Hydrogen chloride (HCl) is an acid gas that can be released when chlorine-containing materials are heated in a fire. Polyvinyl chloride (PVC), used in products including wiring, flooring and pipework, is a major source. HCl can appear during thermal decomposition before flames develop, so its presence cannot be inferred from flaming alone.[1][2] It is a strong irritant to the eyes and airways. The pain, tearing and breathing difficulty can impede escape, while a sufficiently high inhaled dose can injure the lungs after the exposure has ended.[3]

In Fire toxicity assessment, HCl has two distinct roles. Its immediate sensory effects are assessed against the concentration in the breathing zone, whereas serious lung injury depends on both concentration and duration.[3][4] The gas also deposits on wet or adsorptive surfaces. This can reduce the airborne concentration away from the fire, but creates a separate problem of chloride contamination and corrosion of equipment.[1][5] Consequently, the HCl yield of a material, the concentration a person breathes and the contamination left on a surface are different quantities.

Formation in heated materials

Chlorine-bearing Plastics in fire can form HCl during pyrolysis, the thermal breakdown of a material. The halogen acids are formed even when that process does not lead to flaming combustion. Other halogen-bearing materials can form hydrogen bromide or Hydrogen fluoride, and chlorine- or bromine-based fire retardants can add to the acid-gas yield.[1][3] HCl is especially associated with Polyvinyl chloride, whose chlorine is part of the polymer chain rather than merely an external contaminant.[1][2]

The 2008 Fire Protection Handbook says that PVC readily evolves HCl at about 225–275 °C (437–527 °F).[1] Tewarson's SFPE account reports that release can begin at temperatures as low as about 100 °C in particular tests, with HCl a major effluent up to about 200–220 °C.[5] These observations describe different materials and test conditions, so they should not be turned into a single universal onset temperature. A specimen may lose HCl before a large fraction of its carbon is consumed; the instantaneous HCl mass divided by the carbonaceous mass lost can therefore look unusually high early in decomposition.[1]

PVC products vary widely. The NFPA chapter describes hundreds of rigid and plasticised formulations, and says that most of the chlorine in PVC is released as HCl. Plasticisers and other additions affect fire behaviour, so building products should be tested in the form in which they are used.[2] Tewarson's tests show that acid-neutralising fillers can sharply reduce the measured HCl yield.[6] Gann and Bryner attribute the low yield from PVC containing much calcium carbonate to the formation of solid calcium chloride.[1] The rate and amount of generation therefore have to be tied to a formulation and a heating condition.

An electrical cable illustrates the distinction. Its jacket and insulation may contain different materials, and HCl from PVC wiring can serve as a fuel-specific fire signature in a telecommunications facility.[7] That is a clue to a possible source, not a measurement of how much HCl remains airborne elsewhere in the building. The gas can be retained in char, deposited on surfaces or carried away with the smoke.[8][9]

Yields and material composition

For pure PVC, Tewarson gives a stoichiometric HCl yield of 0.581 g per gram of material.[10] This is a composition-based upper reference, not the HCl concentration in a room. A specimen with less chlorine than pure PVC has a different maximum. One rigid PVC sheet in Tewarson's table contained 49.3 % chlorine; converting that chlorine entirely to HCl gives 0.507 g HCl per gram of sheet. Its measured yield in air was 0.479 g/g, about 94.5 % of that specimen-specific maximum.[6]

The same table reports 0.480 g/g for that sheet in an inert atmosphere, 0.263 g/g for one PVC cable in air, and 0.117 g/g for one PVC–plasticiser–calcium carbonate mixture in nitrogen.[6] These values come from different formulations and conditions. They demonstrate why a single generic yield should not be assigned to every product bearing the PVC name. The table also shows that adding acid neutraliser and changing the proportions of PVC and plasticiser alter the measured release; it does not isolate any one change as the sole cause.[6]

The apparent yield can vary over the course of a test. Early HCl release may precede much of the material's other mass loss, while later products include carbon monoxide and organic compounds.[1][5] The yields in Tewarson's table are reported as grams of HCl per gram of tested material. They must be kept separate from a room concentration, which depends on release rate, ventilation, mixing and removal.[6][4][9] For this reason, a material balance by itself does not show what an occupant breathes along an escape route.

Effects on people

HCl is both a sensory and a pulmonary Irritant gas. It can stimulate the eyes, nose, mouth and throat almost immediately. The handbook describes pain, blinking, tearing and mucus production; shutting the eyes can briefly relieve pain while making wayfinding harder.[3] A person may also cough or experience bronchoconstriction as HCl reaches the lungs. High exposures can lead to inflammation, pulmonary oedema and death, usually 6–48 hours after exposure in the account given by Gann and Bryner.[3] The delayed effect is one reason that an ability to keep moving during exposure does not establish that the exposure was harmless.

The handbook describes 75–100 µL/L as extremely irritating to the eyes and upper airway, with possible interference with physical activity needed for escape. For gas volume fractions, 1 µL/L is numerically equal to 1 part per million by volume (ppm).[3][11] Purser gives 50–100 ppm as strongly irritating in the human reports he reviews, and describes about 100–500 ppm as potentially slowing escape.[12][13] Those are observations and expert interpretations with different exposure conditions, not a sharp boundary between safe and unsafe air.

The two effects follow different time patterns. Sensory discomfort is principally associated with the concentration encountered at a given moment and does not normally intensify merely because the same concentration continues. Lung injury depends on the inhaled dose, including exposure duration, and may become evident only later.[3][12] Van Rossum likewise describes acidic halogen gases as obstructing vision and breathing during escape, although the Dutch engineering text does not supply an HCl-specific numerical criterion in that discussion.[14]

Animal results do not directly define a human escape limit. In short baboon exposures, trained animals still performed an escape manoeuvre at about 17,000 µL/L for five minutes. Yet deaths followed some exposures that had not stopped the manoeuvre.[3] The handbook cautions that humans may be endangered at far lower concentrations and that people with impaired lung function may be more susceptible.[3]

For the distinct endpoint of lethality in rats, its Table 6.2.1 gives a 30-minute LC50 of 3,800 µL/L. The N-gas equation on the same page uses 3,700 in an HCl term and attributes small differences between models to experimental uncertainty.[15] Neither number is a validated human escape concentration.

Concentration criteria and worked example

The 2008 handbook presents an ISO 13571 incapacitating volume fraction of 1,000 µL/L for HCl. It uses a Fractional effective concentration (FEC) to add the effects of irritants in a modelled smoke atmosphere.[3][4] The HCl contribution at a particular time is the current HCl concentration divided by that criterion. The same source gives 500 µL/L for HF, so a two-gas illustration can be written as follows:[3]

FECHCl+HF=CHClFHCl+CHFFHF

Symbols for the illustrative FEC calculation
Symbol Description Unit
CHCl,CHF simultaneous breathing-zone volume fractions of the two gases µL/L
FHCl,FHF source-specific incapacitating reference values µL/L
FEC sum of the concentration fractions at that instant dimensionless

For a hypothetical breathing-zone snapshot of 300 µL/L HCl and 50 µL/L HF, the ISO-based fractions are 300/1,000 = 0.30 and 50/500 = 0.10. Their sum is FEC = 0.40. This is only a worked arithmetic example; it is not a measured fire atmosphere or a prediction of an individual's escape or later lung injury.[3][4] The full assessment requires the time-varying concentrations of all important gases at the person's location, while heat and visibility present separate hazards.[4]

The value of 1,000 µL/L should not be confused with every other HCl criterion. Purser's 2002 SFPE chapter estimates that 200 ppm would impair escape in half the population and 900 ppm would incapacitate half. His first value concerns impaired movement; the second is a more severe endpoint.[16] The handbook's 1,000 µL/L is a separate ISO-based incapacitation estimate, rather than a revision of Purser's 200 ppm value.[3] The inputs differ in endpoint and judgement, even though both are used to discuss escape in a fire.

For more sensitive people, a criterion of FEC = 1 is insufficient as a guarantee. The 2008 handbook's illustrative susceptibility distribution associates FEC = 0.3 with 11.4 % of the population still susceptible to incapacitation at lower exposures and says no numerical criterion protects everybody.[9] Purser also proposes a 0.3 factor for escape impairment, but against his own 200 ppm reference and for a different outcome.[16] A workplace exposure limit or a one-hour emergency-planning level has yet another purpose; the handbook explicitly warns that occupational long-term limits are normally of little use for short, high fire exposures.[11][16]

Movement, deposition and corrosion

The HCl concentration at the point of generation need not persist as smoke moves. Gann and Bryner say that halogen-acid concentrations decay relatively quickly in effluent below 100 °C when water droplets and adsorptive surfaces are present.[1] They also explain why a mass-loss toxicity model that keeps all gases in fixed proportions can overestimate acid-gas concentration farther from the fire: acid gases stick to surfaces more readily than the narcotic gases.[9] This is a modelling tendency, not a guaranteed reduction for every compartment or escape route.

The deposited chloride creates another exposure pathway for property. In a PVC floor-covering fire test in an unventilated room measuring 2.8 m × 2.8 m × 2.4 m, about half of the original chloride ions were deposited on walls.[5] In a separate apparatus experiment, HCl deposition on wet filter paper was almost four times that on dry paper.[5] Neither fraction should be applied unaltered to a different room: humidity, surface material, air movement and the fire itself affect deposition.[17]

HCl and deposited chloride can corrode metal and damage electronics. Tewarson describes chloride deposits reacting with zinc to form hygroscopic zinc chloride, which can form a conductive solution and lead to electrical shorting at low relative humidity.[17] In one handbook discussion, electronic equipment is described as vulnerable to smoke containing 0.01 % HCl, especially where restoration does not start promptly.[18] That statement addresses potential equipment damage, not an occupant tenability criterion. A different NFPA chapter says that acid gases are especially harmful to electronics, yet HCl deposited on intervening walls may reduce the concentration reaching equipment farther from the fire.[19]

These competing effects make telecommunications facilities a clear example of the dual hazard. PVC wiring can identify the likely source of HCl, while smoke movement and deposition determine both exposure and contamination.[7][19] In a fire involving a sensitive installation, an airborne reading alone cannot describe the chloride left on equipment. Equally, a contaminated surface does not by itself reconstruct the concentration that an occupant breathed earlier.[5][9]

Using the data in a fire assessment

An assessment starts with the actual products present, their plausible decomposition conditions and the location of people or assets. A yield from a laboratory specimen is an input to a release estimate; it is not automatically an input concentration for a person's breathing zone.[4][6] A fire-growth and smoke-spread calculation may distribute those gases through a building, but the handbook notes that the gas yields themselves remain inputs rather than being predicted by the fire model's combustion chemistry.[4] The analysis must keep temperature, ventilation and deposition assumptions visible.

The FEC calculation addresses immediate escape impairment from sensory irritants. It does not cover the dose-dependent lung effects of prolonged HCl exposure, nor the cumulative action of asphyxiants, heat or obscuration.[3][4] The 30-minute rat LC50 and Purser's derived 114,000 ppm·min dose belong to lethality discussions with specified endpoints and populations.[15][13][20] Dividing that dose by an arbitrary concentration would assume a linear concentration–time response outside the tested condition; it cannot establish a safe exposure duration or a human incapacitation time.

Lastly, source disagreement should remain visible. The handbook's 225–275 °C description of ready release and Tewarson's report of an onset as low as 100 °C refer to different circumstances.[1][5] The 200, 900 and 1,000 ppm values describe different escape endpoints or models.[16][3] Concentrations in a compartment may also change through deposition while the contaminant remains on surfaces.[9][5] These are reasons to select material-specific data and an explicit endpoint, rather than to treat any single HCl number as a universal fire limit.

See also

Notes

  1. ↑ 1.00 1.01 1.02 1.03 1.04 1.05 1.06 1.07 1.08 1.09 Gann and Bryner (2008), p. 6-13.
  2. ↑ 2.0 2.1 2.2 Benedetti and Colonna (2008), p. 6-222.
  3. ↑ 3.00 3.01 3.02 3.03 3.04 3.05 3.06 3.07 3.08 3.09 3.10 3.11 3.12 3.13 3.14 Gann and Bryner (2008), p. 6-16.
  4. ↑ 4.0 4.1 4.2 4.3 4.4 4.5 4.6 4.7 Gann and Bryner (2008), p. 6-24.
  5. ↑ 5.0 5.1 5.2 5.3 5.4 5.5 5.6 5.7 Tewarson (2002), p. 3-138.
  6. ↑ 6.0 6.1 6.2 6.3 6.4 6.5 Tewarson (2002), p. 3-139.
  7. ↑ 7.0 7.1 Custer and Milke (2008), p. 2-76.
  8. ↑ Tewarson (2002), p. 3-143.
  9. ↑ 9.0 9.1 9.2 9.3 9.4 9.5 Gann and Bryner (2008), p. 6-25.
  10. ↑ Tewarson (2002), p. 3-123.
  11. ↑ 11.0 11.1 Gann and Bryner (2008), p. 6-14.
  12. ↑ 12.0 12.1 Purser (2002), p. 2-115.
  13. ↑ 13.0 13.1 Purser (2002), p. 2-119.
  14. ↑ Van Rossum (2027), §7.7.
  15. ↑ 15.0 15.1 Gann and Bryner (2008), p. 6-18.
  16. ↑ 16.0 16.1 16.2 16.3 Purser (2002), p. 2-121.
  17. ↑ 17.0 17.1 Tewarson (2002), p. 3-137.
  18. ↑ Milke and Klote (2008), p. 18-46.
  19. ↑ 19.0 19.1 Hurley and Bukowski (2008), p. 3-133.
  20. ↑ Purser (2002), p. 2-122.

References

  • Benedetti, R. P., & Colonna, G. R. (2008). Polymeric materials. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-209–6-231). National Fire Protection Association.
  • Custer, R. L. P., & Milke, J. A. (2008). Fundamentals of fire detection. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 2-75–2-78). National Fire Protection Association.
  • Gann, R. G., & Bryner, N. P. (2008). Combustion products and their effects on life safety. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-11–6-34). National Fire Protection Association.
  • Hurley, M. J., & Bukowski, R. W. (2008). Fire hazard analysis techniques. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 3-121–3-134). National Fire Protection Association.
  • Milke, J. A., & Klote, J. H. (2008). Smoke movement in buildings. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 18-43–18-55). National Fire Protection Association.
  • Purser, D. A. (2002). Toxicity assessment of combustion products. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-83–2-171). National Fire Protection Association; Society of Fire Protection Engineers.
  • Tewarson, A. (2002). Generation of heat and chemical compounds in fires. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 3-82–3-161). National Fire Protection Association; Society of Fire Protection Engineers.
  • Van Rossum, E. (2027). Introduction to Fire Safety Engineering. Fire Safety Academy.