Fse-spill-fire-v1.svg (SVG file, nominally 1,220 × 820 pixels, file size: 13 KB)
Summary
Small unconfined spills on concrete lose heat to the floor and can burn at about one-fifth of a deep pool's rate per unit area. The depths shown are conservative estimates; large continuous spills may approach pool rates. Based on Gottuk and White (2002), pp. 2-300 and 2-311–2-312, and Budnick et al. (2008), p. 3-149.
Original illustration for Spill fire.
- Source basis: Gottuk and White (2002), p. 2-297 (pool deeper than 1 cm, spill thin layer), p. 2-300 (0.7 and 2.8 mm rules), pp. 2-311–2-312 (one-fifth burning rate, heat loss to concrete); Budnick et al. (2008), p. 3-149 (confined/unconfined, about 80 % reduction, 2.8 mm on concrete)
- Alt text: Cross-sections of a thin unconfined spill on concrete losing heat downward and of a deeper confined pool inside a curb, each with flames above.
Licensing
New drawing by Fire Safety Academy. © Fire Safety Academy.
File history
Click on a date/time to view the file as it appeared at that time.
| Date/Time | Thumbnail | Dimensions | User | Comment | |
|---|---|---|---|---|---|
| current | 08:06, 8 November 2026 | 1,220 × 820 (13 KB) | Lisa (talk | contribs) | Watermark: Fire Safety Academy logo icon, 70 px, 45 % opacity | |
| 07:41, 8 November 2026 | 1,220 × 730 (13 KB) | Lisa (talk | contribs) | Watermark: Fire Safety Academy logo icon, 70 px, 45 % opacity |