Load combination for fire is the combination of structural actions assumed to act while a structure is exposed to a specified fire. It connects the fire scenario to the loads that members and connections must resist. Structural fire engineering compares those demands with the capacity remaining as materials heat and deform.[1][2]
Permanent weight, occupancy-related loads and actions caused by heating are different contributions. Their combination is defined by the selected design framework and assessment objective. The NFPA Fire Protection Handbook describes several national approaches, whose factors cannot be exchanged without retaining their original assumptions. The fire case also differs from the loading used to assess a damaged building after cooling.[2][3]
A critical steel temperature is consequently a result of the member, its load and its failure mechanism. It is not one universal material temperature. Fire resistance criteria identify the performance that this assessment must demonstrate.[2]
Permanent, variable and thermal actions
Dead load is the permanent weight carried by a structure, including its own construction. Live load arises from occupancy or use and can vary in location and magnitude. The NFPA handbook explains that severe fire is treated as an unusual event in many structural design frameworks. The simultaneous design values of other actions therefore need their own definition.[4]
Reducing a variable load is an assumption about coincidence. It does not mean that fire physically removes the contents of a room at the start of heating. Storage loads can remain substantial, and escape stairs can carry people moving from other floors. The handbook's historical British load-factor table treats these conditions differently from ordinary office occupancy.[4]
The Eurocodes and the British and North American approaches described in the 2008 handbook use different combinations and assessment conventions. A factor quoted without its jurisdiction and document context is incomplete. The reported historical values describe those methods as presented in that edition. They are not a universal replacement for the applicable structural design basis.[2]
Heating can also create structural actions. Restrained expansion produces forces in adjoining members and connections, while nonuniform temperature causes curvature. A calculation that reduces gravity loads but ignores relevant restraint can miss the controlling mechanism. The load combination and the structural response model therefore answer connected parts of the same problem.[5][1]
Prestressed concrete in fire introduces an initial internal force as well as external loading. Changes in tendon properties and prestress affect the resisting mechanism. Blast-resistant design concerns a different short-duration action and its possible damage to load paths. Neither condition is represented merely by assigning an ordinary gravity-load reduction.[6][7]
A historical combination and a worked comparison
The NFPA handbook reports a United States probabilistic proposal by Ellingwood and Corotis. It combines nominal dead load, half the nominal live load and the structural action caused by fire. The expression below describes that reported proposal; the handbook separately discusses the different factors adopted in ASCE 7-05.[8]
| Symbol | Description | Unit |
|---|---|---|
| Combined action in the reported proposal | Consistent force, moment or load-intensity unit | |
| Nominal dead-load contribution | Same as | |
| Nominal live-load contribution | Same as | |
| Structural action caused by fire | Same as |
For an arithmetic illustration, the handbook's Bradford Interchange case provides an unfactored dead-load intensity of 4 kPa and live-load intensity of 5 kPa. Applying only the gravity part of the reported proposal to these intensities gives 6.5 kPa. The result combines published example inputs with a different published combination, solely to illustrate the calculation.[9]
This is not the design load used for Bradford Interchange. Its own case study reports 8 kPa at the fire limit state, under its stated design assumptions. It also provides calculated capacities for two slab arrangements. The comparison shows why a load factor cannot be copied into a case study without carrying over the governing method.[10]
The arithmetic excludes the separate thermal action represented by F. A load intensity is not automatically interchangeable with a bending moment or an axial force. Converting loads into member actions requires the structural geometry, supports and load distribution. Only compatible quantities can be combined in the same expression.[8][1]
Post-fire structural assessment asks a later question: whether the damaged structure can support the loads associated with recovery, repair or renewed use. It needs residual material properties and the remaining load paths. The reduced accidental combination used during heating does not establish the adequacy of permanent reoccupation.[11]
The functions being assessed
Fire resistance criteria identify the functions that an assembly must maintain. Structural adequacy concerns carrying the specified load without unacceptable structural response. Integrity concerns the passage of flames or hot gases through a separating assembly. Insulation concerns heat transmission to the unexposed side. These functions can reach their endpoints at different times.[12][13][14]
A separating wall illustrates the difference between integrity and insulation. Heat can conduct through an intact wall and raise the temperature of its unexposed surface. No visible opening is needed for that heat transfer to become excessive under an insulation criterion. Conversely, a crack can permit hot gases or flames to pass even where most of the wall remains comparatively cool.[15]
Structural adequacy is a further, separate question. A load-bearing member can lose strength or stiffness as its temperature rises, and its response also depends on applied loads and the conditions at its supports. A thermal result therefore cannot establish structural endurance unless it is connected to a suitable structural criterion or model.[16]
New Zealand's C/VM2, second edition of 2025, expresses the fire resistance rating through three times in minutes, and the stated order is structural adequacy, integrity and insulation. That notation makes the separate functions explicit. Other test and classification systems require their own interpretation rather than an assumed transfer of symbols or values.[14]
Critical temperature and structural endpoints
Critical steel temperature is a temperature associated with an unacceptable structural condition under stated assumptions, and it depends on the load to be supported and the material's remaining capacity. The concept can simplify a thermal calculation when those structural conditions have already been established. It does not replace them with a universal failure temperature.[17][18]
Kodur and Harmathy describe historical North American examples of 538 °C for structural steel, 593 °C for reinforcing steel and 426 °C for prestressing steel. The structural-steel example is associated with particular ASTM E119-related assumptions, including full design loading in the discussion of columns. These figures illustrate method-dependent endpoints. They do not represent melting temperatures or limits applicable to every steel member.[17]
Milke's description of A36 steel provides the mechanical context. At approximately 538 °C, its yield strength in the cited relationship is about 60% of the room-temperature value. The significance of that reduction depends on the stress already imposed on the member. A lightly loaded and a heavily loaded member need not reach their structural endpoints at the same temperature.[19]
A temperature endpoint and a structural endpoint therefore answer related questions: the thermal calculation can determine when a specified temperature is reached. A structural calculation evaluates the resulting stresses, deformation and capacity under the adopted loading and restraint. Where a temperature criterion is used, its connection to those structural conditions remains part of the method.[18][20]
Expansion, restraint and structural response
Steel expands as its temperature rises. If supports or surrounding construction limit that movement, Restrained thermal expansion changes the forces and deformations within the system. The member then responds to more than its original mechanical loading. Milke consequently includes thermal expansion and end conditions in the structural assessment.[21]
Test restraint is a defined condition rather than an informal description of a connection. Milke reproduces historical ASTM examples distinguishing different floor and framing arrangements, and the classification considers how the surrounding structure resists movement. A restrained test result therefore requires interpretation in relation to the proposed construction and its actual boundaries.[22]
Temperature gradients add another complication: a beam beneath a slab can have a hotter lower flange and a cooler upper flange. A uniform-temperature model does not explicitly describe that difference. Where the gradient affects the structural question, Milke identifies the need for a more suitable analytical approach.[23]
Structural fire engineering combines these effects rather than treating steel temperature as a complete outcome, and it uses the exposure to calculate temperatures, then applies temperature-dependent properties within a structural model. Loads, geometry and end conditions determine how the member responds. The required result may involve deformation and stability as well as a nominal strength comparison.[24]
Beams, slabs and structural continuity
A simply supported slab provides a useful starting model: its ends permit expansion and rotation under the idealised support conditions described by Fleischmann and Buchanan. As reinforcement heats and weakens, the section's resistance to bending decreases. Structural failure is assessed by comparing that remaining resistance with the bending demand from the applied load.[25]
Concrete near the compression face may remain cooler than reinforcement near the fire-exposed underside. The structural calculation therefore uses the temperature distribution, rather than applying one reduction to the entire section. If part of the compression zone becomes sufficiently hot, the source method reduces its contribution. That step depends on the chosen material model and calculation procedure.[25]
A continuous member behaves differently because it can redistribute bending moments between the span and its supports. Redistribution can extend endurance, but the remaining sections must still resist the transferred demand. Fleischmann and Buchanan describe failure through the formation of a mechanism involving several yielding regions. Continuity is therefore a structural condition, not an automatic allowance added to a rating.[26]
Structural fire engineering combines this structural response with the preceding fire and thermal calculations. The assessment depends on loads, geometry, reinforcement and support conditions as well as temperature. More specialised structural behaviour is addressed in the related topic Tensile membrane action. The heat-penetration example above does not calculate any redistribution or membrane resistance.[27][28]
Calculation methods and validation
Structural fire engineering connects fire exposure, heat transfer and structural response. The first stage defines the thermal environment. The second calculates temperatures within the member, using material properties and boundary conditions. The third evaluates the consequences for stresses, deformation and load-carrying capacity. A calculation of one stage does not independently establish the others.[29]
Empirical correlations provide a simpler route where sufficient test data exist. Milke explains that such correlations are limited by the exposure, loading and span represented in their underlying tests. Their numerical simplicity does not remove those limits. Applying a correlation outside its supporting range introduces a different problem from interpolating within the tested conditions.[29]
Thermal models can represent either standard exposure or a specified nonstandard fire, and their output may be the time to a chosen temperature or a temperature distribution for structural analysis. Temperature-dependent properties and the description of heating both affect accuracy. A model with detailed geometry can still produce a misleading result if those physical inputs are unsuitable.[29]
Testing remains relevant even where calculation is available, and it supplies material behaviour, checks assembly interactions and provides evidence for judging model predictions. New Zealand's 2025 C/VM2 definition explicitly connects its calculation route to verification against standard fire-resistance tests. That connection identifies the evidence supporting a rating rather than treating calculation as evidence by itself.[13][14]
How a furnace test establishes a rating
A Fire resistance test exposes a defined specimen to a prescribed heating history while monitoring the required endpoints. Milke describes this approach through the United States ASTM E119 framework in the 2002 handbook, and a successful specimen receives a rating for the stated test duration and conditions. The rating belongs to the tested assembly and its permitted applications.[16]
The specimen can include several materials and components. Protection around a steel member, for example, changes the heat entering the steel and its temperature history, and the test observes the interaction between the protection and the member. This is one reason separate material properties do not always reproduce the behaviour of an assembled construction.[16]
Loads and restraint form part of the test arrangement. Restraint describes the extent to which surrounding construction prevents thermal movement. Milke explains that framing geometry and connections affect the distinction between restrained and unrestrained test systems. A result obtained under one arrangement cannot automatically represent another arrangement with different movement conditions.[13]
The monitored endpoints also depend on the assembly. They can include maintaining the applied load, limiting temperatures and preventing the passage of flames or gases capable of igniting a specified target. Some historical ASTM procedures include a hose-stream exposure. These observations have distinct purposes, so a report identifies which endpoints and procedures apply to its specimen.[13]
An unlisted assembly and a failed assembly are not the same evidential category. Milke explains that an assembly without a listing has no established rating unless acceptable performance is demonstrated. That demonstration may involve a standard test, a special experiment or an analytical method. Absence of a rating therefore concerns the available evidence, rather than an observed failure time.[29]
See also
Notes
- ↑ 1.0 1.1 1.2 Fleischmann and Buchanan (2002), pp. 4-245–4-246.
- ↑ 2.0 2.1 2.2 2.3 Cote et al. (2008), §19.5, pp. 19-93–19-94.
- ↑ Cote et al. (2008), §19.4, pp. 19-65, 19-70.
- ↑ 4.0 4.1 Cote et al. (2008), §19.5, p. 19-93.
- ↑ Cote et al. (2008), §19.2, p. 19-53.
- ↑ Cote et al. (2008), §19.2, pp. 19-53–19-54.
- ↑ Cote et al. (2008), §2.8, pp. 2-95–2-97.
- ↑ 8.0 8.1 Cote et al. (2008), §19.5, p. 19-94.
- ↑ Cote et al. (2008), §19.5, pp. 19-94, 19-114.
- ↑ Cote et al. (2008), §19.5, p. 19-114.
- ↑ Cote et al. (2008), §19.4, pp. 19-65, 19-69–19-70.
- ↑ Kodur and Harmathy (2002), p. 1-155.
- ↑ 13.0 13.1 13.2 13.3 Milke (2002), pp. 4-210–4-211.
- ↑ 14.0 14.1 14.2 Ministry of Business, Innovation and Employment (2025), p. 64.
- ↑ Australian Building Codes Board et al. (2005), p. 1.6-7.
- ↑ 16.0 16.1 16.2 Milke (2002), pp. 4-209–4-210.
- ↑ 17.0 17.1 Kodur and Harmathy (2002), p. 1-163.
- ↑ 18.0 18.1 Milke (2002), p. 4-209.
- ↑ Milke (2002), p. 4-212.
- ↑ Milke (2002), p. 4-222.
- ↑ Milke (2002), pp. 4-209–4-211.
- ↑ Milke (2002), pp. 4-210–4-211.
- ↑ Milke (2002), pp. 4-223–4-224.
- ↑ Milke (2002), pp. 4-209–4-210.
- ↑ 25.0 25.1 Fleischmann and Buchanan (2002), p. 4-245.
- ↑ Fleischmann and Buchanan (2002), p. 4-246.
- ↑ Fleischmann and Buchanan (2002), p. 4-239.
- ↑ Fleischmann and Buchanan (2002), pp. 4-245–4-246.
- ↑ 29.0 29.1 29.2 29.3 Milke (2002), p. 4-209.
References
- Australian Building Codes Board, National Research Council of Canada, International Code Council, & Department of Building and Housing New Zealand. (2005). International fire engineering guidelines. Australian Building Codes Board.
- Cote, A. E., Grant, C. C., Hall, J. R., Jr., & Solomon, R. E. (Eds.). (2008). Fire protection handbook (20th ed.). National Fire Protection Association.
- Fleischmann, C., & Buchanan, A. (2002). Analytical methods for determining fire resistance of concrete members. In P. J. DiNenno (Ed.), SFPE handbook of fire protection engineering (3rd ed., pp. 4-239–4-256). National Fire Protection Association.
- Kodur, V. K. R., & Harmathy, T. Z. (2002). Properties of building materials. In P. J. DiNenno (Ed.), SFPE handbook of fire protection engineering (3rd ed., pp. 1-155–1-181). National Fire Protection Association.
- Milke, J. A. (2002). Analytical methods for determining fire resistance of steel members. In P. J. DiNenno (Ed.), SFPE handbook of fire protection engineering (3rd ed., pp. 4-209–4-238). National Fire Protection Association.
- Ministry of Business, Innovation and Employment. (2025). C protection from fire: Verification method C/VM2 (2nd ed.).