The fire point of a liquid is the lowest temperature to which it must be heated to give off enough vapour for burning to continue after a small test flame has ignited it.[1] The Fire Protection Handbook (20th edition, 2008) sets the criterion at sustained burning for at least 5 seconds. It also describes the fire point as the temperature at which the liquid evolves vapour as fast as the flame consumes it.[1] The fire point is related to the flash point, at which the vapour above the liquid can only flash briefly and then goes out.[2]

The difference matters because a flash consumes only the vapour that has gathered above the surface, while a fire at or above the fire point can keep burning as a pool fire.[3] The fire point is never lower than the flash point. For high-flashpoint liquids the handbook reports it as typically about 5.6 °C to 15 °C (10 °F to 27 °F) higher.[1] It is usually measured with the Cleveland open-cup apparatus, ASTM D92.[1] The 2008 handbook describes the property's use in United States codes such as NFPA 30, which exempt some liquids that have a flash point but cannot sustain burning from storage limits.[1] The same idea of a minimum surface temperature for sustained flaming is also applied to solid materials and to the theory of flame extinction.[3][4]

Definition

Slye defines the fire point as the lowest temperature to which a liquid must be heated to evolve enough vapour for sustained burning. The burning must last at least 5 seconds after a test flame is applied. This definition comes from Hagopian (1990), as cited in Slye (2008).[1] In physical terms, the fire point is the minimum temperature at which the liquid releases vapour as fast as the flame burns it. It therefore indicates the temperature for indefinite burning of a pool of the liquid.[1]

The SFPE Handbook gives a qualitative definition without a time criterion. Kanury describes the fire point as very similar to the flash point, except that the flame must not merely flash and cease but must sustain itself and go on burning the liquid.[2] In the same chapter, the flash point is the uniform liquid temperature at which the mixture just above the surface supports a momentary flash. The flash is prompted by a quick sweep of a small gas pilot flame.[2] The two definitions describe the same property. The handbook adds a measurable duration of 5 seconds, and the SFPE chapter stresses the distinction between flashing and self-sustained flaming.[1][5]

NUREG-1805 is a set of fire hazard tools of the U.S. Nuclear Regulatory Commission. It defines the fire point as the minimum temperature to which a liquid must be heated in a standardised apparatus for sustained combustion to follow when a small pilot flame is applied. The definition assumes the liquid is at normal atmospheric pressure.[6] Its glossary adds a shorter form: the lowest temperature at which flaming can be sustained at the surface of the liquid.[7]

Flash point, fire point and vapour pressure

A liquid does not burn as a liquid. It must first turn into a gas or a mist, and in a pool fire this happens through evaporation.[8] Evaporation is a physical change and not a chemical one, so candle wax, for example, can only burn once it has evaporated.[9] For flammable and combustible liquids, the fire hazard therefore comes from their vapours rather than from the liquid itself.[10]

The amount of vapour depends on the vapour pressure of the liquid, which rises steeply with temperature.[5] At a limiting temperature the vapour above the surface reaches the lean limit of the flammability limits, and a pilot flame can then propagate through the mixture.[5] Drysdale states that the closed-cup flash point corresponds to the temperature at which the equilibrium vapour pressure equals the lower flammability limit.[3] Slye gives the same link as an approximate one and uses it to estimate the lower flammable limit from the vapour pressure at the flash point.[1]

Vapour concentration rising with liquid temperature, crossing the lower flammable limit at the flash point; in this example the fire point lies further right.
The vapour concentration above a liquid rises with its temperature. It reaches the lower flammable limit at about the flash point; in this example, sustained burning begins at a higher fire point.

At the flash point, the vapour already present above the surface burns in a brief flash, but flaming does not persist.[3] Kanury explains that the flame becomes self-sustained only when evaporation is copious enough, which requires a higher bulk temperature of the liquid.[5] Simmons describes the same step. The vapour pressure at the flash point is just enough for a lean mixture, but a somewhat higher temperature is needed before the burning gas above the surface ignites the fuel.[11] The fire point is the temperature at which this supply of vapour keeps pace with its consumption by the flame.[1]

Ignition is defined by Drysdale as the process by which self-sustaining combustion is initiated. He adds that for ignition of a liquid to be followed by continuous burning, its temperature must be raised to the firepoint.[3] At sufficiently high temperatures the vapour and air mixture can ignite without any pilot flame, and the lowest such temperature is the autoignition temperature.[5][11] By the time autoignition becomes evident, the liquid is evaporating vigorously and may even be boiling.[12]

Measurement

The fire point is typically determined with the Cleveland open-cup apparatus described in ASTM D92.[1] The Tag open-cup apparatus of ASTM D1310 also determines both the flash point and the fire point of liquids.[13] In these tests the sample is heated slowly, and a test flame is applied to the vapour space at regular intervals.[1] The cup is heated either directly by a small laboratory flame or indirectly by a water or water and glycol bath.[5] When the liquid reaches its open-cup flash point, the flame flashes across the surface and goes out. When it reaches the fire point, the flash is followed by sustained burning.[3]

Laboratory Cleveland open-cup tester: a brass cup on a heated plate with a small test flame on a swivel arm and a thermometer.
A Cleveland open-cup tester, the apparatus of ASTM D92 in which flash point and fire point are usually measured.

Another test of the same kind is ASTM D4206, which uses the Seta flash open-cup apparatus to determine whether a liquid will sustain burning.[14] Scarbrough (2008b) describes it as useful for coatings and advises treating a liquid that supports flame in this test as a flammable liquid.[14] The test thus separates liquids that only flash from liquids that can keep burning, which is the same distinction the fire point draws.[14][1]

The open cup has a known weakness for mixtures. As the liquid is heated slowly, it can lose its volatile components before it reaches the point of ignition. The test may therefore fail to recognise that large volumes of such mixtures can burn rather than only flash. This point comes from Britton (1999), as cited in Slye (2008).[1] Gottuk and White go further and consider it impractical to determine a fire point for a multicomponent fuel. A value would require closed-cup heating to a test temperature, exposure of the surface, application of a pilot flame and repetition until the temperature is bracketed.[15]

Like other flammability properties, the fire point is not an intrinsic property of the material. Custer and Sheppard note that reported results of most flammability tests depend on the specific test method used.[16] Kanury shows that closed cups give lower flash points than open cups, and that the other differences between cups are neither small nor systematic.[2] Slye adds that the flash point varies with pressure, oxygen content, purity, test method and even the skill of the operator.[13]

Typical values

Slye reports a typical difference of about 5.6 °C to 15 °C (10 °F to 27 °F) between fire point and flash point for high-flashpoint liquids. The range comes from Friedman (1998), as cited in Slye (2008).[1] Kanury, using data from the International Critical Tables, states that the fire point consistently exceeds the flash point by about 20 °C to 40 °C.[2] The individual open-cup entries in his table range from 5 °C for Texas solar oil to 38 °C for one paraffin oil.[17] The two handbooks therefore give different typical gaps. Kanury's table compares mostly open-cup flash points of oils with their fire points, while Slye states his range for high-flashpoint liquids in general.[17][1]

Liquid Flash point (°C) Fire point (°C) Source
n-Decane 46 (closed cup), 56 (open cup) 64 [3]
Gas oil 90 (open cup) 109 [17]
Texas solar oil 92 (open cup) 97 [17]
Paraffin oil 98 (Pensky-Martens closed cup) 112 [17]
Fuel oil 133 (open cup) 164 [17]
Diphenyl ether and diphenyl eutectic (heat transfer fluid) 124 135 [18]
Partially hydrogenated terphenyl (heat transfer fluid) 168 191 [18]
Aliphatic oil (heat transfer fluid) 218 246 [18]
1,2,4-Trichlorobenzene (heat transfer fluid) 99 none up to the boiling point [18]

For n-decane, Drysdale gives a closed-cup flash point of 46 °C, an open-cup flash point of 56 °C and a fire point of 64 °C. The fire point is thus 18 °C above the closed-cup value and 8 °C above the open-cup value.[3] The last row of the table shows that a liquid can have a flash point but no measured fire point before boiling. LeBlanc lists 1,2,4-trichlorobenzene with a flash point of 99 °C (210 °F) and no fire point up to its boiling point.[18]

Dumbbell chart of flash point and fire point for eight liquids from n-decane to aliphatic oil, with gaps of 5 to 31 °C.
Flash point (open circle) and fire point (filled circle) of eight liquids. The fire point is always higher, by between 5 °C and 31 °C here.

Solids also have fire points, defined in terms of their surface temperature. Drysdale gives about 360 °C for polypropylene and about 300 °C for wood and for polymethylmethacrylate (PMMA).[3] These values partly offset the differences in heat of combustion of the vapours, which are about 44 kJ/g for polypropylene, 14 kJ/g for wood and 23 kJ/g for PMMA.[3]

Role in flame spread over liquids

The temperature of a spilled liquid relative to its flash point is the most important single factor for the speed at which flame spreads over it.[19] Below the flash point, flame spreads through a flow of hot liquid driven by surface tension ahead of the flame front. This liquid-phase controlled flame spread runs at about 1 cm/s to 12 cm/s.[19] Above the flash point, flame spreads through the vapour layer at about 130 cm/s to 220 cm/s, which is more than ten times faster.[19] Slye makes the same point for stored liquids: if the liquid is below its flash point, the heat of the fire must first warm the surface before flame can spread.[20]

Glassman and Hansel identified the temperature at which gas-phase controlled flame spread begins as the fire point of the liquid. They called the temperature of maximum spread rate the stoichiometric temperature, at which the vapour at the surface is in stoichiometric proportion.[15] In the data reproduced by Gottuk and White, the onset of gas-phase spread lay on average 15 °C above the closed-cup flash point for hydrocarbon fuels. For decane it lay 12 °C above, at 56 °C, and for 1-pentanol only 4 °C above.[21] Gottuk and White add that none of the standard flash point tests correlates with the onset of gas-phase flame spread for all fuels.[21]

Flame spread rate on a log scale rising with liquid temperature, slow below the flash point and jumping to fast gas-phase spread near the fire point.
Flame spread over a liquid is slow (about 1 to 12 cm/s) while it is driven by surface flow, and fast (about 130 to 220 cm/s) once it runs through the vapour. Glassman and Hansel placed the transition at the fire point.

Quintiere uses the same property in the energy balance of flame spread over a surface. The ignition temperature in that balance is the surface temperature that produces enough fuel vapour to sustain piloted ignition. For liquid fuels this temperature is called the firepoint.[22] Kanury notes that in many practical situations a liquid is heated by a heat flux on its evaporating surface. The surface temperature must then be estimated before it can be compared with the flash point or fire point.[23]

Fire point of solids and the fire point equation

Drysdale points out that flashing and sustained burning can also be observed for combustible solids. For solids, however, vapour is released through irreversible chemical decomposition, so these temperatures can only be defined at the surface, which is not normally measured.[3] The ignition of solids is therefore usually characterised by the imposed heat flux, and the measured values depend on the test method.[3] In simple ignition calculations for a thermally thin solid, ignition is taken to occur when its temperature reaches this firepoint.[24]

Tewarson describes fire control, suppression and extinguishment with the fire point equation. It applies at the moment the flame is about to go out. The convective heat flux from the flame to the surface then equals a fraction of the heat released by the fuel leaving the surface at a critical rate.[4]

q˙′'fc=ϕΔHTm˙′'cr

Symbol Description Unit
q˙′'fc convective heat flux from the flame to the surface at the extinction condition kW/m²
ϕ kinetic parameter: the largest fraction of the combustion energy that the flame can lose to the surface by convection without going out –
ΔHT net heat of complete combustion of the fuel kJ/g
m˙′'cr critical mass loss rate for flame extinction g/(m²·s)

Fire point theory and experiments show that the critical mass loss rate for flame extinction is similar to that for ignition.[25] Tewarson lists critical mass loss rates measured in the ASTM E2058 fire propagation apparatus and at the University of Edinburgh. For PMMA the values are 3.2 g/(m²·s) and 1.9 g/(m²·s), with kinetic parameters of 0.28 and 0.53.[25] The E2058 values are higher because they were measured when the sustained flame was just being established.[25] The kinetic parameter is higher for aliphatic materials than for aromatic and chlorinated ones.[25]

As a worked example, PMMA has a net heat of complete combustion of 25.2 kJ/g.[26] Tewarson reports that critical mass-loss rates for ignition and extinction are similar; the table's measured ignition values can therefore give an illustrative estimate of the extinction flux.[25] With the E2058 values, the estimate is 0.28 × 25.2 kJ/g × 3.2 g/(m²·s), or about 22.6 kW/m². With the Edinburgh values, 0.53 × 25.2 kJ/g × 1.9 g/(m²·s) gives about 25.4 kW/m².[25][26] Both data sets thus give a similar estimate, although their individual parameters differ. The parameters themselves differ because the two laboratories measured them at different stages of flame establishment.[25]

Use in regulation, industry and fire fighting

In the United States, flammable and combustible liquids are grouped by flash point, not by fire point. In the system of NFPA 30 described by Slye (2008), Class I liquids have flash points below 37.8 °C (100 °F), while Class II starts at 37.8 °C and ends below 60 °C (140 °F).[27] Class IIIA starts at 60 °C and ends below 93.3 °C (200 °F); Class IIIB starts at 93.3 °C, as explained under flammable and combustible liquid classification.[27] The fire point enters where codes such as NFPA 30, as described in the 2008 edition of the Fire Protection Handbook, exempt liquids that have a flash point but cannot sustain burning.[1]

Several industrial chapters of the handbook rely on this distinction. Scarbrough notes that many waterborne coatings show a flash point but have no fire point, so they will not sustain a flame. Their dried residues are still combustible and must be managed as such.[14] Dobbs describes less hazardous hydraulic fluids that burn when released at high pressure onto an ignition source but stop burning when the source is removed.[28] Most petroleum-based hydraulic oils have flash points between 177 °C and 316 °C (350 °F and 600 °F), and the less hazardous fluids have flash points in a similar range.[28] LeBlanc warns that organic heat transfer fluids are nearly always circulated well above their flash points, so a leak can quickly produce a pool or spray fire.[29]

NUREG-1805, written for fire protection inspections at US nuclear power plants, counts Class IIIA and IIIB liquids as high-risk fuels when they are heated to within 10 °C of their flash point. The same definition includes all Class I and Class II liquids and liquids pressurised to 174.4 kPa or more.[6] It thus treats a combustible liquid near its flash point in the same way as a flammable liquid.[6]

The fire point also explains how some extinguishing agents work. When foam covers a burning pool, it blocks the radiant heat that keeps the liquid evaporating. If the fire point of the liquid is above the temperature of the foam, the liquid is cooled and its vapour pressure falls.[30] For a high-flashpoint liquid such as diesel oil, water can work by cooling the liquid below its flash point, but a high-velocity jet can scatter the burning liquid.[31] For solids, Drysdale relates the specific heat to the heat that must be removed to cool a burning solid below its firepoint. Water is effective partly because its specific heat of 4,200 J/(kg·K) is higher than that of most other substances.[32]

Limits and common misconceptions

A common error is to treat the flash point and the fire point as the same temperature. At the flash point only a brief flash occurs, while sustained burning requires the higher fire point.[3] The reverse error is to treat a liquid without a fire point as safe. Waterborne coatings with a flash point but no fire point still leave combustible residues.[14] An open-cup test on a mixture may also miss the ability of large volumes to burn, because the sample loses its volatile fractions during slow heating.[1]

A liquid stored below its fire point is not necessarily safe in a fire. An external fire can heat the liquid surface until flammable vapour forms and flame spreads over it.[20] The bulk temperature in a cup test then says little about the surface temperature reached under an imposed heat flux.[23] Once a fire has burned for a short time, the flash point and related ignition properties have minimal influence on how the liquid burns.[27]

Fire point values also carry the uncertainty of the test. They depend on the apparatus and procedure, and for multicomponent fuels the concept is hard to apply at all.[16][15] The effective flash point of a released hydrocarbon mixture can change in the time between release and ignition, as the lighter fractions evaporate. Gottuk and White therefore regard immediate ignition of a released fuel as the conservative assumption.[21]

See also

Notes

  1. ↑ 1.00 1.01 1.02 1.03 1.04 1.05 1.06 1.07 1.08 1.09 1.10 1.11 1.12 1.13 1.14 1.15 1.16 1.17 Slye (2008), p. 6-200.
  2. ↑ 2.0 2.1 2.2 2.3 2.4 Kanury (2002b), p. 2-190.
  3. ↑ 3.00 3.01 3.02 3.03 3.04 3.05 3.06 3.07 3.08 3.09 3.10 3.11 3.12 Drysdale (2008), p. 2-17.
  4. ↑ 4.0 4.1 Tewarson (2002), p. 3-145.
  5. ↑ 5.0 5.1 5.2 5.3 5.4 5.5 Kanury (2002b), p. 2-189.
  6. ↑ 6.0 6.1 6.2 Iqbal and Salley (2004), p. B-21.
  7. ↑ Iqbal and Salley (2004), p. F-27.
  8. ↑ Van Rossum (2027), §4.1.
  9. ↑ Van Rossum (2027), §3.5.
  10. ↑ Slye (2008), p. 6-197.
  11. ↑ 11.0 11.1 Simmons (2002), p. 1-147.
  12. ↑ Kanury (2002b), p. 2-195.
  13. ↑ 13.0 13.1 Slye (2008), p. 6-201.
  14. ↑ 14.0 14.1 14.2 14.3 14.4 Scarbrough (2008b), p. 9-27.
  15. ↑ 15.0 15.1 15.2 Gottuk and White (2002), p. 2-301.
  16. ↑ 16.0 16.1 Custer and Sheppard (2008), p. 3-36.
  17. ↑ 17.0 17.1 17.2 17.3 17.4 17.5 Kanury (2002b), p. 2-191.
  18. ↑ 18.0 18.1 18.2 18.3 18.4 LeBlanc (2008), p. 8-67.
  19. ↑ 19.0 19.1 19.2 Gottuk and White (2002), p. 2-300.
  20. ↑ 20.0 20.1 Slye (2008), p. 6-205.
  21. ↑ 21.0 21.1 21.2 Gottuk and White (2002), p. 2-306.
  22. ↑ Quintiere (2002b), p. 2-247.
  23. ↑ 23.0 23.1 Kanury (2002b), p. 2-198.
  24. ↑ Drysdale (2008), p. 2-7.
  25. ↑ 25.0 25.1 25.2 25.3 25.4 25.5 25.6 Tewarson (2002), p. 3-146.
  26. ↑ 26.0 26.1 Tewarson (2002), p. 3-108.
  27. ↑ 27.0 27.1 27.2 Slye (2008), p. 6-198.
  28. ↑ 28.0 28.1 Dobbs (2008), p. 9-70.
  29. ↑ LeBlanc (2008), p. 8-68.
  30. ↑ Yu and Newman (2008), p. 2-79.
  31. ↑ Yu and Newman (2008), p. 2-84.
  32. ↑ Drysdale (2008), p. 2-5.

References

  • Custer, R. L. P., & Sheppard, D. T. (2008). Fire loss investigation. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 3-31–3-41). National Fire Protection Association.
  • Dobbs, P. G. (2008). Metalworking processes. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-67–9-72). National Fire Protection Association.
  • Drysdale, D. (2008). Physics and chemistry of fire. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 2-3–2-20). National Fire Protection Association.
  • Gottuk, D. T., & White, D. A. (2002). Liquid fuel fires. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-297–2-316). National Fire Protection Association; Society of Fire Protection Engineers.
  • Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.
  • Kanury, A. M. (2002b). Ignition of liquid fuels. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-188–2-199). National Fire Protection Association; Society of Fire Protection Engineers.
  • LeBlanc, J. A. (2008). Heat transfer systems and fluids. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 8-65–8-70). National Fire Protection Association.
  • Quintiere, J. G. (2002b). Surface flame spread. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-246–2-257). National Fire Protection Association; Society of Fire Protection Engineers.
  • Scarbrough, D. R. (2008b). Spray finishing and powder coating. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-27–9-37). National Fire Protection Association.
  • Simmons, R. F. (2002). Premixed burning. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 1-144–1-154). National Fire Protection Association; Society of Fire Protection Engineers.
  • Slye, O. M., Jr. (2008). Flammable and combustible liquids. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-197–6-208). National Fire Protection Association.
  • Tewarson, A. (2002). Generation of heat and chemical compounds in fires. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 3-82–3-161). National Fire Protection Association; Society of Fire Protection Engineers.
  • Van Rossum, E. (2027). Introduction to Fire Safety Engineering. Fire Safety Academy.
  • Yu, H.-Z., & Newman, J. S. (2008). Theory of fire extinguishment. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 2-79–2-92). National Fire Protection Association.