2005), p. 89.
- ↑ 6.0 6.1 6.2 6.3 6.4 Zarghamee, Kitane, et al. (2005), p. 311.
- ↑ Zarghamee, Bolourchi, et al. (2005), p. xxxiii.
- ↑ National Institute of Standards and Technology (2005), p. 144.
- ↑ 9.0 9.1 9.2 Zarghamee, Bolourchi, et al. (2005), p. xxxviii.
- ↑ 10.0 10.1 10.2 Zarghamee, Bolourchi, et al. (2005), p. xxxix.
- ↑ 11.0 11.1 11.2 11.3 McAllister et al. (2008), p. 338.
- ↑ 12.0 12.1 12.2 McAllister et al. (2008), p. 336.
- ↑ McAllister et al. (2008), p. 350.
References
- Gross, J. L., & McAllister, T. P. (2005). Structural fire response and probable collapse sequence of the World Trade Center towers (NIST NCSTAR 1-6). National Institute of Standards and Technology.
- McAllister, T. P., Gann, R. G., Averill, J. D., Gross, J. L., Grosshandler, W. L., Lawson, J. R., McGrattan, K. B., Pitts, W. M., Prasad, K. R., Sadek, F. H., & Nelson, H. E. (2008). Structural fire response and probable collapse sequence of World Trade Center Building 7 (NIST NCSTAR 1-9, Vols. 1–2). National Institute of Standards and Technology.
- Milke, J. A. (2002a). Analytical methods for determining fire resistance of steel members. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 4-209–4-238). National Fire Protection Association; Society of Fire Protection Engineers.
- National Institute of Standards and Technology. (2005). Final report on the collapse of the World Trade Center towers (NIST NCSTAR 1).
- Zarghamee, M. S., Bolourchi, S., Eggers, D. W., Erbay, Ö. O., Kan, F. W., Kitane, Y., Liepins, A. A., Mudlock, M., Naguib, W. I., Ojdrovic, R. P., Sarawit, A. T., Barrett, P. R., Gross, J. L., & McAllister, T. P. (2005). Component, connection, and subsystem structural analysis (NIST NCSTAR 1-6C). National Institute of Standards and Technology.
- Zarghamee, M. S., Kitane, Y., Erbay, Ö. O., McAllister, T. P., & Gross, J. L. (2005). Global structural analysis of the response of the World Trade Center towers to impact damage and fire (NIST NCSTAR 1-6D). National Institute of Standards and Technology.