An arc-fault circuit interrupter (AFCI) is a protective device that uses electronics to recognise the current and voltage characteristics of an arcing fault and interrupts the circuit when such a fault occurs.[1] It is designed to prevent fires that start from an arc fault, an unintentional electrical discharge with a low and erratic current that can ignite combustible materials.[1] Ordinary fuses and circuit breakers respond to overloads and to the high current of a short circuit, but not to such low-level arcing.[1] As described in the 20th edition of the Fire Protection Handbook (2008), AFCIs are made for 125 V branch circuits of 15 or 20 A and were then available built into circuit breakers. An AFCI breaker protects the branch-circuit wiring and also the power cords, extension cords and internal wiring of connected equipment.[1] In the United States, the Consumer Product Safety Commission (CPSC) identified arc-fault detection as a promising technology against home wiring fires in the 1980s and later found AFCIs effective in tests.[1]

Purpose and principle

An AFCI addresses one specific route to electrical ignition. Electricity can cause a fire either when an arc occurs or when electrical equipment overheats.[2] When unwanted arcing occurs, it produces high temperatures that can ignite nearby combustibles such as wood, paper and carpets, making the arc an ignition source.[1] The AFCI is meant to remove that source before ignition, by de-energising the circuit as soon as it recognises the arc.[1]

The key task of the device is discrimination. Arcing also occurs in normal operation, for example when a switch is opened or a plug is pulled from a receptacle, and the AFCI should not trip in those cases.[1] It uses dedicated current-sensing circuitry to tell normal from unwanted arcing. Once an unwanted arc is detected, the control circuitry trips the internal contacts, de-energises the circuit and so reduces the potential for a fire.[1] A nuclear-industry glossary defines arcing as the flashing that occurs at electrical terminals when a circuit is opened or closed.[3]

Block diagram of an AFCI: current sensing, electronics that separate normal from unwanted arcing, and a trip mechanism opening the contacts
Operating principle of an arc-fault circuit interrupter: current-sensing circuitry and electronics separate normal arcing from arcing faults and trip the contacts only for a fault. Based on Milatovich (2008), p. 8-148.

The need for a separate device follows from the way overcurrent protection works. Fuses and circuit breakers are the most common overcurrent protective devices, and they open a circuit when the current would raise the conductor temperature above the rating of its insulation.[4] A common molded-case breaker has two elements: an electromagnetic trip that acts quickly on a high fault current and a bimetallic element that provides a time delay. The current must exceed the rating before the breaker trips.[5] A glossary used in fire hazard analysis defines a high-impedance fault as one whose current stays below the trip point of the breaker on the circuit.[6] Arcing faults have a low and erratic current, so they can continue undetected by such conventional devices and ignite nearby materials.[1]

Faults addressed

The handbook distinguishes three types of arc fault. A parallel arc fault results from direct contact between two conductors of opposite polarity, for example in a damaged extension cord. A ground arc fault is an arc between a single conductor and ground, for example in an improperly installed wall receptacle. A series arc fault is an arc across a break in one conductor, for example in a cable pierced by a nail.[1] Short circuits, by contrast, are usually high and rapid current flows that conventional protective devices detect quickly.[1]

The handbook lists the common situations in which arcing leads to fire. Insulation deteriorates with age, and extension cords are caught in a doorjamb or crimped between furniture and a wall. Cord insulation is damaged by sunlight or by a hot air duct, appliance cords fray, and the insulation of internal appliance wiring becomes impaired.[1] Appliance wire is damaged by constant use, bending and abuse, and wire stapled too tightly against a stud has its insulation cut or damaged. Overheated cords or wires, exposed stranded wiring on old-style plug caps and receptacles with loose connections complete the list.[1]

Cords explain why the AFCI also protects equipment beyond the fixed wiring. Electrical cord fires are described as a leading cause of residential fires in the United States, and extension cord fires remain a major problem.[7] Circuit breakers and fuses are designed to protect the fixed wiring. They allow an overload to persist for a time, according to their inverse-time trip curve, and do not provide overload protection for extension cords.[7] A series fault in a cord or a parallel fault through damaged insulation leads to carbon tracking within the cord set, then to leakage current, arcing and finally combustion.[7]

Development and the fire problem

In the United States in the mid- to late 1980s, home wiring fires averaged 17,000 a year with more than 150 deaths a year. At that time the CPSC identified arc-fault detection as a promising new technology, and its electrical engineers later tested AFCIs and found them effective.[1] The technology was first used to protect the areas around downed utility lines. Advances in electronics then made it available for 125 V branch circuits of 15 or 20 A.[1]

Two small bar charts comparing US home wiring fires and deaths in the mid to late 1980s with fixed wiring fires and deaths in 1998
Home wiring fires and civilian deaths in the United States: average for the mid- to late 1980s and the 1998 values for fixed wiring in homes. Based on Milatovich (2008), p. 8-148.

In 1998, fixed wiring in homes accounted for 13,000 reported structure fires, with 96 civilian deaths and 293 civilian injuries.[1] That corresponds to about 0.74 deaths and 2.3 injuries per 100 fires. The earlier estimate covers “home wiring”, while the 1998 estimate specifies fixed wiring, so the pair does not establish a trend.

Broader statistics show the size of the target. In 1994–1998, an average of 49,700 United States structure fires a year originated with electrical distribution equipment. Fixed wiring accounted for 17,800 of them, cords or plugs for 8,000 and switches, receptacles or outlets for 5,700, together about 63% of the total.[8] In 1999–2002, electrical distribution or lighting equipment caused an average of 32,400 home fires a year, with 220 civilian deaths and $679 million in direct property damage.[9] In United States home fires of the same period, arcing was the heat source in 12% of the fires, and a short circuit or other electrical malfunction was the factor contributing to ignition in 18%.[10]

Most of these home fires occur in one- and two-family dwellings. There, electrical distribution or lighting equipment caused 27,900 fires a year in 1999–2002, about 86% of the home total, and 200 civilian deaths, a very close fifth among the causes of fire deaths.[11] Typical problems are frayed cords, broken switches or plugs, and bypassed protection such as oversized fuses or pennies in place of fuses. Overloaded cords, circuits or outlets and cords run through traffic areas or pinned by furniture are others.[11] Frayed cords and cords crimped by furniture also appear in the handbook's list of situations in which arcing leads to fire.[1] The CPSC's Hazard Analysis Group has carried out watershed analyses of home electrical fires, which the handbook names among the best-known examples of such analyses.[12]

Installation and application

According to the 2008 handbook, AFCIs can be installed in any single-pole 125 V branch circuit of 15 or 20 A, and at that time they were available as built-in features of circuit breakers.[1] In homes with conventional circuit breakers, an AFCI breaker can be installed in the panel box in place of an existing breaker. Homes with fuses were limited to receptacle-type or portable AFCIs, which were then expected to become available.[1] Installed in the panel, the AFCI breaker covers the branch wiring and the cords and equipment plugged into that circuit.[1]

House wall section with a panel, an AFCI breaker, branch wiring, a receptacle, an extension cord and a lamp, with the protected zone shaded
An AFCI breaker in the panel protects the 125 V, 15 or 20 A branch circuit, including power cords, extension cords and the internal wiring of connected equipment. Based on Milatovich (2008), p. 8-148.

The handbook chapter refers to the 2005 edition of the National Electrical Code (NEC) and states that the then current edition would contain updated AFCI requirements, without listing them.[2][1] The detailed scope of NEC requirements for AFCIs, such as the rooms or circuits covered, is therefore not given in the source documents. Other NEC rules limit the distance between appliances and outlets. In dwellings, no point along the floor line should be more than 1.8 m (6 ft) from a receptacle. A lamp or appliance with a 1.8 m cord can then stand anywhere along the wall.[13]

An AFCI does not replace good workmanship. One benchmark study found that 61% of home electrical fires involved code violations, particularly of the general workmanship provisions, and exposed elements such as cords are especially open to abuse by occupants.[9] The handbook also advises that repairs and modifications in one- and two-family dwellings be carried out by knowledgeable, experienced people in strict accordance with the applicable codes.[11] In fire engineering frameworks such as the International Fire Engineering Guidelines (2005), electrical safety equipment is one of the measures listed for limiting fire initiation.[14]

Comparison with GFCI and LCDI

The AFCI should not be confused with the ground-fault circuit interrupter (GFCI). The GFCI protects people from severe or fatal electric shocks, whereas the AFCI protects against fires caused by arcing faults.[1] A GFCI senses when even a small current passes to ground through a path other than the proper conductor and then trips almost instantly.[5]

The 2008 handbook says available GFCIs operate when the line-to-ground current exceeds 5 mA, and evaluation standards permit a range of 4–6 mA.[5] The trip time is about 25 ms (1/40 s) once the fault reaches 6 mA. Class A devices trip at not more than 6 mA and are used where personnel protection is required. Class B devices trip above 20 mA and serve only pool lighting installed before local adoption of the 1965 NEC.[15] As little as 20 mA can kill a healthy adult under certain conditions, far below the 15 or 20 A rating of lighting and receptacle circuits.[5] A 15 A rating is 3000 times the 5 mA trip current of a GFCI.

Logarithmic current scale from 1 mA to 10,000 A with GFCI trip current, 20 mA body current, 15 and 20 A branch ratings and ground-fault protection levels
Current levels of protective devices on a logarithmic scale, from the 5 mA trip current of a GFCI to the ground-fault protection levels of large services, as summarised for the 2005 NEC. Based on Milatovich (2008), pp. 8-140 and 8-146–8-147.

The GFCI can protect against some electrical fires, because it detects arcing and other faults to ground. It cannot detect the hazardous across-the-line arcing faults between conductors that can cause fires.[1] The two devices are therefore complementary, and in 2008 combination devices with both AFCI and GFCI protection in one unit were expected to become available soon, based on CPSC reports.[1] The 2005 NEC, as summarised in the handbook, requires GFCI protection by location, for example for 125 V receptacles of 15 and 20 A in dwelling bathrooms, garages, outdoors, unfinished basements and at kitchen countertops.[15]

A third device works on the cord itself. The leakage current detection and interruption (LCDI) device is similar to an AFCI and is usually provided by the manufacturer in the power supply cord of a piece of equipment.[1] If the cord is damaged, current begins to leak from the conductor to a shield. Electronics in the plug sense this current and disconnect the power in less than 25 milliseconds.[7]

For large services, a different device deals with arcing to ground. In the United States, ground-fault protection of equipment was first required by the 1971 NEC on services of 1000 A or more at 480Y/277 V, because of an unusually high number of burndowns.[16] The NEC limits the duration of fault currents above 3000 A to no more than 1 second. This limits the damage done by an arcing ground fault, which is directly proportional to the time the arc burns.[16]

Limits

The handbook text dates from 2008 and records a technology still in development. It describes AFCIs as expected to provide enhanced protection and notes that other device types and combination devices were still to come.[1] It gives no measured effectiveness, such as the share of arcing fires prevented, and the source documents contain no fire statistics from after 2002. The AFCI devices described in the handbook are for 125 V branch circuits of 15 or 20 A.[1] High-energy arcing faults occur in switchgear, load centres and bus ducts of 440 V and above, which lie outside that range.[17]

The arc-detection function addresses only arcing. Electricity can also cause fires by overheating, for example when the current exceeds the ampacity of a conductor and the heat degrades the insulation.[18] Equipment with hot surfaces placed too close to combustibles is involved in many fires that are not electrical failures at all.[19] Not every arc ignites a fuel, either. An arc may be far above the ignition temperature of a material yet too short to deliver enough energy; investigators assess this as the question of a competent ignition source.[20] After a fire, the locations of arcs on energised circuits help investigators to reconstruct its progression, a technique called arc fault mapping.[21]

Risk analysis offers a way to frame the benefit. For products that start fires as heat sources, such as wiring and cords, fire risk is measured solely by whether ignition occurs. Fire risk in general is usually expressed as expected loss, the sum over all fires of probability times severity.[22] An AFCI works on the probability term, because de-energising the circuit reduces the potential for a fire to occur.[1] A value for its effect on that probability is not given in the source documents.

See also

Notes

  1. ↑ 1.00 1.01 1.02 1.03 1.04 1.05 1.06 1.07 1.08 1.09 1.10 1.11 1.12 1.13 1.14 1.15 1.16 1.17 1.18 1.19 1.20 1.21 1.22 1.23 1.24 1.25 1.26 1.27 1.28 Milatovich (2008), p. 8-148.
  2. ↑ 2.0 2.1 Milatovich (2008), p. 8-127.
  3. ↑ Iqbal and Salley (2004), p. F-5.
  4. ↑ Milatovich (2008), p. 8-145.
  5. ↑ 5.0 5.1 5.2 5.3 Milatovich (2008), p. 8-146.
  6. ↑ Generic Letter 86-10, as cited in Iqbal and Salley (2004), p. F-36.
  7. ↑ 7.0 7.1 7.2 7.3 Milatovich (2008), p. 8-149.
  8. ↑ Milatovich (2008), p. 8-136.
  9. ↑ 9.0 9.1 Hall and Cote (2008), p. 3-15.
  10. ↑ Ahrens et al. (2008), p. 3-72.
  11. ↑ 11.0 11.1 11.2 Lathrop (2008b), p. 20-58.
  12. ↑ Hall (2008), p. 5-118.
  13. ↑ Milatovich (2008), p. 8-151.
  14. ↑ National Research Council of Canada et al. (2005), p. 1.2-10.
  15. ↑ 15.0 15.1 Milatovich (2008), p. 8-147.
  16. ↑ 16.0 16.1 Milatovich (2008), p. 8-140.
  17. ↑ Nowlen et al. (2005b), p. M-1.
  18. ↑ Milatovich (2008), p. 8-131.
  19. ↑ Milatovich (2008), p. 8-135.
  20. ↑ Custer and Sheppard (2008), p. 3-37.
  21. ↑ Custer and Sheppard (2008), p. 3-35.
  22. ↑ Hall (2002b), p. 5-143.

References

  • Ahrens, M., Frazier, P., & Kelch, G. (2008). Use of fire incident data and statistics. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 3-61–3-92). National Fire Protection Association.
  • Custer, R. L. P., & Sheppard, D. T. (2008). Fire loss investigation. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 3-31–3-41). National Fire Protection Association.
  • Hall, J. R., Jr. (2002b). Product fire risk. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 5-143–5-152). National Fire Protection Association; Society of Fire Protection Engineers.
  • Hall, J. R., Jr. (2008). Using data for public education planning and decision making. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 5-103–5-118). National Fire Protection Association.
  • Hall, J. R., Jr., & Cote, A. E. (2008). An overview of the fire problem and fire protection. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 3-3–3-30). National Fire Protection Association.
  • Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.
  • Lathrop, J. K. (2008b). One- and two-family dwellings. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 20-55–20-61). National Fire Protection Association.
  • Milatovich, R. M. (2008). Electrical systems and appliances. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 8-127–8-173). National Fire Protection Association.
  • National Research Council of Canada, International Code Council, Department of Building and Housing, & Australian Building Codes Board. (2005). International fire engineering guidelines (2005 ed.). Australian Building Codes Board.
  • Nowlen, S. P., Najafi, B., Wyant, F. J., Forester, J., Kazarians, M., Kolaczkowski, A., Joglar, F., Funk, D., Hannaman, G., & Anoba, R. (2005b). EPRI/NRC-RES fire PRA methodology for nuclear power facilities: Vol. 2. Detailed methodology (NUREG/CR-6850; EPRI 1011989). Electric Power Research Institute; U.S. Nuclear Regulatory Commission, Office of Nuclear Regulatory Research.