Fse-oxidiser-v3.svg (SVG file, nominally 1,260 × 760 pixels, file size: 7 KB)
Summary
Separation of oxidising and flammable gas cylinders under NFPA 55 as described in the 2008 Fire Protection Handbook: 6.1 m (20 ft), or less where a noncombustible barrier at least 1.5 m (5 ft) high with at least half an hour fire resistance separates them.
Original illustration for Oxidiser.
- Alt text: Plan view of oxidising and flammable gas cylinder groups 6.1 m apart, and a variant with a 1.5 m high half-hour barrier between them.
Licensing
New drawing by Fire Safety Academy. © Fire Safety Academy.
File history
Click on a date/time to view the file as it appeared at that time.
| Date/Time | Thumbnail | Dimensions | User | Comment | |
|---|---|---|---|---|---|
| current | 07:58, 8 November 2026 | 1,260 × 760 (7 KB) | Lisa (talk | contribs) | Watermark: Fire Safety Academy logo icon, 70 px, 45 % opacity |