An irritant gas is a gas that inflames the tissue it touches without destroying it. In fire smoke the irritants attack the eyes, the nose and throat and, deeper in, the lungs. Their first effect is pain rather than poisoning. They cause tears, coughing and breathing difficulty while a person is trying to escape.[1] A glossary of fire terms describes irritant gases simply as acid gases and other hydrocarbon by-products that can cause pain on contact or inhalation.[2]

Irritants form one of the three classes of fire gas toxicant, alongside the asphyxiants and a small group with unusual effects.[3] They matter to Fire toxicity in a different way from the asphyxiants. Sensory irritation depends mainly on the concentration present at that moment, while narcosis depends on the dose built up over time.[4] The two most studied fire irritants are hydrogen chloride from polyvinyl chloride and acrolein from smouldering cellulose and polyethylene.[5][1]

Irritants rarely kill during a fire exposure. They kill afterwards, through lung inflammation and oedema that appear hours later, and they kill indirectly by slowing or stopping escape.[1][6] In the Netherlands they are treated separately from the toxic gases for exactly this reason: they are judged by the concentration encountered, not by the dose absorbed.[7]

What counts as an irritant gas

In the United States, NFPA 55 as described in the 2008 edition of the Fire Protection Handbook lists irritant gas among the health hazards of gases, next to corrosive, cryogenic, toxic and highly toxic gases.[8] An irritant gas is defined there as a chemical that is not corrosive but causes a reversible inflammatory effect on living tissue by chemical action at the site of contact.[9] The test is formal. A chemical is a skin irritant if it scores 5 or more on intact skin of albino rabbits by the methods of 16 CFR 1500.41. It is an eye irritant if so determined by the procedure of 16 CFR 1500.42.[9]

Reversibility is what separates an irritant from a corrosive gas. A corrosive gas causes visible destruction or irreversible alteration of living tissue at the point of contact.[9] The same substance can appear in both roles at different concentrations, which is why fire engineering uses concentration thresholds rather than a yes or no classification.[1]

Combustion toxicology divides the effects into two groups. Sensory irritation covers the eyes and the upper respiratory tract, while pulmonary irritation affects the lungs.[1] Most fire irritants produce signs of both.[1] Occupational limits are of little help here. Threshold limit values and long-term exposure values are designed for daily workplace exposure, while fire exposures are high concentrations over a few minutes.[3]

Sensory and pulmonary irritation

Eye irritation is immediate and depends primarily on concentration.[1] Nerve endings in the cornea are stimulated, which causes pain, reflex blinking and tearing, and severe exposure can damage the eye.[1] A victim may shut the eyes to relieve the pain, which protects the cornea but also prevents them from finding the way out.[1] Airborne irritants also enter the nose, mouth and throat, where they cause burning sensations and mucus secretion.[1] These sensory effects do not normally grow more severe as the exposure continues.[1]

What follows is different in kind. Inhaled irritants reach the lungs and produce coughing, bronchoconstriction and increased pulmonary flow resistance.[1] Tissue inflammation, pulmonary oedema and death may follow high concentrations, usually within 6 to 48 hours, and survivors appear more liable to bacterial infection afterwards.[1] Unlike sensory irritation, this response depends on both the concentration and the duration of the exposure, and it follows the accumulated dose fairly closely.[1][6]

The gap between the two effects is wide. For most sensory irritants the ratio between a severely irritating concentration and the dose that kills is 15 to 500 times for a 30 minute exposure.[6] Animal data must be read with care, because the response differs between species. Rodents reflexively slow their breathing when exposed, which protects them, whereas primates breathe faster, so a larger share of the irritant reaches the lungs.[1][10]

The standard animal measure is the mouse RD50, the concentration that halves the respiratory rate.[10] A relationship has been demonstrated between this value and the potency of known irritants in people.[10] One author holds that a human exposed at the mouse RD50 of any substance would be severely irritated, and seriously incapacitated within three minutes.[10] Potencies cover an enormous span. The sensory potencies of fire irritants differ by six orders of magnitude, and their lethal potencies by about five.[11]

Which gases occur in fire smoke

Inorganic irritants in smoke are the halogen acids and the compounds formed from nitrogen oxides; the organic irritants are mainly aldehydes.[12] Polymers containing fluorine, chlorine or bromine give hydrogen fluoride, Hydrogen chloride and hydrogen bromide.[5] These acids form during the pyrolysis part of combustion and are not oxidised further, so they appear even without flaming, and their production efficiencies are close to unity.[5]

Polyvinyl chloride is the best known source. It releases hydrogen chloride readily at about 225 to 275 °C, and the mass yield can exceed the stoichiometric value early in decomposition.[5] Formulations with a high calcium carbonate filler give far lower yields, because the chlorine reacts to form solid calcium chloride, which is thermally stable in a fire.[5] Fluoropolymers are a major source of hydrogen fluoride, and halogenated fire-retardant additives contribute as well.[1]

The acid gases do not persist. Their concentrations decay quickly on adsorptive surfaces and in the water droplets present in most fire effluent below 100 °C.[5] Away from the fire the acid gases therefore fall relative to the narcotic gases, which is why a model that keeps them in fixed proportion is conservative.[13] The same deposition lowers the exposure of equipment to corrosion, and zone models include a routine for the loss of hydrogen chloride to surfaces.[14]

Nitrogen dioxide and nitric oxide are the main oxides of nitrogen, with nitric oxide about one fifth as potent as the dioxide.[1] In rat tests under smoke toxicity test conditions nitrogen dioxide has a lethal potency comparable with hydrogen cyanide, but it acts as a pulmonary irritant, and deaths occur after the exposure, usually within a day.[1] Sulfur-containing polymers give sulfur oxides, and phosphorus-based fire retardants can give a phosphoric acid aerosol, for which no predictive yields exist.[5]

Among the organic irritants, formaldehyde, the unsaturated aldehydes and the isocyanates from nitrogen-containing polymers are judged the most important.[5] Acrolein stands out. It has been found in many fire atmospheres, and it forms during the smouldering of all cellulosic materials and the oxidative pyrolysis of polyethylenes.[5] Because hydrogen chloride and sulfur dioxide are strongly irritating, they ordinarily force evacuation long before their toxic effects become dangerous.[15]

Effect on escape

The practical importance of irritants lies in what they do to movement. Sensory irritation of the respiratory tract can reduce the speed of movement and the ability to negotiate an escape route, and at higher exposures it leads to incapacitation or death.[16] Eye irritation prolongs exposure to all the other hazards, because it adds to the loss of Visibility in smoke.[16]

Walking experiments show the size of the effect. In nonirritant smoke, walking speed fell from about 1.2 m/s in clear air to 0.3 m/s at an optical density of 0.5 per metre. At that density people behaved as if in darkness and felt their way along the walls.[17] With irritant smoke from heated wood chippings, speed dropped to the same level at an optical density of only 0.2 per metre, and the experience was more distressing.[17] In one corridor study, 31 subjects walked up to 10.5 m through smoke from smouldering cedar crib chips at extinction coefficients of 0.1 to 1.2 per metre. Both their walking speed and their ability to answer mental arithmetic questions fell as the smoke density and the radiant heat rose.[18]

Tears are the specific mechanism. In thick irritating smoke they prevented subjects from reading the words on signs and made them walk irregularly or along the wall. In thin smoke, walking speeds were about the same as in non-irritating smoke.[19] Visibility through thin smoke is governed by physical obscuration, but in thick smoke the physiological irritant effect becomes the dominant factor.[20] Roughly 30 per cent of people turn back rather than enter smoke, on average at a visibility of about 3 m.[17]

Classification tests do not capture any of this. The smoke developed index of NFPA 255 is determined solely by obscuration of light. The irritancy of the smoke and its debilitating effect on escaping occupants are not evaluated by the usual limit of 450.[21] Neither does a Smoke toxicity test record sensory irritation, because it measures lethality.[22] In nonflaming cup furnace tests of wood and of flexible polyurethane foam, the measured gases explained only 0.47 and 0.29 of the lethality, and the remainder was attributed to organic irritants that were never identified.[23]

Tenability criteria

Sensory irritation follows the concentration rather than the dose. It is therefore assessed with a Fractional effective concentration rather than with an accumulated dose. Each irritant present is divided by the concentration of that gas judged to incapacitate, and the fractions are added:[4]

FEC=fHClFHCl+fHBrFHBr+fHFFHF+fSO2FSO2+fNO2FNO2+facroleinFacrolein+fformaldehydeFformaldehyde+∑firritantFirritant

The time at which the sum reaches 1 is taken as the time at which the average person becomes incapacitated.[4] The same criterion of 1 is used for the dose-based measure applied to the asphyxiants. The two thresholds should be set equal, so that neither hazard is weighted more heavily than the other.[13]

Symbols in the fractional effective concentration equation
Symbol Description Unit
fx volume fraction of irritant x present at that moment µL/L
Fx volume fraction of irritant x judged to incapacitate µL/L
FEC sum of the fractions for all irritants present –
Irritant criteria from two sources, in µL/L (numerically equal to ppm by volume)
Gas Incapacitating value, ISO 13571[1][24] Impairs escape in half the population[25] Incapacitates half the population[25]
Hydrogen chloride 1,000 200 900
Hydrogen bromide 1,000 200 900
Hydrogen fluoride 500 200 900
Sulfur dioxide 150 24 120
Nitrogen dioxide 250 70 350
Acrolein 30 4 20
Formaldehyde 250 6 30

A second sum handles the delayed lung injury. The fraction of a lethal dose is formed from the exposure doses of the same gases and accumulated until it reaches 1. The doses used are 114,000 ppm·min for hydrogen chloride and 4,500 ppm·min for acrolein.[26] Dividing those doses by the 30 minute exposure returns 3,800 and 150 µL/L, the 30 minute LC50 values of the two gases.[27] Where the aldehyde concentrations are unknown, an optical density of 0.5 per metre may stand in for escape-impairing irritancy, and 90 OD·m−1·min for a lethal organic irritant dose.[25][26]

Worked example: two baboon exposures

Baboons were trained to operate a lever to escape from a chamber after a five minute exposure. They performed the task at 2,780 µL/L of acrolein and at 16,570 µL/L of hydrogen chloride.[28][1] Dividing by the incapacitating values of the equation gives 2,780/30 = 92.7 for the acrolein test and 16,570/1,000 = 16.6 for the hydrogen chloride test.

Both values exceed 1 by a wide margin, yet neither exposure prevented the trained escape movement. The model would have predicted incapacitation at a thirtieth and a sixteenth of these concentrations.[1][24] The handbook draws the obvious conclusion for acrolein and calls its own consensus value conservative.[24]

The lethal side of the same experiments points the other way. One baboon died from pulmonary effects after exposure at 1,025 µL/L of acrolein, and two died at about 17,000 µL/L of hydrogen chloride.[28] In each case death came hours after an exposure that had not stopped the animal escaping.[28] Escape capability and survival are therefore not the same test, and a criterion that protects the first does not automatically protect the second.[1]

Uncertainty and disagreement

Setting irritant thresholds has been controversial, because almost no controlled human studies exist and most information is anecdotal.[1] The two main sources in fire engineering do not agree. For hydrogen chloride the handbook's consensus incapacitating value is five times the concentration at which Purser expects escape to be impaired, and for formaldehyde it is more than forty times.[1][24][25] Values for hydrogen fluoride run the other way, with Purser placing incapacitation at 900 µL/L against the handbook's 500 µL/L.[1][25]

Human data that do exist come from accidents and from low-level experiments. Hydrogen chloride is perceived as irritant from about 10 to 50 µL/L, is strongly irritant at 50 to 100 µL/L, and brief exposure at 1,000 to 2,000 µL/L is regarded as dangerous to lethal.[25] A separate account gives 75 µL/L as extremely irritating to the eyes and upper respiratory tract, with 50 µL/L as the maximum for exposures of 30 to 60 minutes.[29] For nitrogen dioxide, throat irritation can begin at 62 µL/L, 117 to 154 µL/L is dangerous for short exposures, and 140 to 775 µL/L is rapidly fatal.[30]

Hydrogen fluoride shows how widely the thresholds are spaced. Detection, severe sensory irritation and the approximate lethal concentration lie roughly two and three orders of magnitude apart.[31] Published health effects put slight eye and nasal irritation below 50 µL/L for two minutes, while above 200 µL/L for ten minutes escape-impairing effects will occur and higher concentrations can be lethal without medical treatment.[32] Emergency planning guidelines for ten minute exposures set 50 µL/L as the level at which evacuation should begin and 170 µL/L as the maximum non-lethal concentration.[32]

Susceptibility varies as much as the data. Asthmatics and people with chronic bronchitis or reactive airways dysfunction can suffer bronchoconstriction, collapse and occasionally death after brief exposure to low irritant concentrations.[13] A criterion of 0.3 instead of 1 leaves about 11 per cent of the population liable to incapacitation, and no threshold is statistically safe for everyone.[13] Applying a factor of 0.3 to the escape-impairment concentrations is suggested as allowing nearly all exposed people to escape.[25]

Two further gaps remain. Smoke atmospheres often prove more irritant than their measured composition can explain, which points to short-lived reactive species that are not routinely measured.[33] Tests for incapacitation by sensory irritation have been developed but are little used, partly for want of validation against effects on people, so the field has settled on inferring incapacitation from lethality instead.[27]

See also

Notes

  1. ↑ 1.00 1.01 1.02 1.03 1.04 1.05 1.06 1.07 1.08 1.09 1.10 1.11 1.12 1.13 1.14 1.15 1.16 1.17 1.18 1.19 1.20 1.21 1.22 1.23 1.24 Gann and Bryner (2008), p. 6-16.
  2. ↑ Iqbal and Salley (2004), p. F-40.
  3. ↑ 3.0 3.1 Gann and Bryner (2008), p. 6-14.
  4. ↑ 4.0 4.1 4.2 Gann and Bryner (2008), p. 6-24.
  5. ↑ 5.0 5.1 5.2 5.3 5.4 5.5 5.6 5.7 5.8 Gann and Bryner (2008), p. 6-13.
  6. ↑ 6.0 6.1 6.2 Purser (2002), p. 2-112.
  7. ↑ Van Rossum (2027), §7.7.
  8. ↑ Lemoff (2008), p. 6-166.
  9. ↑ 9.0 9.1 9.2 Lemoff (2008), p. 6-167.
  10. ↑ 10.0 10.1 10.2 10.3 Purser (2002), p. 2-113.
  11. ↑ Purser (2002), p. 2-91.
  12. ↑ Gann and Bryner (2008), p. 6-15.
  13. ↑ 13.0 13.1 13.2 13.3 Gann and Bryner (2008), p. 6-25.
  14. ↑ Hurley and Bukowski (2008), p. 3-132.
  15. ↑ Benedetti and Colonna (2008), p. 6-230.
  16. ↑ 16.0 16.1 Gann and Bryner (2008), p. 6-11.
  17. ↑ 17.0 17.1 17.2 Purser (2002), p. 2-118.
  18. ↑ Bryan (2008), pp. 4-35–4-36.
  19. ↑ Iqbal and Salley (2004), p. 18-3.
  20. ↑ Iqbal and Salley (2004), p. 18-6.
  21. ↑ Hirschler (2008b), p. 18-27.
  22. ↑ Purser (2002), p. 2-151.
  23. ↑ Purser (2002), p. 2-152.
  24. ↑ 24.0 24.1 24.2 24.3 Gann and Bryner (2008), p. 6-17.
  25. ↑ 25.0 25.1 25.2 25.3 25.4 25.5 25.6 Purser (2002), p. 2-121.
  26. ↑ 26.0 26.1 Purser (2002), p. 2-122.
  27. ↑ 27.0 27.1 Gann and Bryner (2008), p. 6-18.
  28. ↑ 28.0 28.1 28.2 Purser (2002), p. 2-115.
  29. ↑ Iqbal and Salley (2004), p. B-68.
  30. ↑ Iqbal and Salley (2004), p. B-69.
  31. ↑ DiNenno and Taylor (2008), p. 17-115.
  32. ↑ 32.0 32.1 DiNenno and Taylor (2008), p. 17-116.
  33. ↑ Purser (2002), p. 2-116.

References

  • Benedetti, R. P., & Colonna, G. R. (2008). Polymeric materials. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-209–6-231). National Fire Protection Association.
  • Bryan, J. L. (2008). Human behavior and fire. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 4-3–4-47). National Fire Protection Association.
  • DiNenno, P. J., & Taylor, G. M. (2008). Halon and halon replacement agents and systems. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 17-93–17-121). National Fire Protection Association.
  • Gann, R. G., & Bryner, N. P. (2008). Combustion products and their effects on life safety. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-11–6-34). National Fire Protection Association.
  • Hirschler, M. M. (2008b). Interior finish. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 18-23–18-42). National Fire Protection Association.
  • Hurley, M. J., & Bukowski, R. W. (2008). Fire hazard analysis techniques. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 3-121–3-134). National Fire Protection Association.
  • Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.
  • Lemoff, T. C. (2008). Gases. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-165–6-186). National Fire Protection Association.
  • Purser, D. A. (2002). Toxicity assessment of combustion products. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-83–2-171). National Fire Protection Association; Society of Fire Protection Engineers.
  • Van Rossum, E. (2027). Introduction to Fire Safety Engineering. Fire Safety Academy.