Electronic inputs can include contacts, motion detection, sound detection and other methods. Their effectiveness depends on the protected opening or space and on expected environmental disturbances. Exterior detection has to distinguish relevant intrusions from normal site conditions. Interior arrangements must account for the coverage actually provided by their sensing method.<ref name="F-bd1175fbdc">Cote et al. (2008), chapter 14.10, pp. 14-126–14-127.</ref> | Electronic inputs can include contacts, motion detection, sound detection and other methods. Their effectiveness depends on the protected opening or space and on expected environmental disturbances. Exterior detection has to distinguish relevant intrusions from normal site conditions. Interior arrangements must account for the coverage actually provided by their sensing method.<ref name="F-bd1175fbdc">Cote et al. (2008), chapter 14.10, pp. 14-126–14-127.</ref> | ||
Transmission is a separate dependency. The handbook compares methods that reveal a lost communication path with arrangements that may not immediately report its loss. A backup path changes the available communication only if its operation and failure dependencies are understood. Receiving-station procedures also determine what follows a security message.<ref name="F-cf82a8fa4e">Cote et al. (2008), chapter 14.10, | Transmission is a separate dependency. The handbook compares methods that reveal a lost communication path with arrangements that may not immediately report its loss. A backup path changes the available communication only if its operation and failure dependencies are understood. Receiving-station procedures also determine what follows a security message.<ref name="F-cf82a8fa4e">Cote et al. (2008), chapter 14.10, p. 14-126.</ref> | ||
Access control can conflict with emergency movement if locking functions are considered independently of fire safety. The handbook discusses door-release arrangements that coordinate security equipment with the fire alarm installation. Integrated testing has to verify the intended behaviour during normal operation, a fire condition and relevant power failures. A functioning intrusion alarm does not establish a functioning escape arrangement.<ref name="F-c1c93d0c3f" /> | Access control can conflict with emergency movement if locking functions are considered independently of fire safety. The handbook discusses door-release arrangements that coordinate security equipment with the fire alarm installation. Integrated testing has to verify the intended behaviour during normal operation, a fire condition and relevant power failures. A functioning intrusion alarm does not establish a functioning escape arrangement.<ref name="F-c1c93d0c3f" /> | ||
== Devices, control and notification == | == Devices, control and notification == | ||
The SFPE Handbook describes detection, processing and signalling as separate elements of an alarm system. Detection supplies information about a possible fire. Processing interprets that information and determines the response. Signalling then warns occupants, sends information elsewhere or initiates another protective action. Keeping these functions distinct makes it possible to identify what a component actually contributes to the overall system.<ref name="S-fd76472e02">Schifiliti et al. (2002), | The SFPE Handbook describes detection, processing and signalling as separate elements of an alarm system. Detection supplies information about a possible fire. Processing interprets that information and determines the response. Signalling then warns occupants, sends information elsewhere or initiates another protective action. Keeping these functions distinct makes it possible to identify what a component actually contributes to the overall system.<ref name="S-fd76472e02">Schifiliti et al. (2002), p. 4-3.</ref> | ||
[[File:fse-intrusion-detection-system-v2.svg|thumb|upright=1.5|alt=Detection, processing and signalling in sequence, with processing and signalling inside the control equipment, power on a separate path and the response outside the control equipment.|Detection, processing and signalling as separate functions of an intrusion detection system.]] | [[File:fse-intrusion-detection-system-v2.svg|thumb|upright=1.5|alt=Detection, processing and signalling in sequence, with processing and signalling inside the control equipment, power on a separate path and the response outside the control equipment.|Detection, processing and signalling as separate functions of an intrusion detection system.]] | ||
| Line 26: | Line 26: | ||
== Alarm, supervisory and trouble conditions == | == Alarm, supervisory and trouble conditions == | ||
The Fire Protection Handbook distinguishes three signal categories. An alarm signal indicates a fire condition requiring an immediate response. A supervisory signal concerns the condition of another protection system being monitored. A trouble signal identifies a fault in the alarm system, its monitored circuits or its power supplies. These distinctions describe the meaning of the information, rather than the loudness of an indicator.<ref name="F-2e2884d4f3">Cote et al. (2008), chapter 14.1, | The Fire Protection Handbook distinguishes three signal categories. An alarm signal indicates a fire condition requiring an immediate response. A supervisory signal concerns the condition of another protection system being monitored. A trouble signal identifies a fault in the alarm system, its monitored circuits or its power supplies. These distinctions describe the meaning of the information, rather than the loudness of an indicator.<ref name="F-2e2884d4f3">Cote et al. (2008), chapter 14.1, p. 14-5.</ref> | ||
Sprinkler equipment provides a useful comparison. Waterflow associated with operation of the sprinkler installation can initiate a fire alarm. Movement of a monitored control valve away from its normal position can initiate a supervisory signal. A broken electrical connection to an input device can instead create a trouble condition. The same area of a building can therefore generate several signals that demand different investigations.<ref name="F-30475209b0">Cote et al. (2008), chapter 14.4, pp. 14-39–14-45.</ref> | Sprinkler equipment provides a useful comparison. Waterflow associated with operation of the sprinkler installation can initiate a fire alarm. Movement of a monitored control valve away from its normal position can initiate a supervisory signal. A broken electrical connection to an input device can instead create a trouble condition. The same area of a building can therefore generate several signals that demand different investigations.<ref name="F-30475209b0">Cote et al. (2008), chapter 14.4, pp. 14-39–14-45.</ref> | ||
| Line 32: | Line 32: | ||
Supervision can include both an off-normal condition and its restoration. The off-normal message identifies a condition needing attention. Restoration records that the monitored condition has returned to its normal state. Neither message, considered alone, demonstrates the performance of every part of the protected installation. The indicated condition has to be understood in relation to the particular switch, sensor or interface producing it.<ref name="F-2e2884d4f3" /><ref name="F-6bf2cd92da">Cote et al. (2008), chapter 14.4, pp. 14-43–14-45.</ref> | Supervision can include both an off-normal condition and its restoration. The off-normal message identifies a condition needing attention. Restoration records that the monitored condition has returned to its normal state. Neither message, considered alone, demonstrates the performance of every part of the protected installation. The indicated condition has to be understood in relation to the particular switch, sensor or interface producing it.<ref name="F-2e2884d4f3" /><ref name="F-6bf2cd92da">Cote et al. (2008), chapter 14.4, pp. 14-43–14-45.</ref> | ||
Correct signal differentiation depends on the circuit and the control logic working together. The handbook illustrates arrangements in which combining contacts incorrectly makes a closed valve indistinguishable from broken wiring. Addressable arrangements can share a communication circuit while retaining distinct device identities and signal categories. The relevant question is therefore whether the system preserves the required information under normal and fault conditions. Merely obtaining an electrical response is not sufficient evidence of correct classification.<ref name="F-771d907030">Cote et al. (2008), chapter 14.4, | Correct signal differentiation depends on the circuit and the control logic working together. The handbook illustrates arrangements in which combining contacts incorrectly makes a closed valve indistinguishable from broken wiring. Addressable arrangements can share a communication circuit while retaining distinct device identities and signal categories. The relevant question is therefore whether the system preserves the required information under normal and fault conditions. Merely obtaining an electrical response is not sufficient evidence of correct classification.<ref name="F-771d907030">Cote et al. (2008), chapter 14.4, p. 14-45.</ref> | ||
== Communication paths and fault behaviour == | == Communication paths and fault behaviour == | ||
An initiating device circuit connects conventional input devices to the control unit. A notification appliance circuit carries the output needed by the connected warning appliances. A signalling line circuit supports data communication, including communication with individually identified devices. These names describe circuit functions; they do not by themselves establish how the circuit behaves after damage.<ref name="F-0e490afc12">Cote et al. (2008), chapter 14.1, | An initiating device circuit connects conventional input devices to the control unit. A notification appliance circuit carries the output needed by the connected warning appliances. A signalling line circuit supports data communication, including communication with individually identified devices. These names describe circuit functions; they do not by themselves establish how the circuit behaves after damage.<ref name="F-0e490afc12">Cote et al. (2008), chapter 14.1, p. 14-6.</ref> | ||
In the conventional arrangement described by the handbook, a small current passes through an end-of-line device. This allows the control unit to distinguish an intact circuit from an open connection. Operation of an input contact changes the electrical condition so that the panel can recognise the intended signal. An intact electrical path is nevertheless only one condition of successful protection. It does not demonstrate that smoke can enter a detector or that a mechanical device can move.<ref name="F-0e490afc12" /><ref name="F-527d72e812">Cote et al. (2008), chapter 14.2, | In the conventional arrangement described by the handbook, a small current passes through an end-of-line device. This allows the control unit to distinguish an intact circuit from an open connection. Operation of an input contact changes the electrical condition so that the panel can recognise the intended signal. An intact electrical path is nevertheless only one condition of successful protection. It does not demonstrate that smoke can enter a detector or that a mechanical device can move.<ref name="F-0e490afc12" /><ref name="F-527d72e812">Cote et al. (2008), chapter 14.2, p. 14-28.</ref> | ||
The handbook's Class A and Class B descriptions concern operation in the presence of specified circuit faults. In its Class B example, equipment beyond an open circuit becomes unavailable. The Class A arrangement returns wiring to a suitably configured control unit, allowing operation on either side of a single open circuit. The classification consequently depends on equipment behaviour as well as the visible cable route. A loop-shaped drawing alone is not evidence of the claimed fault performance.<ref name="F-34a97ca319" /> | The handbook's Class A and Class B descriptions concern operation in the presence of specified circuit faults. In its Class B example, equipment beyond an open circuit becomes unavailable. The Class A arrangement returns wiring to a suitably configured control unit, allowing operation on either side of a single open circuit. The classification consequently depends on equipment behaviour as well as the visible cable route. A loop-shaped drawing alone is not evidence of the claimed fault performance.<ref name="F-34a97ca319" /> | ||
Addressable devices can be polled to confirm that they still communicate. Some arrangements also use isolators to restrict the consequences of a short circuit. These features can improve the information available about a fault, but they do not remove all common dependencies. Power, control equipment and configuration remain part of the path between an input and its required output. Testing therefore examines the complete response as well as individual communication links.<ref name="F-0e490afc12" /><ref name="F-da5fc124ca">Cote et al. (2008), chapter 14.2, | Addressable devices can be polled to confirm that they still communicate. Some arrangements also use isolators to restrict the consequences of a short circuit. These features can improve the information available about a fault, but they do not remove all common dependencies. Power, control equipment and configuration remain part of the path between an input and its required output. Testing therefore examines the complete response as well as individual communication links.<ref name="F-0e490afc12" /><ref name="F-da5fc124ca">Cote et al. (2008), chapter 14.2, p. 14-20.</ref><ref name="F-b787a07946">Cote et al. (2008), chapter 14.5, p. 14-62.</ref> | ||
== Interfaces with other protective systems == | == Interfaces with other protective systems == | ||
An alarm system can initiate actions beyond occupant warning. The handbook describes interfaces for door release, ventilation, smoke control, lifts and extinguishing systems. Each interface translates an input condition into a specified building response. The engineering question is whether that response supports the protection strategy for the actual location and fire scenario.<ref name="F-4871ee351b">Cote et al. (2008), chapter 14.1, | An alarm system can initiate actions beyond occupant warning. The handbook describes interfaces for door release, ventilation, smoke control, lifts and extinguishing systems. Each interface translates an input condition into a specified building response. The engineering question is whether that response supports the protection strategy for the actual location and fire scenario.<ref name="F-4871ee351b">Cote et al. (2008), chapter 14.1, p. 14-7.</ref><ref name="F-db1bc053f9">Cote et al. (2008), chapter 14.4, pp. 14-45–14-50.</ref> | ||
An interface is more than a connection between two terminals. The connected equipment must be compatible, the communication path must have the intended fault behaviour, and the operating sequence must be defined. A command to start a fan, for example, does not prove that the associated damper has reached its required position. The handbook illustrates feedback arrangements that return information about controlled equipment to the alarm system.<ref name="F-37cedef59b">Cote et al. (2008), chapter 14.4, pp. 14-47–14-49.</ref> | An interface is more than a connection between two terminals. The connected equipment must be compatible, the communication path must have the intended fault behaviour, and the operating sequence must be defined. A command to start a fan, for example, does not prove that the associated damper has reached its required position. The handbook illustrates feedback arrangements that return information about controlled equipment to the alarm system.<ref name="F-37cedef59b">Cote et al. (2008), chapter 14.4, pp. 14-47–14-49.</ref> | ||
| Line 50: | Line 50: | ||
Door controls illustrate the relationship between normal operation and the fire condition. An electrically held-open door can be arranged to release when its holding power is removed. Access-control equipment also has to be coordinated with the intended means of escape. Security objectives and emergency movement can conflict if their control functions are considered separately. The result depends on the particular door, power arrangement and control sequence.<ref name="F-5037f72703">Cote et al. (2008), chapter 14.4, pp. 14-46–14-47.</ref> | Door controls illustrate the relationship between normal operation and the fire condition. An electrically held-open door can be arranged to release when its holding power is removed. Access-control equipment also has to be coordinated with the intended means of escape. Security objectives and emergency movement can conflict if their control functions are considered separately. The result depends on the particular door, power arrangement and control sequence.<ref name="F-5037f72703">Cote et al. (2008), chapter 14.4, pp. 14-46–14-47.</ref> | ||
Interconnected systems need tests that follow the intended sequence across the interface. Testing a detector and testing a fan separately do not establish that the detector will initiate the correct fan response. Temporary bypasses used during tests also change the protection available. Documentation must therefore distinguish functions actually demonstrated from functions isolated during the test, and record their restoration. These observations support assessment of the integrated installation rather than only its individual products.<ref name="F-250bc1fa6a">Cote et al. (2008), chapter 14.4, | Interconnected systems need tests that follow the intended sequence across the interface. Testing a detector and testing a fan separately do not establish that the detector will initiate the correct fan response. Temporary bypasses used during tests also change the protection available. Documentation must therefore distinguish functions actually demonstrated from functions isolated during the test, and record their restoration. These observations support assessment of the integrated installation rather than only its individual products.<ref name="F-250bc1fa6a">Cote et al. (2008), chapter 14.4, p. 14-50.</ref><ref name="F-d70f9bf924">Cote et al. (2008), chapter 14.5, pp. 14-61–14-62.</ref> | ||
== Protection objectives and response time == | == Protection objectives and response time == | ||
Latest revision as of 01:34, 16 November 2026
An intrusion detection system identifies conditions associated with unauthorised entry or movement and communicates them to a local or remote recipient. The Fire Protection Handbook places electronic detection within a wider assessment of premises security. Physical barriers, detection, communication and response address different parts of the protection objective.[1]
An installation can share premises or interfaces with a fire alarm system and transmit to a supervising station. That relationship requires clear separation of signal meanings and response procedures. Detection supporting protection against arson or records protection remains distinct from detecting smoke or flame.[2][3]
Video smoke detection and ordinary security video also have different functions. A camera view used for security does not automatically provide a smoke-detection capability. Each claimed function depends on the selected sensing, processing and response arrangement.[4][5]
Function and operating distinctions
The handbook begins security design with an assessment of assets, threats and vulnerabilities. The required extent of protection depends on what could be harmed and how unauthorised access might occur. A perimeter-only arrangement and a system also monitoring internal movement therefore address different scenarios. The device list follows the assessment rather than replacing it.[6]
Electronic inputs can include contacts, motion detection, sound detection and other methods. Their effectiveness depends on the protected opening or space and on expected environmental disturbances. Exterior detection has to distinguish relevant intrusions from normal site conditions. Interior arrangements must account for the coverage actually provided by their sensing method.[7]
Transmission is a separate dependency. The handbook compares methods that reveal a lost communication path with arrangements that may not immediately report its loss. A backup path changes the available communication only if its operation and failure dependencies are understood. Receiving-station procedures also determine what follows a security message.[8]
Access control can conflict with emergency movement if locking functions are considered independently of fire safety. The handbook discusses door-release arrangements that coordinate security equipment with the fire alarm installation. Integrated testing has to verify the intended behaviour during normal operation, a fire condition and relevant power failures. A functioning intrusion alarm does not establish a functioning escape arrangement.[3]
Devices, control and notification
The SFPE Handbook describes detection, processing and signalling as separate elements of an alarm system. Detection supplies information about a possible fire. Processing interprets that information and determines the response. Signalling then warns occupants, sends information elsewhere or initiates another protective action. Keeping these functions distinct makes it possible to identify what a component actually contributes to the overall system.[9]
The Fire Protection Handbook adds the physical components needed to implement those functions. These include a control unit, primary and secondary power, input circuits and output circuits. Inputs can originate from automatic detectors, manual alarm devices or sprinkler waterflow equipment. Outputs can operate sounders, visible appliances and interfaces to other building systems. An off-premises connection adds a further communication path and a receiving organisation.[10]
A local indication and a transmitted message are different results. A system can notify people inside a building without automatically informing an external receiving station. Likewise, receipt of a signal at another location does not itself describe the action that the receiver will take. The system specification therefore includes both the transmission arrangement and the associated response responsibilities.[11]
The control unit also provides information for people investigating an incident. Annunciation means displaying the origin or condition of a signal in a usable form. Useful location information must correspond to the building and the response organisation's needs. A display containing many individual addresses can still be difficult to interpret if its descriptions are unclear. The handbook consequently treats the human interface as part of system design, alongside the electrical equipment.[12]
Alarm, supervisory and trouble conditions
The Fire Protection Handbook distinguishes three signal categories. An alarm signal indicates a fire condition requiring an immediate response. A supervisory signal concerns the condition of another protection system being monitored. A trouble signal identifies a fault in the alarm system, its monitored circuits or its power supplies. These distinctions describe the meaning of the information, rather than the loudness of an indicator.[13]
Sprinkler equipment provides a useful comparison. Waterflow associated with operation of the sprinkler installation can initiate a fire alarm. Movement of a monitored control valve away from its normal position can initiate a supervisory signal. A broken electrical connection to an input device can instead create a trouble condition. The same area of a building can therefore generate several signals that demand different investigations.[14]
Supervision can include both an off-normal condition and its restoration. The off-normal message identifies a condition needing attention. Restoration records that the monitored condition has returned to its normal state. Neither message, considered alone, demonstrates the performance of every part of the protected installation. The indicated condition has to be understood in relation to the particular switch, sensor or interface producing it.[13][15]
Correct signal differentiation depends on the circuit and the control logic working together. The handbook illustrates arrangements in which combining contacts incorrectly makes a closed valve indistinguishable from broken wiring. Addressable arrangements can share a communication circuit while retaining distinct device identities and signal categories. The relevant question is therefore whether the system preserves the required information under normal and fault conditions. Merely obtaining an electrical response is not sufficient evidence of correct classification.[16]
Communication paths and fault behaviour
An initiating device circuit connects conventional input devices to the control unit. A notification appliance circuit carries the output needed by the connected warning appliances. A signalling line circuit supports data communication, including communication with individually identified devices. These names describe circuit functions; they do not by themselves establish how the circuit behaves after damage.[17]
In the conventional arrangement described by the handbook, a small current passes through an end-of-line device. This allows the control unit to distinguish an intact circuit from an open connection. Operation of an input contact changes the electrical condition so that the panel can recognise the intended signal. An intact electrical path is nevertheless only one condition of successful protection. It does not demonstrate that smoke can enter a detector or that a mechanical device can move.[17][18]
The handbook's Class A and Class B descriptions concern operation in the presence of specified circuit faults. In its Class B example, equipment beyond an open circuit becomes unavailable. The Class A arrangement returns wiring to a suitably configured control unit, allowing operation on either side of a single open circuit. The classification consequently depends on equipment behaviour as well as the visible cable route. A loop-shaped drawing alone is not evidence of the claimed fault performance.[12]
Addressable devices can be polled to confirm that they still communicate. Some arrangements also use isolators to restrict the consequences of a short circuit. These features can improve the information available about a fault, but they do not remove all common dependencies. Power, control equipment and configuration remain part of the path between an input and its required output. Testing therefore examines the complete response as well as individual communication links.[17][19][20]
Interfaces with other protective systems
An alarm system can initiate actions beyond occupant warning. The handbook describes interfaces for door release, ventilation, smoke control, lifts and extinguishing systems. Each interface translates an input condition into a specified building response. The engineering question is whether that response supports the protection strategy for the actual location and fire scenario.[21][22]
An interface is more than a connection between two terminals. The connected equipment must be compatible, the communication path must have the intended fault behaviour, and the operating sequence must be defined. A command to start a fan, for example, does not prove that the associated damper has reached its required position. The handbook illustrates feedback arrangements that return information about controlled equipment to the alarm system.[23]
Door controls illustrate the relationship between normal operation and the fire condition. An electrically held-open door can be arranged to release when its holding power is removed. Access-control equipment also has to be coordinated with the intended means of escape. Security objectives and emergency movement can conflict if their control functions are considered separately. The result depends on the particular door, power arrangement and control sequence.[24]
Interconnected systems need tests that follow the intended sequence across the interface. Testing a detector and testing a fan separately do not establish that the detector will initiate the correct fan response. Temporary bypasses used during tests also change the protection available. Documentation must therefore distinguish functions actually demonstrated from functions isolated during the test, and record their restoration. These observations support assessment of the integrated installation rather than only its individual products.[25][26]
Protection objectives and response time
A detection and alarm design begins with the outcome that the protection is intended to achieve. Life safety, property protection and continuity of a building's activities can require different responses to the same fire. A warning intended to support evacuation has to arrive while useful escape time remains. Protection of sensitive equipment may instead demand detection before a small fire produces unacceptable contamination. These objectives influence the devices, processing and response arrangements chosen for the installation.[27]
The response is a sequence rather than a single event. Products of combustion must reach an appropriate sensor, the system must recognise its input, and the intended action must follow. A person receiving a warning may then need time to interpret it and begin moving. For an automatic protective function, the corresponding delay includes operation of the connected equipment. Treating detector operation as the end of the process therefore omits part of the protection mechanism.[27][28]
The SFPE design approach separates delays associated with transport from delays associated with processing and subsequent response. Transport depends on the fire, distance and enclosure geometry. Processing delays depend on the selected system and its configuration. This distinction helps identify whether an improvement requires a different sensor location, different processing or a different response arrangement.[27]
A single favourable fire scenario does not establish performance for every possible fire. Different fuels, locations and growth histories can change which signature reaches the system first. Assessment therefore compares plausible scenarios and the consequences of delayed or unsuccessful operation. The resulting performance claim belongs to the complete arrangement and its stated assumptions, rather than to an isolated component.[27]
Inspection, testing and continuing performance
Inspection, testing and maintenance answer different questions about the installation. Inspection can reveal damage, obstruction, unsuitable surroundings or changes in the protected space. Functional testing demonstrates an intended response under a stated test condition. Maintenance addresses defects and deterioration so that the installation can continue to perform its specified functions. The handbook treats these activities as part of the original protection design.[29]
Acceptance testing checks the installed arrangement against its intended sequence of operation. Changes to hardware, wiring or software can require reacceptance testing because they can affect previously demonstrated functions. The scope of the assessment depends on the change and its consequences. Records make the original arrangement, subsequent changes and observed performance available for later comparison.[26]
Electrical supervision cannot identify every physical impairment. A communicating smoke detector may have an obstructed smoke-entry path, and an interface may remain electrically normal while its mechanical connection is ineffective. The handbook specifically identifies painting, covering and changed airflows as reasons for examining detectors physically. Test planning therefore includes the real stimulus and the downstream response wherever those are necessary to demonstrate the required function.[18][26]
The Australian part of the International Fire Engineering Guidelines, published in 2005, connects commissioning with management and maintenance throughout building use. It also identifies alterations as a possible challenge to the original engineering assumptions. A changed layout or operating procedure can invalidate an earlier assessment without causing an electrical fault. Continuing performance consequently involves reviewing both equipment condition and the circumstances in which the equipment is expected to work.[30]
Warning, recognition and movement
A warning reaches its life-safety objective through the response of the people who receive it. Hearing a sound or seeing a light is only the first part of that process. People must recognise its significance, interpret the situation and decide what action to take. Movement towards safety follows those earlier stages rather than occurring automatically at the instant of detection.[28]
Van Rossum distinguishes awareness, decision-making and the actions preceding purposeful movement. Behaviour depends on perceived danger, previous experience, training, roles and the conduct of other people. The same audible signal can therefore produce different responses in different occupancies. A calculation that assigns no time to interpretation removes a part of the evacuation process described in the source.[31]
Information content also matters. A simple alarm pattern identifies an emergency condition but carries little detail about its location or the required response. A voice message can convey additional instructions, provided that the message is understandable. The Fire Protection Handbook consequently treats audibility and intelligibility as separate performance questions. Greater sound output alone does not establish that a listener understands spoken instructions.[32]
The intended audience influences the notification arrangement. Public-mode notification addresses occupants generally, while private-mode arrangements address trained people responsible for emergency actions. The handbook uses hospitals and prisons as examples where staff may mediate the response. Such arrangements depend on the defined management and assistance strategy. They cannot be evaluated solely by checking whether a warning appliance operates electrically.[33][34]
See also
Notes
- ↑ Cote et al. (2008), chapter 14.10, pp. 14-119–14-120, 14-126–14-127.
- ↑ Cote et al. (2008), chapter 14.10, pp. 14-119–14-120, 14-126.
- ↑ 3.0 3.1 Cote et al. (2008), chapter 14.4, pp. 14-47–14-50.
- ↑ Cote et al. (2008), chapter 14.2, pp. 14-22–14-23.
- ↑ Cote et al. (2008), chapter 14.10, pp. 14-119, 14-126.
- ↑ Cote et al. (2008), chapter 14.10, pp. 14-120, 14-126–14-127.
- ↑ Cote et al. (2008), chapter 14.10, pp. 14-126–14-127.
- ↑ Cote et al. (2008), chapter 14.10, p. 14-126.
- ↑ Schifiliti et al. (2002), p. 4-3.
- ↑ Cote et al. (2008), chapter 14.1, pp. 14-5–14-7.
- ↑ Cote et al. (2008), chapter 14.1, pp. 14-7–14-12.
- ↑ 12.0 12.1 Cote et al. (2008), chapter 14.1, pp. 14-6–14-7.
- ↑ 13.0 13.1 Cote et al. (2008), chapter 14.1, p. 14-5.
- ↑ Cote et al. (2008), chapter 14.4, pp. 14-39–14-45.
- ↑ Cote et al. (2008), chapter 14.4, pp. 14-43–14-45.
- ↑ Cote et al. (2008), chapter 14.4, p. 14-45.
- ↑ 17.0 17.1 17.2 Cote et al. (2008), chapter 14.1, p. 14-6.
- ↑ 18.0 18.1 Cote et al. (2008), chapter 14.2, p. 14-28.
- ↑ Cote et al. (2008), chapter 14.2, p. 14-20.
- ↑ Cote et al. (2008), chapter 14.5, p. 14-62.
- ↑ Cote et al. (2008), chapter 14.1, p. 14-7.
- ↑ Cote et al. (2008), chapter 14.4, pp. 14-45–14-50.
- ↑ Cote et al. (2008), chapter 14.4, pp. 14-47–14-49.
- ↑ Cote et al. (2008), chapter 14.4, pp. 14-46–14-47.
- ↑ Cote et al. (2008), chapter 14.4, p. 14-50.
- ↑ 26.0 26.1 26.2 Cote et al. (2008), chapter 14.5, pp. 14-61–14-62.
- ↑ 27.0 27.1 27.2 27.3 Schifiliti et al. (2002), pp. 4-2–4-3.
- ↑ 28.0 28.1 Van Rossum (2027), §7.2–7.3.
- ↑ Cote et al. (2008), chapter 14.5, pp. 14-53–14-54, 14-61–14-62.
- ↑ National Research Council of Canada et al. (2005), §0.3.2.4–0.3.2.8; pp. 0.3-6–0.3-7.
- ↑ Van Rossum (2027), §7.3.
- ↑ Cote et al. (2008), chapter 14.3, pp. 14-29–14-32.
- ↑ Cote et al. (2008), chapter 14.3, pp. 14-29–14-30.
- ↑ National Research Council of Canada et al. (2005), §0.3.2.6; p. 0.3-6.
References
- Cote, A. E., Grant, C. C., Hall, J. R., Jr., & Solomon, R. E. (Eds.). (2008). Fire Protection Handbook (20th ed.). National Fire Protection Association.
- National Research Council of Canada, International Code Council, Department of Building and Housing, & Australian Building Codes Board. (2005). International Fire Engineering Guidelines (2005 ed.). Australian Building Codes Board.
- Schifiliti, R. P., Meacham, B. J., & Custer, R. L. P. (2002). Design of detection systems. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall, Jr., & J. M. Watts, Jr. (Eds.), SFPE Handbook of Fire Protection Engineering (3rd ed., chapter 4-1, pp. 4-1–4-43). National Fire Protection Association.
- Van Rossum, E. (2027). Introduction to Fire Safety Engineering. Fire Safety Academy.