A floating-roof tank is a storage tank for flammable liquids whose roof floats on the surface of the liquid and moves up and down with the liquid level.[1] Because the roof rests on the liquid, there is normally no vapour space between roof and liquid during storage, which limits vapour loss and reduces the fire hazard.[2][3] Two forms are described: the open-top floating-roof tank, whose roof is exposed to the weather, and the covered floating-roof tank, which has a fixed steel roof above the floating one.[1][3] The usual fire in such a tank is a small fire in the seal space between the edge of the roof and the shell, which lightning can start.[4][3] A full-surface fire can result if the roof sinks, and explosions can occur when an almost empty tank has its roof resting on its supports.[4] The requirements summarised here are US codes and practice (NFPA 11, NFPA 30 and NFPA 780) as described in the Fire Protection Handbook (2008) and the SFPE Handbook (2002).

Definition and types

The SFPE Handbook defines floating roof tanks by contrast with single roof tanks. They have a cover or roof over the flammable liquid that floats on the liquid surface and moves vertically with the liquid level in the tank.[1] The Fire Protection Handbook lists the floating roof tank among the common types of atmospheric storage tank, with a roof deck that rests on the liquid.[5] Atmospheric tanks are designed for gauge pressures of 0 to 1.0 psig (0 to 6.9 kPa).[5]

If the floating roof is open to the atmosphere, the tank is called an open-top floating roof tank. If a permanent cover is placed over the whole tank, it is a covered floating roof tank.[1] Scheffey describes the covered type as totally enclosed above the floating roof by a properly vented steel roof.[3] Ordile uses the related term "cone roof tanks with internal floating roofs".[5]

Floating roofs are mainly used for the more volatile liquids. Scheffey notes that Class IB flammable liquids, such as gasolines and crudes, are usually stored in open-top or covered floating-roof tanks. Class II and III combustible liquids are usually stored in fixed-roof tanks.[3] The classes are those of the US code NFPA 30, as described in the 2008 handbook.

Purpose: vapour conservation and fire safety

A fixed-roof tank must vent vapour during filling and draw in air during emptying, and its vapour space may lie in the flammable range.[5][6] Under a floating roof there is no vapour space during normal storage.[3] Ordile writes that floating roof tanks minimise vapour loss and tend to reduce the fire hazard.[2][5] Floating roof tanks, cone roof tanks with internal floating roofs, lifter roof tanks and vapour dome tanks are all used to conserve the vapour of Class I liquids.[5]

The benefit is greatest for liquids whose vapour is normally flammable inside a fixed-roof tank. Ordile names ethyl and methyl alcohol and JP-4 (Jet B) turbine fuel, with vapour pressures of about 14 to 28 kPa at 38 °C (2 to 4 psia at 100 °F). For these liquids, storage in floating roof or similar tanks, or inert gas in the vapour space, is desirable to reduce the chance of an internal explosion.[5]

The floating roof also changes the code treatment of the tank. As described in the 2008 handbook, the provision of floating roofs negates the need for emergency relief venting, which fixed-roof tanks need against exposure fires.[7] Floating roof tanks provide greater fire safety for aboveground installations. For that reason the handbook notes that they are permitted closer to a property line than other types of tanks.[4]

Roof seals

A perimeter seal closes the gap between the edge of the floating roof and the tank shell. It keeps flammable vapour from escaping into the atmosphere and collecting above the floating roof.[1] The SFPE Handbook lists three seal devices: a mechanical shoe seal or pantograph-type seal, a metal weather shield, and a metal secondary seal. Some of these devices need a foam dam when the tank has fixed foam protection.[1]

The Fire Protection Handbook illustrates a double-seal system. A primary seal envelope containing resilient foam fills the gap between the roof rim and the tank shell at the fuel level. Above it, a secondary seal on a support plate closes the gap again, with a stainless steel shunt against the shell. The roof itself has a top deck and a bottom deck joined by the rim, with a bumper at the base of the rim.[4]

Ordile calls a good tank roof and seal maintenance programme, with proper tank operating procedures, the best way to prevent the problems that lead to fires.[4] Fire protection equipment should be installed on tanks where needed, following NFPA 11.[4] The design of that equipment is described below.

Fire and explosion scenarios

Rim seal fires. When fires occur in floating roof tanks, they are normally restricted to the seal space between the roof and the shell.[4] The SFPE Handbook calls a fire in the seal area the basic fire problem of these tanks and notes that its surface area is typically quite small.[1] In an open-top tank, a rim of fire is all that can be expected. Such fires can be put out with portable extinguishers or handheld foam lines.[4][3] A serious exposure fire can start a rim fire in either type of floating-roof tank.[3] NUREG-1805 (2004) also notes that rim fires can occur on both open and closed floating roof tanks.[8]

Lightning. Rim fires may be caused by atmospheric disturbances such as lightning. According to Scheffey, they usually do not occur if the floating roof is bonded properly to the shell as specified in NFPA 780. Covered floating-roof tanks do not suffer them, because of the "Faraday effect" of the fixed roof.[3] Caloggero adds that direct hits can ignite vapours escaping from metal floating roof tanks, and nearby strokes can induce sparks.[9]

Floating roof tanks with hangers in the vapour space can be protected by bonding the roof to the seal shoes at 3.05 m (10 ft) intervals around the circumference. Insulated joints or jumper bonds are added around each pinned joint of the hanger mechanism.[9] Floating roof tanks without vapour spaces do not appear to need lightning protective measures.[9] For steel tanks at atmospheric pressure in general, Caloggero lists conditions for reasonable protection. They include closed vapour openings or flame arresters, and a tank and roof of sheet steel at least 4.8 mm (3/16 in.) thick that strokes cannot burn through.[9] The wider subject is treated in Lightning protection system.

Worked example. The SFPE Handbook design example uses a tank 36.6 m (120 ft) in diameter.[10] If such a tank had a floating roof with hangers in the vapour space, its circumference of π × 36.6 = 114.9 m (377 ft) would need bonds at 3.05 m (10 ft) intervals.[9] Dividing gives 37.7, rounded up to 38 bonds between roof and seal shoes. For a 61 m (200 ft) tank the same rule gives 63 bonds. The number grows in proportion to the diameter.

Static electricity from foam. NUREG-1805 reports that Howells (1993) described several incidents in which foam injection appears to have ignited volatile refined products in a floating roof storage tank. He suggested two ways of generating the charge: water droplets settling through the hydrocarbon liquid, and the streaming current of the foam mixture leaving the nozzle.[11]

Vapour space under a landed roof. A floating roof cannot follow the liquid all the way to the bottom, and rests on low-level supports in an almost empty tank. A flammable vapour space then forms beneath the roof, and explosions have occurred in this state.[4] During initial filling, a flammable vapour space also exists until the roof becomes buoyant.[3] In a covered tank, the space between the fixed and the floating roof will be within the flammable range during initial fill and possibly longer. How long depends on the atmospheric temperature, the wind and the vapour pressure of the product.[3]

Sunken roof and full-surface fire. Full-surface fires can result from the roof sinking. Ordile lists as causes a roof that hangs up because of overfilling or obstructions in the tank, excessive snow or rainwater on the roof, and excessive water or foam from fire fighting.[4] Once the roof has sunk, the whole liquid surface can burn as a large pool fire.[4] With certain crude oils, a boilover may follow after a long period of quiet burning, when boiling water at the tank bottom forms a steam-oil froth that ejects part of the oil.[12]

Fire protection

Because the fire record is good, fixed protection is usually not required. The SFPE Handbook describes the fire experience with floating roof tanks as very good. Fixed foam outlets are therefore not generally required on open-top or covered floating roof tanks.[1] The Fire Protection Handbook states that the floating-roof storage tank has a good chance of freedom from fire, so fixed foam systems are usually not required. A foam-flooding system for the rim area may still be needed in some circumstances.[3] NUREG-1805 gives the same picture, with rim fires as the one exception.[8]

Where an oil company or the fire authority wants protection for an open-top tank, the SFPE Handbook describes three techniques. In the portable nozzle method, highly trained personnel take a hose line to the top of the tank and apply firefighting foam to the seal area by hand.[1] In the catenary system, foam makers are spaced around the roof near the seal. They are fed through a flexible hose that rides with the access stairway, which moves on tracks as the roof rises and falls.[1] Foam can be discharged under the seal directly onto the liquid or above the seal.[1]

The third technique is the fixed foam maker method. Piping runs around the outside wall of the tank and feeds foam makers mounted above the rim. The number of discharge points depends on the circumference.[1][13] A foam dam, normally 305 to 610 mm (12 to 24 in.) high, holds the foam over the seal or weather shield.[13] The Fire Protection Handbook describes the same arrangement: aspirating foam makers flood the annular area covered by the seal, and a metal foam dam may be needed. Construction details are given in the appendix of NFPA 11.[3]

For the foam application rate of these systems the SFPE Handbook refers to NFPA 11, and neither handbook gives a value for seal protection. The SFPE Handbook gives 0.1 gpm/ft² (4.07 L/min per m²) only as the minimum rate for the whole liquid surface of a hydrocarbon tank. It warns that other methods may need different rates.[10] For covered floating-roof tanks, both handbooks point to the systems used for fixed-roof tanks where protection is wanted.[13][3]

Subsurface foam injection, in which foam is pumped in at the base of the tank and rises through the fuel, is not recommended for floating-roof tanks. A tilted or sunken roof can stop the foam from spreading properly.[3][1][8] Large mobile monitors are one way to reach a full-surface fire from outside the tank. Monitors with capacities up to 15,144 L/min (4,000 gpm) have extinguished hydrocarbon fires in tanks up to 60 m (195 ft) in diameter.[14] Excess water or foam from fire fighting is itself one of the listed causes of roof sinking.[4]

Limits and common misconceptions

A floating roof does not make a tank fire-proof. It removes the vapour space only while the roof floats, and the empty, landed and filling states bring the vapour space back.[4][3] Nor does the good fire record of these tanks mean that every fire stays small. A sunk roof turns a seal fire problem into a full-surface fire, which for crude oil can end in boilover.[4][12]

The sources also differ in emphasis. The Fire Protection Handbook treats lightning as a cause of rim fires that proper bonding usually prevents. Caloggero states that floating roof tanks without vapour spaces do not appear to need lightning protective measures at all.[3][9] The bonding of the roof to the shell or the seal shoes is the common element of both. All requirements above are US practice of about 2002 to 2008. The handbook text names NFPA 11, NFPA 30 and NFPA 780 without stating their editions, and current editions and other national codes may differ.

See also

Notes

  1. ↑ 1.00 1.01 1.02 1.03 1.04 1.05 1.06 1.07 1.08 1.09 1.10 1.11 1.12 Scheffey and Hickey (2002), p. 4-127.
  2. ↑ 2.0 2.1 Ordile (2008), p. 7-15.
  3. ↑ 3.00 3.01 3.02 3.03 3.04 3.05 3.06 3.07 3.08 3.09 3.10 3.11 3.12 3.13 3.14 3.15 3.16 Scheffey (2008), p. 17-62.
  4. ↑ 4.00 4.01 4.02 4.03 4.04 4.05 4.06 4.07 4.08 4.09 4.10 4.11 4.12 4.13 Ordile (2008), p. 7-23.
  5. ↑ 5.0 5.1 5.2 5.3 5.4 5.5 5.6 Ordile (2008), p. 7-16.
  6. ↑ Ordile (2008), p. 7-18.
  7. ↑ Ordile (2008), p. 7-20.
  8. ↑ 8.0 8.1 8.2 Iqbal and Salley (2004), p. B-62.
  9. ↑ 9.0 9.1 9.2 9.3 9.4 9.5 Caloggero (2008), p. 11-78.
  10. ↑ 10.0 10.1 Scheffey and Hickey (2002), p. 4-130.
  11. ↑ Howells (1993), as cited in Iqbal and Salley (2004), p. B-60.
  12. ↑ 12.0 12.1 Slye (2008), p. 6-205.
  13. ↑ 13.0 13.1 13.2 Scheffey and Hickey (2002), p. 4-128.
  14. ↑ Scheffey (2008), p. 17-61.

References

  • Caloggero, J. M. (2008). Lightning protection systems. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 11-69–11-81). National Fire Protection Association.
  • Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.
  • Ordile, A. M. (2008). Storage of flammable and combustible liquids. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 7-15–7-33). National Fire Protection Association.
  • Scheffey, J. L. (2008). Foam extinguishing agents and systems. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 17-45–17-70). National Fire Protection Association.
  • Scheffey, J. L., & Hickey, H. E. (2002). Foam system calculations. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 4-123–4-148). National Fire Protection Association; Society of Fire Protection Engineers.
  • Slye, O. M., Jr. (2008). Flammable and combustible liquids. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-197–6-208). National Fire Protection Association.