Contents
Fse-silane-v4.svg (SVG file, nominally 1,240 × 740 pixels, file size: 12 KB)
Summary
Average silane concentration in a well-mixed, ventilated enclosure for a leak of 1.18 L/s (0.25 mm orifice, 103.4 bar), calculated with the dilution balance, with the lower flammable limit of 1.0 percent and 25 percent of it. Based on DeGiorgio and Peterkin (2008), p. 9-127 and Slye (2008), p. 6-202.
Original illustration for Silane.
- Source basis: DeGiorgio and Peterkin (2008), p. 9-127 (Table 9.9.1 and the NFPA 318 concentration chart, which the calculated curve matches); Slye (2008), p. 6-202 (dilution method); National Research Council of Canada et al. (2005), p. 3.3-3 (LFL)
- Alt text: Line chart: average silane concentration falls from above 1 percent to 0.17 percent as exhaust flow rises from 50 to 708 L/s; LFL line at 1 percent.
Licensing
New drawing by Fire Safety Academy. © Fire Safety Academy.
File history
Click on a date/time to view the file as it appeared at that time.
| Date/Time | Thumbnail | Dimensions | User | Comment | |
|---|---|---|---|---|---|
| current | 08:02, 8 November 2026 | 1,240 × 740 (12 KB) | Lisa (talk | contribs) | Watermark: Fire Safety Academy logo icon, 70 px, 45 % opacity |
You cannot overwrite this file.