A flammable gas is a substance that is a gas at normal temperature and pressure and that burns when mixed with air in the right proportions.[1] In the United States, the formal definition in NFPA 55 and in the transport regulations of the Department of Transportation (DOT) rests on two tests. The gas must be ignitable in a mixture of 13 % or less by volume with air, or have a flammable range in air at least 12 percentage points wide.[1][2] Common examples are natural gas, propane, butane, hydrogen, acetylene and ethylene.[3]
Unlike a flammable liquid, a flammable gas does not first have to evaporate, so it can always ignite once it is released and mixed with air.[2] The Fire Protection Handbook distinguishes two basic hazards of a release: a combustion explosion inside a building or structure, and a fire.[3] An enclosure that is only partly filled with a flammable mixture can already be destroyed, because ordinary structures withstand only a few kilopascals.[4] Outdoors, a release can burn as a jet flame, as a flash fire through a drifting cloud, or as a vapour cloud explosion.[5][6] Protection relies on tight containment, odorisation, ventilation, control of ignition sources, gas detection and water cooling of exposed containers.[4][7]
Definition and classification
The handbook chapter on gases uses the term gas only for substances that are gaseous at normal temperature and pressure (NTP), about 21 °C (70 °F) and 101 kPa.[1] In the United States, NFPA 55, as described in the 2008 edition of the Fire Protection Handbook, is the standard for the storage, use and handling of compressed gases. It defines a flammable gas as a material that is a gas at 20 °C (68 °F) or less at 101.325 kPa.[1] It must also be ignitable at that pressure in a mixture of 13 % or less by volume with air, or have a flammable range with air of at least 12 %, regardless of the lower limit.[1] A flammable liquefied gas is a liquefied compressed gas that is partly liquid at 20 °C in its charged container and that is flammable.[2]
Lemoff notes that these definitions are the same as those of the DOT regulations, and therefore identical to those used for labelling gases in transport in the United States.[2] They are also essentially identical to the United Nations protocols for international gas shipments.[2] In the DOT hazard classes, flammable gases form Division 2.1, with propane, butadiene, acetylene and methyl chloride as examples.[8] In the 2007 edition of NFPA 704, the highest flammability rating, 4, covers materials that turn rapidly or completely into vapour at atmospheric pressure and normal ambient temperature and burn readily.[9]
NFPA 55 places flammable gases among the physical-hazard classes, next to nonflammable, oxidising, pyrophoric and unstable reactive gases.[2] Pyrophoric gases are flammable gases that ignite spontaneously in air, such as silane and phosphine, and are found mostly in semiconductor manufacturing.[2] Some gases that can be made to burn are still treated as nonflammable because their range is narrow or their lower limit high. Anhydrous ammonia is the standard example: the DOT classifies it as a nonflammable gas for interstate transport.[2]
The flash point, which is central to the classification of flammable liquids, has no practical meaning for flammable gases.[2] A flammable gas normally exists above its boiling point, even when it is stored as a liquid, and therefore always above its flash point.[2] By usage, the most widely used fuel gases are natural gas and the liquefied petroleum gases butane and propane.[10]
Combustion properties
Introduction to Fire Safety Engineering explains that a flammable gas burns only when it mixes with oxygen in the right proportion and enough energy is available to ignite the mixture.[11] The ideal proportion is the stoichiometric ratio, and the further a mixture departs from it, the more slowly it burns.[12] The stoichiometric fuel fraction in air is 0.095 for methane, 0.040 for propane and 0.296 for hydrogen.[13]
Every flammable gas has a lower and an upper flammable limit. A mixture with air ignites only between these flammability limits, and only when at least the minimum ignition energy is supplied.[2] The SFPE Handbook defines the limits as the range of compositions within which a premixed flame can propagate, at a specified temperature and pressure.[14] For most simple hydrocarbons, the limits in air correspond to equivalence ratios of about 0.5 and 3.[14] Adding oxygen raises the upper limit but hardly changes the lower limit, and both limits widen as the temperature rises.[15] The lower limit is insensitive to pressure except well below atmospheric, while the upper limit rises above atmospheric pressure.[15]
The table below gives the combustion properties of common flammable gases from the handbook. The specific gravity compares the density of the gas with that of air.[3]
| Gas | Lower limit (vol %) | Upper limit (vol %) | Specific gravity (air = 1) | Ignition temperature (°C) |
|---|---|---|---|---|
| Natural gas (high methane type) | 4.7 | 15.0 | 0.590–0.614 | 482–632 |
| Propane (commercial) | 2.15 | 9.6 | 1.52 | 493–604 |
| Butane (commercial) | 1.9 | 8.5 | 2.0 | 482–538 |
| Acetylene | 2.5 | 81.0 | 0.91 | 305 |
| Hydrogen | 4.0 | 75.0 | 0.07 | 500 |
| Ethylene | 2.7 | 36.0 | 0.98 | 490 |
| Carbon monoxide | 12.5 | 74.0 | 0.97 | 609 |
| Anhydrous ammonia | 16.0 | 25.0 | 0.60 | 651 |
Ignition energies differ by orders of magnitude. In dry air at 1 atm and 25 °C, the minimum ignition energy is 0.016 mJ for hydrogen and 0.017 mJ for acetylene. Methane needs 0.21 mJ and propane 0.24 mJ, while ammonia needs 680 mJ.[16] Hydrogen also has an extremely wide flammable range and the highest burning velocity of any gas, and it burns with a nearly invisible flame.[17] Ethylene combines a wide flammable range with a high burning velocity.[18] Ammonia, by contrast, owes its limited flammability to its high lower limit and low heat of combustion.[19]
Gas concentrations are usually expressed as a percentage of the lower flammable limit (% LFL). For a gas with a lower limit of 4.0 %, a reading of 25 % LFL means 1 % gas by volume in the sample.[20] The older terms lower and upper explosive limit (LEL and UEL) are still found in the literature for the same concentrations.[20] NUREG-1805 states that the terms explosive limits and flammable limits are used interchangeably.[21] Lemoff, however, notes that hydrogen has a recognised explosive range that is narrower than its flammable range. He recommends that the term explosive range be used only for hydrogen.[2]
Hazards in containers
Gases expand when heated, so a fire raises the container pressure. This can open a pressure-relief valve or cause the container to fail, and a heated container can also lose its strength.[10] Container failure releases the energy stored by compression or liquefaction, often extremely rapidly and violently.[22] Failures of compressed gas containers are marked mainly by flying fragments. Liquefied gas containers hold far more gas and can release larger quantities.[22]
Liquefied flammable gases such as liquefied petroleum gas add the hazard of the boiling liquid expanding vapour explosion (BLEVE). When such a container fails, about one-third of the liquid can turn to vapour at normal temperatures, and often more than half in a fire.[23] Container pieces can be thrown up to about 0.8 km (½ mile), and fatal burns have occurred up to 76 m from larger containers.[24] In the LP-gas disaster near Mexico City on 19 November 1984, about 15 BLEVEs were recorded, and some 500 deaths were reported.[24]
A flammable gas can also burn inside a container. Gas–air or gas–oxygen mixtures are seldom made in containers on purpose but can form by accident, for example in piping that carries both oxygen and a fuel gas for cutting and welding. Oxygen–fuel gas cutting systems therefore have special backflow prevention devices.[25]
Hazards after release
The handbook describes a combustion explosion as a sequence of events. The gas escapes, mixes with air and forms an ignitable mixture within its flammable range. Once ignited, the mixture burns rapidly and heats the surrounding air, which expands.[3] If the air is confined in a room, the pressure rises until some part of the structure gives way.[3] The handbook also calls this a room explosion or vapour–air explosion, but notes that these names are less accurate.[3]
The vulnerability of buildings follows from two numbers. An enclosure completely filled with a flammable gas–air mixture would have to withstand about 414 to 758 kPa (60 to 110 psi) to stay intact.[4] Conventional structures withstand only about 3.45 to 6.89 kPa (0.5 to 1.0 psi).[4] Most combustion explosions in conventional structures therefore occur with less than 25 % of the enclosure occupied by the flammable mixture.[4] Because most flammable mixtures are about 90 % air, whether the gas is lighter or heavier than air matters less inside structures than might be expected.[4]
Lemoff describes a gas fire as an aborted combustion explosion. The mixture ignites before an explosive quantity can accumulate, or there is no structure to confine it.[4] Outdoors, fires are therefore more likely than explosions. After a massive release, however, the surrounding air or buildings can provide enough confinement for an open-air explosion.[4] Liquefied noncryogenic gases, hydrogen, ethylene and some reactive gases with a high flame speed are subject to this.[4]
A leak from a pressurised pipe or hose can form a gas jet that is easily ignited into a large turbulent flame.[26] The fuel flow of such a jet fire is set by the leak orifice rather than by heat transfer from the flame.[26] Near or within the flames, its radiation can reach 120 to 160 kW/m².[27] Where jet flames engulf a target, the SFPE Handbook reports heat fluxes of up to 250 kW/m² for two-phase LPG jets and 300 kW/m² for sonic natural gas jets.[28]
If the release is not ignited at once, a cloud forms and drifts downwind. A remote ignition source can then ignite it, producing a vapour cloud fire, or flash fire, that burns back towards the release point.[5] The burning cloud can then start a steady jet flame or pool fire at the source.[5] Where the cloud is large and the flame accelerates, a vapour cloud explosion can follow. Turbulent jet releases, partial confinement, congested equipment and ignition delays all promote the rapid flame speeds involved.[6] Damaging overpressures in a virtually unconfined cloud need flame speeds of the order of 100 m/s.[6] Propane, propylene, ethylene and aromatic hydrocarbons have been involved in many such explosions.[6]
Flammable gases also arise from processes. In nuclear power plants the most common is hydrogen, used to cool generators and released in battery rooms.[29] In electric vehicles, a battery in thermal runaway can release flammable gases. Ignited, they can cause a flare fire or a gas cloud explosion.[30] If they are not ignited at once, they can accumulate in a confined or poorly ventilated car park and explode once the lower explosion limit is reached.[31]
Prevention and protection
The basic safeguards against a combustion explosion limit the formation of a flammable mixture in a structure. They include rugged containers and equipment, emergency flow-control devices and limiting orifices.[4] Burners are often fitted with flame-failure devices that shut off the gas if the flame goes out.[4] Many gases are colourless and odourless. Codes, standards and regulations therefore require natural gas and LP-gas to be odorised, so that people with a normal sense of smell can detect them at one-fifth of the lower limit.[4] Odorisation has limits: nobody may be present, the sense of smell tires and varies, and some soils scrub the odorant from leaking underground gas.[4]
Control of ignition sources is the second line of defence, but it is practical mainly in industrial operations.[4] In the United States, flammable gas storage areas without filling operations are generally classified as Division 2 locations for electrical equipment.[32] Gases are assigned to groups by testing the gap through which a flame can pass, and most flammable gases fall in Groups C and D.[32] Acetylene is the only Group A gas and hydrogen is Group B.[32] NUREG-1805 lists ethylene as a Group C and propane as a Group D example.[33] A gas leak can also create its own ignition source. Gases such as natural gas, methane, ethane and propane are dielectrics, and flow from a high-pressure leak can build up static charges that discharge as sparks.[34]
A gas detection system provides warning before a mixture becomes flammable. The handbook notes that, apart from NFPA 720 for carbon monoxide, no NFPA standard covered the design of flammable gas detection in commercial or industrial occupancies.[35] Common sensors use a catalytic bead on which the gas burns, giving a signal in proportion to its concentration.[36] Such systems usually need monthly calibration with a test gas, typically at 50 % LFL.[34]
In storage, containers of flammable gases should not be kept with oxidising gases such as oxygen and nitrous oxide. These increase the speed of burning and allow explosions of fuel–oxidant mixtures.[37] In the United States, NFPA 55, as described by Lemoff and Rivkin (2008), requires separation of flammable, oxidising, toxic, pyrophoric and unstable reactive gases.[37] Indoor storage of more than about 70.8 m³ (2500 standard cubic feet) of flammable gas needs separation into groups or sprinkler protection.[38] For large containers of liquefied flammable gas, NFPA 15 requires water spray at more than 10.2 (L/min)/m² (0.25 gpm/ft²) of container surface to prevent failure.[38] Deflagration venting according to NFPA 68 can limit explosion damage, but is applied to industrial structures rather than ordinary buildings.[4]
Emergency control
The handbook separates "no fire" and "fire" emergencies.[4] In a no-fire emergency the gas is directed, diluted and dispersed with a carrier fluid, while the flow is stopped where possible.[7] Liquefied gases are visible as a fog of condensed water vapour, but ignitable mixtures often extend some distance beyond it.[7]
In a fire emergency, water is applied to control the heat while the gas flow is stopped if possible.[7] Many gas fires can be put out with carbon dioxide, dry chemical or halogenated agents. If gas keeps escaping after extinguishment, however, the fire can turn into a combustion explosion. Accepted practice is therefore to extinguish only small leaks that would be harmless if they reignited.[7]
Calculation examples
Two simple checks follow from the definitions and data above. The first applies the two tests of the NFPA 55 and DOT definition to the gases in the table. Natural gas, propane and butane meet the first test, with lower limits below 13 %, but their ranges are only 6.6 to 10.3 percentage points wide.[3] Hydrogen, acetylene, ethylene and carbon monoxide pass both tests.[3] Blast furnace gas, with a lower limit of 33.2 %, passes only through its range of 38 points.[3] Anhydrous ammonia fails both: its lower limit of 16 % exceeds 13 %, and its range of 9 points is less than 12. This explains why the DOT lists it as a nonflammable gas in Division 2.2.[2][8]
The second check estimates how a steady leak builds up in a ventilated room. NUREG-1805 gives the method of NFPA 69 for a constant gas source in an enclosed volume.[39] The concentration approaches the ratio of the gas release rate to the ventilation rate, at a speed set by the number of air changes:[39]
| Symbol | Description | Unit |
|---|---|---|
| average gas concentration by volume | – | |
| gas release rate | m³/min | |
| ventilation air flow rate | m³/min | |
| mixing efficiency factor (1.0 for perfect mixing) | – | |
| number of theoretical air changes | – | |
| time since the start of the leak | min | |
| room volume | m³ |
The mixing factor ranges from 0.2 for rooms ventilated only by infiltration through cracks to 0.9 for a perforated ceiling supply with several exhausts.[40] As an assumed example, a room of 4 m × 4 m × 3 m (48 m³) has two air changes per hour, or 1.6 m³/min. A natural gas leak of 0.02 m³/min then gives a long-term average concentration of 0.02/1.6 = 1.25 %. That is 27 % of the lower limit of 4.7 %, so a perfectly mixed room never becomes flammable.[3] The concentration reaches one-fifth of the lower limit, 0.94 %, when 1 − e−KN = 0.75. With perfect mixing (K = 1) this takes 1.39 air changes, or about 41 minutes.
The same leak of propane would reach 58 % of its lower limit of 2.15 %.[3] In this room, a propane leak of about 0.034 m³/min, or 3.7 kg/h, would bring the average concentration to the lower limit. Real rooms are not perfectly mixed, and the handbook warns that practical ventilation systems can handle only rather nominal release rates.[4] A layer or pocket near the leak can therefore be flammable long before the average is.
The SFPE Handbook gives a simple estimate of what such a pocket can do. The pressure rise in a closed enclosure is the closed-vessel pressure multiplied by the fraction of the total mass that burns:[41]
Here P − P0 is the pressure rise, Pm − P0 the closed-vessel deflagration pressure, mb the burned mass and m0 the total mass in the enclosure. For propane–air, Pm − P0 is 7.9 bar.[42] A stoichiometric mixture has almost the density of air, so the mass fraction is close to the volume fraction of the room that the mixture fills.[43] A pocket filling only 1 % of the room would then raise the pressure by about 7.9 kPa if no venting occurred. That exceeds the 3.45 to 6.89 kPa that conventional structures withstand, which agrees with the handbook statement on partly filled rooms.[4]
Limitations and uncertainty
The definitions in this article are American and international transport definitions as described in the 2008 Fire Protection Handbook.[1][2] Other codes and regulations use somewhat different descriptions of related terms such as compressed gas and liquefied gas.[44] The handbook itself notes that a gas such as ammonia can burn and yet be classified as nonflammable for transport.[2] A classification is therefore a regulatory label, and it does not mean that a gas cannot burn or explode in an enclosure.[45]
Tabulated limits depend on the test method. Beyler gives 5 % and 15 % by volume for methane in air, while the handbook table gives 4.7 % and 15.0 % for high-methane natural gas.[14][3] The standard Bureau of Mines method uses a vertical tube 1.5 m long and 0.05 m wide, and limits for downward propagation are narrower than for upward propagation.[14][15] Commercial propane and butane are mixtures, and natural gas compositions vary, so the limits of a real gas can differ from those in a table.[3] Limits also widen with temperature and, for the upper limit, with pressure and oxygen content.[15]
The calculation methods above are first-order approximations. The NFPA 69 buildup equation gives an average concentration and assumes a constant leak and a fixed mixing factor.[39][40] The partial-volume estimate ignores venting through windows and doors and assumes that the burned mixture is stoichiometric.[41]
See also
Notes
- ↑ 1.0 1.1 1.2 1.3 1.4 1.5 Lemoff (2008), p. 6-165.
- ↑ 2.00 2.01 2.02 2.03 2.04 2.05 2.06 2.07 2.08 2.09 2.10 2.11 2.12 2.13 2.14 Lemoff (2008), p. 6-166.
- ↑ 3.00 3.01 3.02 3.03 3.04 3.05 3.06 3.07 3.08 3.09 3.10 3.11 3.12 3.13 Lemoff (2008), p. 6-174, Table 6.10.3.
- ↑ 4.00 4.01 4.02 4.03 4.04 4.05 4.06 4.07 4.08 4.09 4.10 4.11 4.12 4.13 4.14 4.15 4.16 4.17 Lemoff (2008), p. 6-175.
- ↑ 5.0 5.1 5.2 Beyler (2002a), p. 3-269.
- ↑ 6.0 6.1 6.2 6.3 Zalosh (2008), p. 2-104.
- ↑ 7.0 7.1 7.2 7.3 7.4 Lemoff (2008), p. 6-176.
- ↑ 8.0 8.1 C. J. Wright (2008a), pp. 13-119–13-120.
- ↑ C. J. Wright (2008a), p. 13-123.
- ↑ 10.0 10.1 Lemoff (2008), p. 6-168.
- ↑ Van Rossum (2027), §3.1.
- ↑ Van Rossum (2027), §3.3.
- ↑ Zalosh (2008), p. 2-98.
- ↑ 14.0 14.1 14.2 14.3 Beyler (2002b), p. 2-172.
- ↑ 15.0 15.1 15.2 15.3 Beyler (2002b), pp. 2-173–2-174.
- ↑ Britton (1999), as cited in Ural and Garzia (2008), p. 17-147.
- ↑ Lemoff (2008), pp. 6-181–6-182.
- ↑ Lemoff (2008), pp. 6-180–6-181.
- ↑ Lemoff (2008), pp. 6-178–6-179.
- ↑ 20.0 20.1 Cholin (2008a), p. 14-100.
- ↑ Iqbal and Salley (2004), p. B-25.
- ↑ 22.0 22.1 Lemoff (2008), p. 6-169.
- ↑ Lemoff (2008), pp. 6-170–6-171.
- ↑ 24.0 24.1 Lemoff (2008), p. 6-172.
- ↑ Lemoff (2008), p. 6-173.
- ↑ 26.0 26.1 Alpert (2008), p. 2-21.
- ↑ Alpert (2008), p. 2-22.
- ↑ Cowley and Prichard (1990), as cited in Beyler (2002a), p. 3-302.
- ↑ Iqbal and Salley (2004), p. 1-8.
- ↑ Van der Graaf et al. (2021/2023), p. 22.
- ↑ Van der Graaf et al. (2021/2023), p. 27.
- ↑ 32.0 32.1 32.2 Lemoff and Rivkin (2008), p. 7-41.
- ↑ Iqbal and Salley (2004), p. B-24.
- ↑ 34.0 34.1 Cholin (2008a), p. 14-109.
- ↑ Cholin (2008a), p. 14-99.
- ↑ Cholin (2008a), p. 14-103.
- ↑ 37.0 37.1 Lemoff and Rivkin (2008), p. 7-38.
- ↑ 38.0 38.1 Lemoff and Rivkin (2008), p. 7-40.
- ↑ 39.0 39.1 39.2 Iqbal and Salley (2004), p. 16-9.
- ↑ 40.0 40.1 Iqbal and Salley (2004), p. 16-10.
- ↑ 41.0 41.1 Zalosh (2002), p. 3-408.
- ↑ Zalosh (2002), p. 3-407.
- ↑ Zalosh (2002), p. 3-410.
- ↑ Lemoff (2008), p. 6-167.
- ↑ Lemoff (2008), p. 6-179.
References
- Alpert, R. L. (2008). Physics of fire configuration. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 2-21–2-29). National Fire Protection Association.
- Beyler, C. L. (2002a). Fire hazard calculations for large, open hydrocarbon fires. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 3-268–3-314). National Fire Protection Association; Society of Fire Protection Engineers.
- Beyler, C. L. (2002b). Flammability limits of premixed and diffusion flames. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-172–2-187). National Fire Protection Association; Society of Fire Protection Engineers.
- Cholin, J. M. (2008a). Gas and vapor detection systems and monitors. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 14-99–14-112). National Fire Protection Association.
- Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.
- Lemoff, T. C. (2008). Gases. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-165–6-186). National Fire Protection Association.
- Lemoff, T. C., & Rivkin, C. H. (2008). Storage of gases. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 7-35–7-42). National Fire Protection Association.
- Ural, E. A., & Garzia, H. W. (2008). Explosion prevention and protection. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 17-141–17-165). National Fire Protection Association.
- Van der Graaf, J., Hessels, T., & Rosmuller, N. (2023). Fire safety of indoor car parks accommodating electrically powered vehicles. Nederlands Instituut Publieke Veiligheid. (Original work published 2021)
- Van Rossum, E. (2027). Introduction to Fire Safety Engineering. Fire Safety Academy.
- Wright, C. J. (2008a). Managing the response to hazardous material incidents. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 13-117–13-144). National Fire Protection Association.
- Zalosh, R. (2002). Explosion protection. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 3-402–3-421). National Fire Protection Association; Society of Fire Protection Engineers.
- Zalosh, R. (2008). Explosions. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 2-93–2-106). National Fire Protection Association.