Fse-sprinkler-skipping-v2.svg (SVG file, nominally 900 × 600 pixels, file size: 20 KB)
Summary
Calculated temperature of a standard response sprinkler link in a 1,000 kW fire, without droplets and with liquid volume fractions of 1 and 2 millionths in the ceiling jet.
Original illustration for Sprinkler skipping, level 4 Expert.
- Alt text: Line chart: link temperature rising towards 88 °C; it reaches 74 °C at 174 s without droplets, 234 s and 361 s with droplets.
Licensing
New drawing by Fire Safety Academy. © Fire Safety Academy.