Fse-mattress-flammability-v3.svg (SVG file, nominally 1,270 × 740 pixels, file size: 6 KB)

Summary

Simulated-bedclothes exposure in the United States open-flame mattress test (16 CFR 1633): a T-head burner of 18 kW above the top surface and one of 9 kW beside the side. Pass limits: peak heat release rate 200 kW, 15 MJ in the first 10 minutes. Based on Babrauskas (2008b), pp. 6-116–6-117 and Stull and Chines (2008), p. 6-94.

Original illustration for Mattress flammability.

  • Source basis: Babrauskas (2008b), p. 6-116 (18 kW top and 9 kW side T-head burners, Ohlemiller et al.), p. 6-117 (Figure 6.6.6, dimensions; 200 kW and 15 MJ; redraw, do not copy); Stull and Chines (2008), p. 6-94 (twin or larger mattress, peak over 30 min)
  • Alt text: Side and top views of a mattress on its foundation with an 18 kW T-burner above the top and a 9 kW T-burner beside the side.

Licensing

New drawing by Fire Safety Academy. © Fire Safety Academy.