The flooring radiant panel test is a fire test that measures how much radiant heat a floor covering needs to keep a flame spreading across its surface. A horizontal specimen about 1 m long lies beneath a gas-fired radiant panel tilted at 30°. The heat flux on the specimen falls from about 10 to 11 kW/m² at one end to about 1 kW/m² at the other.[1][2] A pilot flame ignites the hot end, and the flame travels until the weakening radiation can no longer support it. The heat flux where the flame stops is the critical radiant flux; the higher it is, the better the floor covering performs.[3][4] For this reason the method is also called the critical radiant flux test.[2]

The test was developed at the National Bureau of Standards (NBS, now the National Institute of Standards and Technology, NIST) after fires in which flame spread over carpet was a major factor. It was standardised as ASTM E648 and as NFPA 253.[1] The test reproduces a corridor whose floor is heated by radiation from the flames and hot gases of a burning room.[2] In the United States, building and life safety codes use the result to place floor finishes in exits and corridors in Class I or Class II.[2][4] An international version of the method, ISO 9239-1, underlies the European classes for floorings and the New Zealand requirements for floor surfaces.[5][6]

Purpose and history

Fire tests for interior finish were first developed with walls and ceilings in mind, long before carpet became a popular floor finish.[7] Official attention turned to soft floor coverings after a series of small fires in the Washington, D.C., area in 1960 and 1961. A well-publicised dwelling fire on the West Coast in 1967 and the Harmer House Nursing Home fire in Ohio in 1970 added to that attention. Carpet was a contributing rather than a causative factor in these incidents.[7] The Harmer House fire, in Marietta on 9 January 1970, killed 32 people, and carpet with a foam-rubber backing was judged to have played a significant role. Until then, floor finishes had been left out of interior finish rules, because experience had been favourable.[8]

In 1965 the Public Health Service of the U.S. Department of Health, Education, and Welfare set flame spread limits for floor coverings in federally funded hospitals, based on the Steiner tunnel test.[7] In that tunnel a floor covering had to be mounted upside down on the ceiling, which matched neither its position nor its mounting in a building. The tunnel could not assess ignitability, its burner was not suited to slow flame spread, and carpets with separate underlays or synthetic fibres that melt, drip or delaminate could not be tested properly.[7][9] A later attempt by Underwriters Laboratories (UL) in 1969, UL Subject 992, was a 2.44 m (8 ft) version of the tunnel with the specimen on its floor. It never gained wide acceptance and is no longer used.[7]

The replacement grew out of research on corridors. In model corridor fire tests, NBS found that the radiant energy reaching a floor covering strongly influenced flame spread across it. This work led to the flooring radiant panel test.[3] NFPA 253 carries the title Standard Method of Test for Critical Radiant Flux of Floor Covering Systems Using a Radiant Heat Energy Source.[1] The handbook lists NFPA 253 and ASTM E648 as technically equivalent standards.[10] The same principle is used in ASTM E970 for exposed attic floor insulation.[1]

Apparatus and procedure

The apparatus is a closed chamber in which a radiant panel is inclined at 30° to a horizontal specimen 1,000 mm (39 in.) long.[2] The panel burns a mixture of air and fuel gas, and its inclination produces a heat flux that varies along the specimen.[1] The share of radiation reaching a surface depends on the size of the radiating surface, its distance and its orientation, and is described by the view factor.[11] Hirschler gives the flux on the specimen as about 11 kW/m² near the panel, falling to about 1 kW/m² at the far end, while Madrzykowski and Stroup give 10 kW/m² to 1 kW/m².[2][1] The decrease follows a standard profile of heat flux against distance.[3]

Side view of a closed chamber with a gas-fired panel tilted at 30 degrees over a horizontal floor-covering specimen and a pilot burner at its hot end.
Side elevation of the flooring radiant panel test: a gas-fired panel inclined at 30° heats a horizontal specimen about 1 m long, from about 11 kW/m² at the pilot end to about 1 kW/m² at the far end.

The schematic reproduced in the handbook from NFPA 253 shows a chamber about 140 cm long and 71 cm high, sheathed with inorganic millboard. A pilot burner sits at the hot end of the specimen, thermocouples sit in the exhaust stack, and a radiation pyrometer views the specimen.[2][3] The pilot flame ignites the specimen at the end with the highest radiant flux. The flame front then travels along the specimen until it is no longer reinforced by the radiant flux, and it goes out.[3] The laboratory measures the distance between the igniter and the point where flame propagation stopped, and reads the heat flux at that distance from a calibration curve of heat flux against distance.[2] The minimum value required to sustain flame propagation is termed the critical radiant flux.[4]

ISO 9239-1 uses a specimen of 1,050 mm × 230 mm under a panel inclined at 30°, with a flux falling from 11 kW/m² to 1.0 kW/m² and a test duration of 30 minutes.[12] The critical radiant flux is defined as the flux at which the flame goes out or the flux reached after 30 minutes, whichever is lower. In other words, it is the flux at the furthest extent of flame spread.[12][5]

Specimens must represent the product as installed. Carpet to be loose-laid over concrete is tested over a thick, high-density, inorganic reinforced cement board; carpet to be bonded is tested with the manufacturer's adhesive.[4] A separate underlay (pad) normally lowers the critical radiant flux, which NIST research attributes to its insulating effect.[4]

The test formerly let manufacturers use a "standard" pad of rubber-coated jute and animal hair or fibre, at least 9.5 mm (3/8 in.) thick, with a mass of about 1.7 kg/m² (50 oz/yd²).[4] NIST found that this pad is likely to give lower values than other underlays in use. A result over the standard pad may therefore be applied to any carpet and underlay combination, whereas a result with the actual pad is valid only for that combination.[4]

Physics of flame spread over floors

Floor coverings with modest resistance to flame spread are unlikely to become involved in the early growth of a fire within a room. They tend to spread flame only under a sizable exposure fire, often after flashover.[2] A corridor is different. Flames and hot gases discharged from the doorway of a fully involved room fill the upper part of the corridor and radiate onto the floor. The level of that radiation is a significant factor in whether progressive flaming will occur.[2] The view factor is also used to calculate how much radiation from a smoke layer reaches floor level.[11]

Section through a burning room and a corridor: hot gases leave the room doorway under the corridor ceiling and radiate down onto the corridor carpet.
The corridor scenario behind the test: flames and hot gases from a fully involved room fill the upper corridor and radiate onto the floor covering, which may then spread flame along the escape route.

Babrauskas, in the SFPE Handbook, writes that carpets in the room of fire origin are unlikely to contribute much to fire growth. The floor is convectively cooled and has the smallest view factor to the hot upper regions. The hazard arises when an unsuitable product lies in a corridor used as an escape path, where very rapid flame spread and a high heat release rate can result. Linoleum and wood parquet can also burn down the length of a corridor.[13] The Australian Fire Safety Verification Method handbook adds that the orientation of floors reduces the risk, but radiant heat from a hot layer can still accelerate spread across combustible flooring before flashover.[14]

The critical radiant flux differs from the critical heat flux for ignition. That quantity is the heat flux at or below which the ignition time is effectively infinite, so that ignition does not occur.[15] In the flooring test the pilot flame does the igniting, and the result describes whether an established flame can keep advancing into less heated material.[3]

Orientation matters a great deal. In upward spread along a vertical surface, much heat goes to the material above the burning zone, which is preheated, so the fire spreads faster.[16] Quintiere gives typical speeds of about 0.1 cm/s for lateral or downward spread on thick solids, against 1 to 100 cm/s for upward spread.[17] This contrast is consistent with the experimental finding that floor coverings add much less to early fire growth than wall or ceiling finishes.[2]

Quintiere treats lateral and downward spread as opposed-flow flame spread, in which the flame advances against the air flow. Lateral spread measured on vertical samples was similar to downward spread, and to spread outward from a small fire on a horizontal surface.[17][18] In his analysis, spread accelerates as far-field radiation raises the surface ahead of the flame towards its ignition temperature.[17] He also identifies a critical surface temperature below which continued spread is not possible, and each level of external radiation heats the surface to its own steady temperature.[18] A minimum surface temperature for spread therefore corresponds to a minimum external flux for spread, the kind of quantity the flooring test reports.[18][3]

Spread speed on a preheated surface

For thick materials burning in air under natural convection, Quintiere and Harkleroad's method describes the opposed-flow spread speed with one equation. The speed equals a flame heating parameter divided by the thermal inertia of the material. It is also divided by the square of the gap between the ignition temperature and the preheated surface temperature.[18]

V=Φkρc(Tig−Ts)2for Ts≥Ts,min

Symbol Description Unit
V flame spread speed m/s
Φ flame heating parameter, deduced from tests kW²/m³
kρc thermal inertia (conductivity × density × specific heat) kW²·s/(m⁴·K²)
Tig ignition temperature of the surface °C
Ts surface temperature ahead of the flame, set by the external heating °C
Ts,min minimum surface temperature for continued spread °C

The parameters are deduced from lateral spread on vertical samples exposed to external radiation. Tabulated values are significant to only two places, and materials that melt and drip excessively behave differently.[18][19] The equation is therefore an illustration of the mechanism, not a prediction of a flooring test result.

Worked example. For an acrylic carpet, Quintiere lists Tig = 300 °C, kρc = 0.42 kW²·s/(m⁴·K²), Φ = 9.9 kW²/m³ and Ts,min = 165 °C.[19] Where the panel keeps the surface at 250 °C, the temperature gap is 50 K. The speed is then 9.9 / (0.42 × 50²) = 0.0094 m/s, or about 9.4 mm/s. At 200 °C the gap doubles to 100 K and the speed falls fourfold to about 2.4 mm/s, so the flame needs about 42 s to cover 0.1 m. At 165 °C the speed is still about 1.3 mm/s, but on any cooler surface the flame cannot continue.

Two rising curves of flame spread speed against surface temperature for an acrylic and a wool carpet, each starting abruptly at its minimum spread temperature.
Opposed-flow flame spread speed against the surface temperature ahead of the flame for two carpets, from Quintiere's thick-solid equation. Each curve starts at its minimum surface temperature for spread; below it the flame goes out.

The flame therefore does not slow smoothly to zero. It stops at a finite speed once the surface is too cool, which matches the observation that the flame front goes out where the radiant flux no longer reinforces it.[3] An untreated wool carpet in the same table needs a surface of at least 335 °C to keep spreading, so it stops much closer to the panel.[19]

Classification and regulation

United States

In the United States, NFPA 101, Life Safety Code (2006 edition), as described by Hirschler (2008b), classifies interior floor finish by critical radiant flux. Class I requires at least 4.5 kW/m² (0.45 W/cm²) and Class II at least 2.2 kW/m² (0.22 W/cm²).[4][20] Hirschler's table assigns Class I or II to exits and exit access corridors in, for example, new assembly, new educational, new health care, new hotel and new apartment occupancies, and in detention and industrial occupancies.[21] The occupancy chapters of the code decide which class applies.[21] According to the annex of NFPA 101, a complete standard sprinkler system allows Class II where Class I is required, and no rating where Class II is required. This trade-off does not apply to new detention and correctional occupancies.[21]

Floor coverings in rooms and open spaces generally need no further regulation if they resist flame spread at least as well as a material passing the federal methenamine pill test (FF-1-70, ASTM D2859).[4] For corridors in health care facilities without sprinklers, O'Connor (2008) gives a minimum critical radiant flux of 4.5 kW/m². Where sprinklers are installed, floor finishes need no regulation beyond the federal flammability standard.[8] Stull and Chines report that the carpet in the Baptist Tower fire had a critical radiant flux of 1.0 kW/m² (0.1 W/cm²). This low value was believed to have aggravated the initial fire conditions.[3]

The test also appears outside the interior finish chapters. The elevator safety code ASME A17.1/CSA B44, as described by Donoghue (2008), requires floor covering, underlay and adhesive in elevator cars to reach 4.5 kW/m² by NFPA 253. Elevator occupants may not be able to escape rapidly, so the level equals the health care requirement.[22] In the fire door provisions described by Davoodi (2008), combustible floor coverings may run through openings protected by doors rated at 1½ hours or less if their critical radiant flux is at least 2.2 kW/m². They may not run through openings that need doors rated at 3 hours or more. Vinyl sheet flooring, wool carpet and some synthetic carpets generally exceed 2.2 kW/m².[23]

In New York City, Local Law 16 of 1984 added a reference standard for the flammability of carpets that cited a pill test (DOC FF1-1970), ASTM E 648-1978 and the smoke test ASTM E 662-1979.[24][25] For United States nuclear power plants, Iqbal and Salley (2004) note that the original licensing basis required carpet in the main control room to meet ASTM E84 Class A. Manufacturers now test carpet to ASTM E648, so a licensee replacing such carpet must run its own E84 tests or prepare an engineering analysis.[26] Their table of standards describes ASTM E648 as measuring the critical radiant flux at flameout.[27]

Europe

In the European classification of construction products (EN 13501-1), as summarised by Hirschler (2008a), floorings have their own classes based on EN ISO 9239-1 with a test duration of 30 minutes. Classes A2fl and Bfl require a critical flux of at least 8.0 kW/m², Cfl at least 4.5 kW/m² and Dfl at least 3.0 kW/m².[5] Classes Bfl to Efl also require a small-flame test (EN ISO 11925-2, 15 s exposure) with flame spread of at most 150 mm within 20 s. An additional smoke class s1 is limited to 750 %·min.[5] The Single Burning Item test used for walls and ceilings is not used for floorings.[28]

New Zealand and Australia

In New Zealand, Verification Method C/VM2 (second edition, 2025) sets minimum critical radiant fluxes for floor surface materials. Sleeping areas and exitways in buildings where care or detention is provided need 4.5 kW/m² without sprinklers and 2.2 kW/m² with sprinklers. Exitways in other buildings need 2.2 kW/m² in both cases. Firecells for more than 50 persons need 2.2 kW/m² without and 1.2 kW/m² with sprinklers, and other occupied spaces except household units need 1.2 kW/m².[29] The same table appeared in Building Code clause C3.4(b), with testing to ISO 9239-1 (2010).[30]

The 2013 commentary states that the method replaced a test in which flooring was damaged by contact with a hot metal nut. The levels of 1.2, 2.2 and 4.5 kW/m² are similar to those of the Building Code of Australia, although they apply in different situations, and smoke is not assessed.[12] Wood products typically reach more than 2.2 kW/m², and some more than 4.5 kW/m², depending on density, thickness and treatment.[29] In Australia, the Fire Safety Verification Method handbook (2020) offers a design scenario for flooring: a growing fire exposing the floor to increasing radiant heat.[31]

Worked example: classifying a floor covering

The same test result leads to different outcomes under different rules. The table compares three critical radiant fluxes. The value of 1.0 kW/m² is the Baptist Tower carpet; the other two are illustrative.[3][4][5][29]

Horizontal scale from 0 to 9 kW/m² with rows of markers for US classes, European flooring classes and New Zealand limits, plus two reference carpets.
Critical radiant flux thresholds for floor coverings in three systems, with two reference values: the lowest flux of a carpet still passing the pill test and the Baptist Tower carpet.
Critical radiant flux NFPA 101 (2006) class EN 13501-1 flux criterion met C/VM2 (2025) locations without sprinklers
1.0 kW/m² (0.10 W/cm²) none none (below Dfl) none
3.0 kW/m² (0.30 W/cm²) Class II Dfl all except sleeping areas and exitways in care or detention buildings
5.0 kW/m² (0.50 W/cm²) Class I Cfl all listed locations

A covering at 3.0 kW/m² is Class II in the United States and reaches Dfl if it also passes the small-flame test.[4][5] In an unsprinklered New Zealand building it is acceptable everywhere except care and detention sleeping areas and exitways, which need 4.5 kW/m².[29] With sprinklers the same covering meets every listed location.[29]

Relation to other floor covering tests

The methenamine pill test is the small-scale ignition test that all carpet made for sale in the United States has had to pass since April 1971. It gives adequate "first to ignite" protection for carpet in rooms.[7] Passing it does not imply a high critical radiant flux. A precision study of the flooring test found carpets well under 2 kW/m², and a product can pass the pill test with a critical radiant flux as low as 0.4 kW/m².[7][2] Traditional floor finishes such as wood flooring and resilient materials will not ignite unless exposed to well over 1 kW/m², but some carpet-like and loose-fill materials may ignite at lower fluxes.[7] Stull and Chines treat both tests in their chapter on fibres and textile flammability.[3]

Bench-scale heat release data offer a second route. Babrauskas cites a study in which floor coverings with a peak heat release rate below 200 kW/m² in the cone calorimeter at 25 kW/m² tended not to show accelerating spread down a corridor.[13] Codes do not generally regulate floor coverings on smoke, because floors are seldom involved until a fire is already large. Some jurisdictions and many transport settings do set smoke criteria, using ASTM E662 for trains and ISO 5659-2 for ships.[4]

Limitations

The test simulates conditions observed in large-scale corridor experiments, particularly where there is little or no combustible wall or ceiling finish.[2] Corridors with combustible wall and ceiling finishes would be expected to present a greater hazard, a situation outside the conditions the test simulates.[2] The result also belongs to the tested system of floor covering, underlay, adhesive and substrate, because an underlay can lower the critical radiant flux.[4]

The reported result is a single flux at flameout, not a heat release rate.[27] Installations other than flat floors can behave very differently: a residential carpet of 80 % acrylic and 20 % nylon fitted over a stairway produced a peak heat release rate of 3 MW.[13] The thresholds are regulatory choices that differ between countries, as the 2.2 kW/m² of US Class II and the 3.0 kW/m² of Dfl show.[4][5] Hirschler concludes that the test serves to evaluate floor coverings in areas where risks need to be especially minimised. Floor coverings in rooms and open spaces generally merit no further regulation.[4]

See also

Notes

  1. ↑ 1.0 1.1 1.2 1.3 1.4 1.5 Madrzykowski and Stroup (2008), p. 2-43.
  2. ↑ 2.00 2.01 2.02 2.03 2.04 2.05 2.06 2.07 2.08 2.09 2.10 2.11 2.12 2.13 Hirschler (2008b), p. 18-34.
  3. ↑ 3.00 3.01 3.02 3.03 3.04 3.05 3.06 3.07 3.08 3.09 3.10 Stull and Chines (2008), p. 6-97.
  4. ↑ 4.00 4.01 4.02 4.03 4.04 4.05 4.06 4.07 4.08 4.09 4.10 4.11 4.12 4.13 4.14 Hirschler (2008b), p. 18-35.
  5. ↑ 5.0 5.1 5.2 5.3 5.4 5.5 5.6 Hirschler (2008a), p. 6-53.
  6. ↑ Ministry of Business, Innovation and Employment (2013), p. 143.
  7. ↑ 7.0 7.1 7.2 7.3 7.4 7.5 7.6 7.7 Hirschler (2008b), p. 18-33.
  8. ↑ 8.0 8.1 O'Connor (2008), p. 20-145.
  9. ↑ Stull and Chines (2008), p. 6-96.
  10. ↑ Hirschler (2008a), p. 6-38.
  11. ↑ 11.0 11.1 Van Rossum (2027), §5.4.
  12. ↑ 12.0 12.1 12.2 Ministry of Business, Innovation and Employment (2013), p. 145.
  13. ↑ 13.0 13.1 13.2 Babrauskas (2002b), p. 3-11.
  14. ↑ Australian Building Codes Board (2020b), p. 83.
  15. ↑ Madrzykowski and Stroup (2008), p. 2-34.
  16. ↑ Van Rossum (2027), §4.3.
  17. ↑ 17.0 17.1 17.2 Quintiere (2002b), p. 2-247.
  18. ↑ 18.0 18.1 18.2 18.3 18.4 Quintiere (2002b), p. 2-250.
  19. ↑ 19.0 19.1 19.2 Quintiere (2002b), p. 2-251.
  20. ↑ Lathrop (2008a), p. 4-75.
  21. ↑ 21.0 21.1 21.2 Hirschler (2008b), p. 18-29.
  22. ↑ Donoghue (2008), p. 10-63.
  23. ↑ Davoodi (2008), p. 18-16.
  24. ↑ Razza and Grill (2005a), p. 19.
  25. ↑ Razza and Grill (2005a), p. 23.
  26. ↑ Iqbal and Salley (2004), p. B-34.
  27. ↑ 27.0 27.1 Iqbal and Salley (2004), p. C-12.
  28. ↑ Hirschler (2008a), p. 6-49.
  29. ↑ 29.0 29.1 29.2 29.3 29.4 Ministry of Business, Innovation and Employment (2025b), p. 52.
  30. ↑ Ministry of Business, Innovation and Employment (2013), pp. 20–21.
  31. ↑ Australian Building Codes Board (2020b), p. 84.

References

  • Australian Building Codes Board. (2020b). Handbook: Fire Safety Verification Method (Print version 1.1).
  • Babrauskas, V. (2002b). Heat release rates. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 3-1–3-37). National Fire Protection Association; Society of Fire Protection Engineers.
  • Davoodi, H. (2008). Confinement of fire in buildings. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 18-3–18-21). National Fire Protection Association.
  • Donoghue, E. A. (2008). Building transportation systems. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 10-57–10-68). National Fire Protection Association.
  • Hirschler, M. M. (2008a). Concepts and protocols of fire testing. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-35–6-60). National Fire Protection Association.
  • Hirschler, M. M. (2008b). Interior finish. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 18-23–18-42). National Fire Protection Association.
  • Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.
  • Lathrop, J. K. (2008a). Concepts of egress design. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 4-69–4-91). National Fire Protection Association.
  • Madrzykowski, D., & Stroup, D. W. (2008). Flammability hazard of materials. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 2-31–2-48). National Fire Protection Association.
  • Ministry of Business, Innovation and Employment. (2013). Commentary for Building Code clauses C1–C6 and Verification Method C/VM2.
  • Ministry of Business, Innovation and Employment. (2025b). Verification Method C/VM2: Framework for fire safety design (2nd ed.).
  • O'Connor, D. J. (2008). Health care occupancies. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 20-139–20-155). National Fire Protection Association.
  • Quintiere, J. G. (2002b). Surface flame spread. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-246–2-257). National Fire Protection Association; Society of Fire Protection Engineers.
  • Razza, J. C., & Grill, R. A. (2005a). Amendments to the fire protection and life safety provisions of the New York City Building Code by local laws adopted while World Trade Center 1, 2, and 7 were in use (NIST NCSTAR 1-1G). National Institute of Standards and Technology.
  • Stull, J. O., & Chines, S. A. (2008). Fibers and textiles. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-75–6-102). National Fire Protection Association.
  • Van Rossum, E. (2027). Introduction to Fire Safety Engineering. Fire Safety Academy.