Summary

Temperature of the sensing element of two heat detectors in a steady ceiling jet of 153 °C and 2.4 m/s; the 57 °C rating is reached after about 11.6 s (RTI 55) and 6.3 s (RTI 30).

Original illustration for Detector activation time, level 4 Expert.

  • Alt text: Line chart: element temperatures for RTI 55 and RTI 30 rise towards a 153 °C gas temperature and cross the 57 °C rating after 11.6 s and 6.3 s.