A fire-resistant hydraulic fluid is a hydraulic fluid that presents a lower fire hazard than petroleum oil. The Fire Protection Handbook (2008) calls these fluids "less hazardous hydraulic fluids, referred to as fire-resistant fluids".[1] They represent a lower fire hazard than petroleum oils or synthesised hydrocarbons, but all of them will ignite under certain conditions.[1] Petroleum oil remains the most common hydraulic medium. Under pressure it presents a considerable fire hazard where ignition sources are always present, as in die casting, plastic moulding, heat treating and steel production.[2] A failed hose or fitting releases an atomised spray that ignites readily and burns as a torch-like flame with a very high rate of heat release.[3] The main fire-resistant types are water-glycol fluids, water-in-oil emulsions, and synthetic fluids such as phosphate esters and polyol esters.[4] Their fire resistance is often certified by FM Approvals with a spray flammability test.[4] It can be lost in service through loss of water, contamination or degradation.[4]

Definition

Neither the SFPE Handbook nor Introduction to Fire Safety Engineering defines the term, so the definition here follows the NFPA Fire Protection Handbook (2008). Its chapter on fluid power uses "less hazardous hydraulic fluids" and "fire-resistant fluids" as synonyms. These fluids represent a lower fire hazard than petroleum oils or synthesised hydrocarbon fluids, but all will ignite under certain conditions.[1] The chapter on metalworking describes their behaviour in a fire. Less hazardous fluids will burn when they are released at high pressure and meet a source of ignition. They do not, however, sustain combustion once that ignition source is removed.[5]

The term therefore describes a degree of fire resistance, not non-combustibility. The handbook stresses that no single test reflects that degree of resistance under all conditions met in industrial and mobile use.[3] Similar wording appears for other fields. Aircraft hydraulic systems use "fire-resistive" fluids, and in underground mines "fire resistive hydraulic fluids" are among the less hazardous materials that are sometimes required.[6][7]

The hazard of petroleum hydraulic oil

Fluid power systems transmit power or motion to parts of machines. A hydraulic press multiplies force, die casting machines use the fluid for actuation, and other machines use it for remote control.[2] Early systems used water as the medium. Water corroded the metal parts and lacked lubricity, so it was replaced by petroleum oil. Apart from its fire hazard, oil is an ideal hydraulic fluid: it is noncorrosive, compatible with many materials, cheap and recyclable.[2]

The fire hazard is set by the oil's properties and the pressure. Petroleum hydraulic oils have a flash point of 148 to 316 °C (300 to 600 °F) and an autoignition temperature of 260 to 399 °C (500 to 750 °F).[2] Synthesised hydrocarbon fluids, such as polyalphaolefins, have flash points of about 106 to 260 °C (225 to 500 °F).[2] High-pressure piping and hose carry the oil at up to 10,000 psi, given as 68,950 kPa.[2] Machine tools use from 400 psi to several thousand psi.[5] Plastics moulding machines normally stay below 2000 psi (13.8 MPa).[8]

Oil escapes mainly through failures of piping at threaded sections, of components, gaskets or fittings, through tubing pulling out of fittings, and through rupture of flexible hose.[2][3] Poorly supported piping can vibrate and move, repeated flexing and abrasion create weak spots in rubber hose, and tubing can be cut by torches, hit by forklift trucks or stepped on. Accumulators can still hold high-pressure fluid after the system is shut down.[3] The released oil forms an atomised spray of mist or droplets that may cover large areas. The spray ignites readily, and the result is usually a torch-like jet fire with a very high rate of heat release.[3]

A fire at the Fort St. Vrain nuclear power plant in the United States shows the sequence. On 2 October 1987 a filter bowl failed, and petroleum-based hydraulic oil at about 3,000 psig (20.7 MPa) sprayed close to 15 ft (4.6 m) onto hot exposed steel.[9] The oil ignited because the hot surfaces were above its autoignition point. An operator put the fire out with a portable dry chemical extinguisher. He did not close the valve feeding the failed filter, so the oil kept spraying and the fire re-ignited, reaching about 8 ft by 3 ft (2.4 m by 0.9 m).[9] In plastics plants, the same petroleum fluids have been used where heaters stay below about 315 °C (600 °F). They have a poor fire record in die casting, where the molten metal is far hotter than the ignition temperature of the fluid.[8]

Types of fire-resistant fluid

The fire-resistant fluids fall into two families: fluids that contain water, and synthetic fluids without water. In the water-containing fluids, loss of water reduces the fire resistance, so makeup water is needed at higher temperatures.[4] The international standards body ISO has given every class of hydraulic fluid a symbol, now used on containers and data sheets.[4]

Tree diagram of hydraulic fluid classes: mineral oils versus water-containing and synthetic fire-resistant fluids with ISO symbols
Classes of hydraulic fluid with their ISO symbols.
ISO symbol Composition, as listed in the handbook
HFAE Oil-in-water emulsions, typically more than 80 % water (coolants)
HFAS Chemical solutions, typically more than 80 % water (coolants)
HFB Water-in-oil emulsions
HFC Water-glycol fluids
HFDR Phosphate esters
HFDU Polyol esters

The table is taken from the ISO classification printed in the handbook, which also lists mineral oils (HH, HL, HM, HV) and environmentally acceptable fluids (HETG, HEPG, HEES, HEPR). The handbook text describes only the water-in-oil, water-glycol and synthetic types; HFAE and HFAS appear in its table only, as coolants.[1]

Water-glycol fluids normally contain 35 to 50 percent water with ethylene or propylene glycol, thickeners and additives. The recommended temperature range is −18 to 66 °C (0 to 150 °F), with normal operation at 49 to 54 °C (120 to 130 °F). At higher temperatures water evaporates quickly and makeup water must be added often. As the water evaporates, the viscosity rises and the fire resistance falls.[4] Water-in-oil emulsions contain 35 to 40 percent water dispersed as fine droplets in petroleum oil, with emulsifiers and additives. Their recommended range is 10 to 66 °C (50 to 150 °F). Loss of water lowers the viscosity and increases the flammability.[4]

Synthetic fluids are man-made liquids without water: phosphate esters, blends of phosphate esters with petroleum oil, and polyol esters. Their recommended range is −7 to 66 °C (20 to 150 °F), again with normal operation at 49 to 54 °C.[4] Phosphate esters are not used extensively throughout the world because of problems with degradability and disposal.[4] A separate group of environmentally acceptable fluids, such as vegetable oils, polyglycols, synthetic esters and synthetic hydrocarbons, serves where leaks could contaminate the ground. These fluids generally have flash points of 210 to 249 °C (410 to 480 °F).[4]

Fire performance and testing

Several test methods have long been used to rate the fire resistance of less hazardous hydraulic fluids. The handbook lists linear flame propagation, autoignition temperature, high-pressure spray flammability, flash point, and the Factory Mutual hot channel ignition test. None of them, alone or sometimes together, reflects the fire resistance achieved under the conditions met in practice.[3]

According to the handbook, perhaps the most respected certification is by Factory Mutual Approvals, a business unit within FM Global. Many industrial facilities require this certification, and some property insurers require it before they insure a plant.[4] A revised standard, CN 6930, was introduced early in 2002. It defines the test commonly known as the spray flammability parameter (SFP). Parameters measured while the fluid is ignited go into an equation that gives the SFP value, and fluids are classified by that number.[4] The handbook notes that there were still unresolved issues with the test, prompting revisions. It also considered a single, universally accepted test method unlikely in the near future.[4]

Large-scale spray tests show how much the fluid types differ. The SFPE Handbook reports heats of combustion measured in high-pressure liquid spray combustion in a fire products collector of 10,000 kW scale.[10] Two quantities are given. The net heat of complete combustion, ΔHT, is the heat released per unit mass if the fuel burns completely. The chemical heat of combustion, ΔHch, is the heat actually released per unit mass in the fire.[11] Their ratio is the combustion efficiency.[12]

Fluid (spray combustion) ΔHT (kJ/g) ΔHch (kJ/g) Combustion efficiency (calculated)
Mineral oil 46.0 44.3 0.96
Organic polyol esters (4 fluids) 35.7–40.3 35.1–37.2 0.92–0.98
Phosphate esters (2 fluids) 31.8–32.0 29.3–29.6 0.92–0.93
Polyglycol-in-water (4 fluids) 11.0–14.7 10.4–12.2 0.83–0.95
Water-in-oil emulsion (1 fluid) 27.6 2.5 0.09

Values from Tewarson (2002), Table 3-4.14; combustion efficiencies calculated as ΔHch/ΔHT.[10]

The data show two different mechanisms. Polyol and phosphate esters burn almost completely once ignited, but release less heat per kilogram than mineral oil. The tested water-in-oil emulsion could in principle release 27.6 kJ/g, yet released only 2.5 kJ/g in the spray test. The polyglycol-in-water fluids have a low heat of combustion to begin with.[10]

Paired bar chart of complete and chemical heat of combustion for mineral oil, esters and water-containing hydraulic fluids
Heat of complete combustion and chemical heat of combustion of hydraulic fluids in spray tests.

Heat release of a spray fire: worked example

The chemical heat release rate of a spray fire can be estimated from the rate at which fluid leaks and burns. Tewarson defines the chemical heat of combustion as the ratio of the chemical heat release rate to the mass loss rate.[11] For a spray in which all leaking fluid burns, the mass loss rate is the leak rate, so: Q˙ch=m˙ΔHchandχ=ΔHchΔHT

Symbol Description Unit
Q˙ch chemical heat release rate of the fire kW
m˙ mass rate of fluid leaking and burning kg/s
ΔHch chemical heat of combustion (1 kJ/g = 1000 kJ/kg) kJ/g
ΔHT net heat of complete combustion kJ/g
χ combustion efficiency –

As a worked example, assume a leak of 0.05 kg/s, or 3 kg per minute, from a failed hose. The leak rate is an assumption for illustration and is not taken from a source. With mineral oil the fire releases about 0.05 × 44,300 = 2,200 kW. A phosphate ester gives about 1,500 kW and a polyol ester 1,800 to 1,900 kW. A polyglycol-in-water fluid gives 520 to 610 kW, and the tested water-in-oil emulsion about 130 kW.[10] The esters thus cut the heat release of the same leak by only about 15 to 35 percent. The water-containing fluids cut it by roughly 70 to 95 percent.

Bar chart of heat release rate of a 0.05 kg/s hydraulic spray leak: mineral oil about 2.2 MW, emulsion about 0.13 MW
Heat release rate of an assumed 0.05 kg/s spray leak for different hydraulic fluids.

The estimate holds only while the spray keeps burning. It assumes that the whole leak burns and that the spray is ignited by a strong, continuous source. The handbook notes that less hazardous fluids stop burning once the ignition source is removed, so for them the estimate applies only while a strong ignition source remains.[5] The heats of combustion come from one apparatus and from a few commercial fluids each.[10]

Applications

Fire-resistant fluids are used where a hydraulic leak would meet a strong ignition source. In plastics plants, water-glycol fluids, water-oil emulsions and synthetic fluids are available for moulding machines. Any change from petroleum fluid should follow the recommendations of the makers of the hydraulic components.[8] For oil quenching and heat treating, the handbook (2008), describing United States practice, states that hydraulic control systems add to the fire hazard near high-temperature equipment and that fire-resistant hydraulic fluids should be used. Where combustible oils must be used, proper maintenance is vital.[13]

Power generation offers further examples. In some larger gas turbines, the combustible lubricating oil may be replaced with a synthetic fire-resistant fluid with a higher flash point, which reduces the chance that a spill ignites on hot engine parts.[14] In steam turbine generators, hydraulic control systems shared with the lubrication oil work at up to 1600 psi (11.0 MPa) and can cause spray fires. Units built after the early 1970s mostly use a separate electrohydraulic control system with a less flammable synthetic fluid such as a phosphate ester. According to the handbook this has nearly eliminated the hazard.[15]

Mines and aircraft follow the same principle. In United States mining practice described in the handbook, less hazardous materials are preferred, or in some cases mandated by law, where suitable substitutes exist. Fire resistive hydraulic fluids, conveyor belting, hydraulic hoses and ventilation tubing are all required in underground mines under certain conditions.[7] Belting is treated under Conveyor fire protection. The handbook also notes that coal mine fires remain common in some parts of the world. It attributes this primarily to extremely hard use of hydraulic equipment without proper maintenance, and adds that, because of fluid and maintenance costs, many systems have not been converted to safer fluids.[2] Aircraft hydraulic systems use fire-resistive fluids with autoignition temperatures above 538 °C (1000 °F), which are only slightly flammable. Older mineral-oil-based fluids are still widely used, particularly in military aircraft.[6]

Limits, maintenance and compatibility

Fire resistance is not permanent. Some fluids that pass the FM Approvals test lose their fire resistance in use through degradation. Oil, solvents or process fluids can also enter the system by accident or through poorly marked containers.[4] The handbook names poor fluid maintenance, mainly loss of water from water-containing fluids, as a very common problem. Evaporation can seriously reduce their fire resistance.[4]

Changing fluids also affects the rest of the system. Phosphate esters and their blends are not compatible with seals, gaskets or hoses made from nitrile, neoprene or natural rubber, which must be replaced by fluorocarbon or other compatible materials.[4] Nitrile seals used with phosphate esters soften and swell, fail and release fluid.[2] Polyol esters are compatible with nitrile and fluorocarbon. All synthetics typically attack paints, coatings and electrical insulation. Water-glycols are incompatible with certain types of leather, cork and paper, and for water-in-oil emulsions seals or gaskets of cork, paper, leather or butyl are unacceptable. Both generally have a solvent action on most petroleum-compatible paints and coatings.[4]

A high flash point does not rule out every ignition mode. The SFPE Handbook notes that hydraulic fluids designed for non-flammability, with extremely high flash points, can still ignite spontaneously if they leak onto thermal lagging such as mineral wool or fibreglass. The very high surface area of the lagging allows this.[16]

Protection of hydraulic systems

The handbook gives additional recommendations for systems that contain oil, on top of those for less hazardous fluids. They describe United States practice around 2007–2008. Automatic sprinklers should cover areas with oil hydraulic systems. Because of the high-pressure atomised oil fire, the sprinkler design area is often 5000 to 7500 ft² (465 to 697 m²).[3] Where more than 100 gal (378 L) of fluid is involved, automatic or remote manual switches should shut off the pumps in a fire. Heat detectors or fusible links over the reservoir, pump and piping can trip the pump. A low-level switch in the reservoir acts more slowly and is acceptable in some conditions, such as outdoors.[3]

The other measures address leaks and ignition sources. Threaded piping should be avoided or its fittings seal-welded, and rubber or synthetic hose should be armoured or enclosed in metal tube. Machines should be isolated from ignition sources such as metal castings and open flames, Class B extinguishers provided, and systems inspected regularly.[3] Staff near an intense hydraulic fire tend to run without stopping the pump, so remote or automatic shutoff is preferred. Automatic shutoff can use a low-level switch, an excess flow switch, a flame detector, a fusible link or thermostat, or the sprinkler waterflow switch.[5] If a building is not fully sprinklered, sprinklers should extend at least 20 ft (6 m) beyond all areas of hydraulic use.[5]

Schematic of a hydraulic power unit with a failed hose spraying oil onto a hot surface, with shutoff, detection and sprinkler measures
Hydraulic spray fire scenario and the main protective measures.

See also

Notes

  1. ↑ 1.0 1.1 1.2 1.3 Schacht (2008), p. 8-116.
  2. ↑ 2.0 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 Schacht (2008), p. 8-113.
  3. ↑ 3.0 3.1 3.2 3.3 3.4 3.5 3.6 3.7 3.8 Schacht (2008), p. 8-114.
  4. ↑ 4.00 4.01 4.02 4.03 4.04 4.05 4.06 4.07 4.08 4.09 4.10 4.11 4.12 4.13 4.14 4.15 4.16 Schacht (2008), p. 8-115.
  5. ↑ 5.0 5.1 5.2 5.3 5.4 Dobbs (2008), p. 9-70.
  6. ↑ 6.0 6.1 Boucher (2008), p. 21-139.
  7. ↑ 7.0 7.1 L. J. Moore (2008), p. 9-216.
  8. ↑ 8.0 8.1 8.2 Ouellette (2008), p. 9-63.
  9. ↑ 9.0 9.1 Iqbal and Salley (2004), p. H-14.
  10. ↑ 10.0 10.1 10.2 10.3 10.4 Tewarson (2002), p. 3-115.
  11. ↑ 11.0 11.1 Tewarson (2002), p. 3-103.
  12. ↑ Tewarson (2002), p. 3-102.
  13. ↑ Ostrowski (2008b), p. 8-97.
  14. ↑ Biggins (2008), p. 8-107.
  15. ↑ Sheridan (2008), p. 9-185.
  16. ↑ Gray (2002), p. 2-224.

References

  • Biggins, J. B. (2008). Stationary combustion engines and fuel cells. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 8-105–8-111). National Fire Protection Association.
  • Boucher, B. (2008). Aviation. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 21-135–21-149). National Fire Protection Association.
  • Dobbs, P. G. (2008). Metalworking processes. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-67–9-72). National Fire Protection Association.
  • Gray, B. (2002). Spontaneous combustion and self-heating. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-211–2-228). National Fire Protection Association; Society of Fire Protection Engineers.
  • Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.
  • Moore, L. J. (2008). Mining and mineral processing. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-203–9-223). National Fire Protection Association.
  • Ostrowski, R. (2008b). Oil quenching and molten salt baths. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 8-93–8-103). National Fire Protection Association.
  • Ouellette, G. (2008). Plastics industry and related process hazards. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-53–9-65). National Fire Protection Association.
  • Schacht, P. K. (2008). Fluid power systems. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 8-113–8-116). National Fire Protection Association.
  • Sheridan, D. J. (2008). Electric generating plants. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-179–9-189). National Fire Protection Association.
  • Tewarson, A. (2002). Generation of heat and chemical compounds in fires. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 3-82–3-161). National Fire Protection Association; Society of Fire Protection Engineers.