Skip to content
From Fire Safety Academy Wiki
Revision as of 08:06, 8 November 2026 by Lisa (talk | contribs) (Lisa uploaded a new version of File:Fse-spill-fire-v4.svg)
Contents
  1. 1Summary
  2. 2Licensing

Fse-spill-fire-v4.svg (SVG file, nominally 1,200 × 840 pixels, file size: 9 KB)

Summary

Constant-rate models for 208 L of gasoline: unconfined spill (about 56 MW for 121 s) and an assumed 4 m² bund (about 9.6 MW for about 700 s). Both release about 6.7 GJ. Actual fires grow and decay. Based on Gottuk and White (2002), pp. 2-313–2-314, and Budnick et al. (2008), p. 3-149.

Original illustration for Spill fire.

  • Source basis: Gottuk and White (2002), p. 2-314; Budnick et al. (2008), p. 3-149; Iqbal and Salley (2004), p. 3-5 (large area: high HRR, short duration)
  • Alt text: Two idealised rectangles of heat release rate against time: spill at 56 MW for 121 s and bunded pool at 9.6 MW for about 700 s.

Licensing

New drawing by Fire Safety Academy. © Fire Safety Academy.

File history

Click on a date/time to view the file as it appeared at that time.

Date/TimeThumbnailDimensionsUserComment
current08:06, 8 November 2026Thumbnail for version as of 08:06, 8 November 20261,200 × 840 (9 KB)Lisa (talk | contribs)Watermark: Fire Safety Academy logo icon, 70 px, 45 % opacity
07:41, 8 November 2026Thumbnail for version as of 07:41, 8 November 20261,200 × 750 (9 KB)Lisa (talk | contribs)Watermark: Fire Safety Academy logo icon, 70 px, 45 % opacity

The following page uses this file:

Metadata