'''Net positive suction head''' is the absolute suction head available above the water's vapour-pressure head at the pump reference. <ref name="T_4-68">Titus (2002), ch. 4-2, pp. 4-68.</ref><ref name="H_15_6_15-91">Cote (2008), ch. 15.6, pp. 15-91.</ref> The abbreviation NPSH distinguishes available head supplied by the installation from required head specified for a pump. Water level, intake losses, temperature and atmospheric pressure influence the available quantity. Pump geometry, flow and speed influence the required quantity. Their comparison determines whether the suction condition is suitable. <ref name="T_4-68_4-69">Titus (2002), ch. 4-2, pp. 4-68–4-69.</ref><ref name="H_15_6_15-91_15-92">Cote (2008), ch. 15.6, pp. 15-91–15-92.</ref>
'''Net positive suction head''' is the absolute suction head available above the water's vapour-pressure head at the pump reference. <ref name="T_4-68">Titus (2002), ch. 4-2, p. 4-68.</ref><ref name="H_15_6_15-91">Cote (2008), ch. 15.6, p. 15-91.</ref> The abbreviation NPSH distinguishes available head supplied by the installation from required head specified for a pump. Water level, intake losses, temperature and atmospheric pressure influence the available quantity. Pump geometry, flow and speed influence the required quantity. Their comparison determines whether the suction condition is suitable. <ref name="T_4-68_4-69">Titus (2002), ch. 4-2, pp. 4-68–4-69.</ref><ref name="H_15_6_15-91_15-92">Cote (2008), ch. 15.6, pp. 15-91–15-92.</ref>


The engineering assessment combines the source, pump, driver, controls and delivery route. Static pressure is only one observation within that chain. Flowing performance, maximum pressure and the capacity to continue for the required duration answer different questions. Records of the installed arrangement and suitable tests connect the calculated duty to the equipment that must operate during a fire. <ref name="H_15_6_15-89_15-99">Cote (2008), ch. 15.6, pp. 15-89–15-99.</ref><ref name="H_16_11_16-220">Cote (2008), ch. 16.11, pp. 16-220.</ref> Starting tests and flowing tests exercise different functions. <ref name="H_16_11_16-220" />
The engineering assessment combines the source, pump, driver, controls and delivery route. Static pressure is only one observation within that chain. Flowing performance, maximum pressure and the capacity to continue for the required duration answer different questions. Records of the installed arrangement and suitable tests connect the calculated duty to the equipment that must operate during a fire. <ref name="H_15_6_15-89_15-99">Cote (2008), ch. 15.6, pp. 15-89–15-99.</ref><ref name="H_16_11_16-220">Cote (2008), ch. 16.11, p. 16-220.</ref> Starting tests and flowing tests exercise different functions. <ref name="H_16_11_16-220" />


== Available and required suction head ==
== Available and required suction head ==
Line 45: Line 45:
A centrifugal pump normally develops its greatest head near shutoff and less head at higher flows; the closed-outlet condition therefore needs assessment for maximum system pressure. At the other end of the operating range, the remaining head must meet the required discharge pressure after losses. Driver capability and suction conditions can constrain operation even where the plotted head appears adequate. <ref name="H_15_6_15-91_15-98">Cote (2008), ch. 15.6, pp. 15-91–15-98.</ref><ref name="T_4-68_4-69" />
A centrifugal pump normally develops its greatest head near shutoff and less head at higher flows; the closed-outlet condition therefore needs assessment for maximum system pressure. At the other end of the operating range, the remaining head must meet the required discharge pressure after losses. Driver capability and suction conditions can constrain operation even where the plotted head appears adequate. <ref name="H_15_6_15-91_15-98">Cote (2008), ch. 15.6, pp. 15-91–15-98.</ref><ref name="T_4-68_4-69" />


The handbook's account of United States NFPA 20 practice describes a rated point, a high-flow point and a shutoff limit. It reports at least 65% of rated head at 150% of rated flow, with shutoff head no greater than 140%. These are historical criteria reported in the 2008 handbook. They are not a substitute for a selected pump's actual curve or a statement of a current adopted standard. <ref name="H_15_6_15-92">Cote (2008), ch. 15.6, pp. 15-92.</ref>
The handbook's account of United States NFPA 20 practice describes a rated point, a high-flow point and a shutoff limit. It reports at least 65% of rated head at 150% of rated flow, with shutoff head no greater than 140%. These are historical criteria reported in the 2008 handbook. They are not a substitute for a selected pump's actual curve or a statement of a current adopted standard. <ref name="H_15_6_15-92">Cote (2008), ch. 15.6, p. 15-92.</ref>


Connecting pumps in series adds their heads at a common flow; connecting them in parallel combines flow at a common head. Neither arrangement automatically doubles delivery through the installed network, because the operating intersection changes. Shared suction piping and power dependencies also remain part of the installation rather than disappearing through duplication. <ref name="T_4-70">Titus (2002), ch. 4-2, pp. 4-70.</ref><ref name="H_15_6_15-93_15-95">Cote (2008), ch. 15.6, pp. 15-93–15-95.</ref>
Connecting pumps in series adds their heads at a common flow; connecting them in parallel combines flow at a common head. Neither arrangement automatically doubles delivery through the installed network, because the operating intersection changes. Shared suction piping and power dependencies also remain part of the installation rather than disappearing through duplication. <ref name="T_4-70">Titus (2002), ch. 4-2, p. 4-70.</ref><ref name="H_15_6_15-93_15-95">Cote (2008), ch. 15.6, pp. 15-93–15-95.</ref>


The water source must be assessed alongside the pump; a booster can overcome insufficient pressure but cannot create an absent water reserve. A powerful driver cannot correct an obstructed intake or inadequate suction conditions. Selection therefore brings together the source, suction route, performance curve, driver, controls and downstream demand. <ref name="H_15_6_15-91_15-99">Cote (2008), ch. 15.6, pp. 15-91–15-99.</ref><ref name="T_4-68_4-69" />
The water source must be assessed alongside the pump; a booster can overcome insufficient pressure but cannot create an absent water reserve. A powerful driver cannot correct an obstructed intake or inadequate suction conditions. Selection therefore brings together the source, suction route, performance curve, driver, controls and downstream demand. <ref name="H_15_6_15-91_15-99">Cote (2008), ch. 15.6, pp. 15-91–15-99.</ref><ref name="T_4-68_4-69" />
Line 85: Line 85:
At fixed diameter and roughness coefficient, Hazen-Williams loss increases approximately with flow raised to the power 1.85; doubling flow therefore produces considerably more than twice the loss. Increasing bore has a strong opposite effect because diameter appears with an exponent of 4.87. This explains why a short restricted connection can materially influence an otherwise generous water supply. <ref name="T_4-52_4-53">Titus (2002), ch. 4-2, pp. 4-52–4-53.</ref><ref name="F_4-75_4-81" />
At fixed diameter and roughness coefficient, Hazen-Williams loss increases approximately with flow raised to the power 1.85; doubling flow therefore produces considerably more than twice the loss. Increasing bore has a strong opposite effect because diameter appears with an exponent of 4.87. This explains why a short restricted connection can materially influence an otherwise generous water supply. <ref name="T_4-52_4-53">Titus (2002), ch. 4-2, pp. 4-52–4-53.</ref><ref name="F_4-75_4-81" />


Fittings can be represented by local resistance coefficients or by equivalent pipe lengths where the selected method permits; equivalent length is a calculation device, not an extra measured length on the drawing. Its use must remain consistent with the pipe and friction assumptions behind the published value. A special valve's measured pressure-loss curve may provide a better representation than a generic fitting allowance. <ref name="T_4-56">Titus (2002), ch. 4-2, pp. 4-56.</ref><ref name="H_15_3_15-59">Cote (2008), ch. 15.3, pp. 15-59.</ref>
Fittings can be represented by local resistance coefficients or by equivalent pipe lengths where the selected method permits; equivalent length is a calculation device, not an extra measured length on the drawing. Its use must remain consistent with the pipe and friction assumptions behind the published value. A special valve's measured pressure-loss curve may provide a better representation than a generic fitting allowance. <ref name="T_4-56">Titus (2002), ch. 4-2, p. 4-56.</ref><ref name="H_15_3_15-59">Cote (2008), ch. 15.3, p. 15-59.</ref>


Age and deposits introduce further uncertainty; corrosion can increase roughness, reduce the effective bore and release material that later obstructs a smaller passage. These mechanisms are distinct, so changing a roughness coefficient does not necessarily represent a local blockage. Inspection findings and flow measurements help determine whether the calculation still describes the installation. <ref name="H_15_5_15-79_15-81">Cote (2008), ch. 15.5, pp. 15-79–15-81.</ref><ref name="H_16_11_16-212">Cote (2008), ch. 16.11, pp. 16-212.</ref>
Age and deposits introduce further uncertainty; corrosion can increase roughness, reduce the effective bore and release material that later obstructs a smaller passage. These mechanisms are distinct, so changing a roughness coefficient does not necessarily represent a local blockage. Inspection findings and flow measurements help determine whether the calculation still describes the installation. <ref name="H_15_5_15-79_15-81">Cote (2008), ch. 15.5, pp. 15-79–15-81.</ref><ref name="H_16_11_16-212">Cote (2008), ch. 16.11, p. 16-212.</ref>


A sound comparison keeps elevation, flow and valve state consistent between observations; a high static pressure can coexist with poor flowing performance because frictional loss emerges when water moves. Conversely, a pressure difference caused by elevation does not establish pipe deterioration. The interpretation depends on the physical route and the condition under which each reading was taken. <ref name="T_4-47_4-52" /><ref name="F_4-81">Fleming (2002), ch. 4-3, pp. 4-81.</ref>
A sound comparison keeps elevation, flow and valve state consistent between observations; a high static pressure can coexist with poor flowing performance because frictional loss emerges when water moves. Conversely, a pressure difference caused by elevation does not establish pipe deterioration. The interpretation depends on the physical route and the condition under which each reading was taken. <ref name="T_4-47_4-52" /><ref name="F_4-81">Fleming (2002), ch. 4-3, p. 4-81.</ref>


== Measuring the available supply ==
== Measuring the available supply ==

Latest revision as of 01:32, 16 November 2026

Net positive suction head is the absolute suction head available above the water's vapour-pressure head at the pump reference. [1][2] The abbreviation NPSH distinguishes available head supplied by the installation from required head specified for a pump. Water level, intake losses, temperature and atmospheric pressure influence the available quantity. Pump geometry, flow and speed influence the required quantity. Their comparison determines whether the suction condition is suitable. [3][4]

The engineering assessment combines the source, pump, driver, controls and delivery route. Static pressure is only one observation within that chain. Flowing performance, maximum pressure and the capacity to continue for the required duration answer different questions. Records of the installed arrangement and suitable tests connect the calculated duty to the equipment that must operate during a fire. [5][6] Starting tests and flowing tests exercise different functions. [6]

Available and required suction head

A fire pump performance curve cannot be interpreted independently of suction conditions; the fire pump may receive positive pressure from a main or draw from a fire water storage tank. In either case, the fire water supply must preserve adequate suction energy while the required flow moves. A large reserve does not automatically produce adequate pressure at the impeller inlet. [7]

Net positive suction head: functional relationships. Measurement and water paths are distinct.
Net positive suction head: functional relationships. Schematic explanation; dimensions are not installation instructions.

Drafting makes the available-head limit particularly visible because water may start below the pump; lift consumes part of the atmospheric-pressure head, while friction loss consumes more as flow passes through the intake. These effects occur before the pump adds useful downstream energy. A universal suction-lift value would conceal changes in water temperature, elevation, pipework and operating flow. [3][8]

For unchanged flow and suction losses, lowering an open reservoir's surface by 1 m reduces available NPSH by 1 m; this follows directly from the elevation term in the energy balance. It is an illustrative change, not a manufacturer-required margin. The actual comparison uses the lowest relevant source level and the selected pump's required-head curve. [1]

Suction conditions and cavitation

Water approaching an impeller must retain enough absolute pressure to avoid excessive vapour formation; pressure falls as flow accelerates through the inlet region. If local pressure reaches the water's vapour pressure, bubbles can form and subsequently collapse in higher-pressure regions. This cavitation can produce noise, vibration, loss of performance and material damage. [2][1]

Available suction head. Measurement and water paths are distinct.
Available suction head. Schematic explanation; dimensions are not installation instructions.

Available net positive suction head describes the installation's suction energy above vapour-pressure head; required net positive suction head describes a pump characteristic supplied by the manufacturer for stated operating conditions. The two quantities must be compared at the relevant flow and speed. They are not two alternative names for a suction gauge reading. [4][1]

For a large open reservoir, the following form separates atmospheric pressure, water level and suction losses; the reservoir surface velocity is treated as negligible. A positive elevation difference means that the water surface is above the pump reference. A lower surface contributes a negative term. [1]

NPSHa=pa−pvρg+zs−zp−hs

Symbol Description Unit
NPSHa Available net positive suction head m
pa,pv Absolute atmospheric and vapour pressures Pa
ρ,g Water density and gravitational acceleration kg/m³; m/s²
zs,zp,hs Surface elevation, pump elevation and suction loss m

The lowest usable tank level can be more demanding than the initial full condition; a greater flow increases suction-pipe loss and can also increase the pump's required suction head. Warmer water increases vapour pressure, while atmospheric pressure varies with elevation. These effects explain why a universal maximum suction lift cannot represent every installation. [9][1]

The handbook illustrates a pump requiring approximately 3.05 m of suction head at 7,570 L/min and 5.49 m at 11,400 L/min. These are converted values from one illustrative manufacturer's-style curve, not general acceptance limits. Their significance is the changing requirement as flow rises. The appropriate comparison uses the actual pump data and the available head under the corresponding supply condition. [2]

Pump operation and selection

A centrifugal pump transfers shaft energy to water through a rotating impeller; its performance varies with flow, speed and pump geometry. The selected duty belongs on a curve showing this relationship, rather than being defined by a single pressure reading. The complete operating point also depends on the resistance and supply conditions of the connected installation. [10][11]

Pump and installed system. Measurement and water paths are distinct.
Pump and installed system. Schematic explanation; dimensions are not installation instructions.

The pump head is the energy added across the pump; discharge pressure alone is not that quantity when suction pressure, elevation or velocity differ between measuring points. Horizontal pumps and vertical turbine arrangements require appropriate references for their respective configurations. A test comparison can be misleading if the water level or suction reference has changed without being recorded. [12]

A centrifugal pump normally develops its greatest head near shutoff and less head at higher flows; the closed-outlet condition therefore needs assessment for maximum system pressure. At the other end of the operating range, the remaining head must meet the required discharge pressure after losses. Driver capability and suction conditions can constrain operation even where the plotted head appears adequate. [13][3]

The handbook's account of United States NFPA 20 practice describes a rated point, a high-flow point and a shutoff limit. It reports at least 65% of rated head at 150% of rated flow, with shutoff head no greater than 140%. These are historical criteria reported in the 2008 handbook. They are not a substitute for a selected pump's actual curve or a statement of a current adopted standard. [14]

Connecting pumps in series adds their heads at a common flow; connecting them in parallel combines flow at a common head. Neither arrangement automatically doubles delivery through the installed network, because the operating intersection changes. Shared suction piping and power dependencies also remain part of the installation rather than disappearing through duplication. [15][16]

The water source must be assessed alongside the pump; a booster can overcome insufficient pressure but cannot create an absent water reserve. A powerful driver cannot correct an obstructed intake or inadequate suction conditions. Selection therefore brings together the source, suction route, performance curve, driver, controls and downstream demand. [17][3]

Pressure, flow and energy

Water pressure describes only one part of the energy available in a pipe; elevation contributes potential energy, while movement contributes velocity head. Titus describes these quantities using head, expressed as an equivalent height of water. A hydraulic calculation must therefore compare locations through a common energy balance, rather than subtracting unrelated gauge readings. [18]

For steady, incompressible flow, the energy balance adds pump head and subtracts irreversible losses between two sections; the following form assumes that section-average velocity adequately represents kinetic energy. It describes a defined flow path, with all elevations measured from the same datum. Sudden changes require a different, transient analysis. [19]

p1ρg+v122g+z1+Hp=p2ρg+v222g+z2+hL

Symbol Description Unit
p Pressure at the section Pa
ρ Water density kg/m³
g Gravitational acceleration m/s²
v Mean velocity m/s
z,Hp,hL Elevation, added pump head and head loss m

Pressure can decrease because water rises, because velocity increases, or because energy is dissipated; these effects have different physical meanings. An elevation change can be recovered on a descending route, whereas friction dissipates mechanical energy. A larger pipe can reduce friction but cannot remove the elevation difference between the source and the outlet. [20]

Continuity provides the corresponding flow constraint: volume flow equals cross-sectional area multiplied by mean velocity; the same flow moves faster through a smaller internal bore. At a junction, incoming and outgoing flows balance, while losses depend on the flow assigned to each connected segment. Nominal pipe size alone does not supply the internal diameter needed for this calculation. [19][21]

The pressure at a sprinkler is the pressure remaining after the complete upstream route has been considered; it is not the pressure indicated beside a remote pump or street hydrant. The route includes connecting mains, valves, elevation and distribution piping. Leaving out an inconvenient section creates an apparently favourable calculation without providing the corresponding water at the outlet. [22][23]

Pipe resistance and internal condition

Moving water loses mechanical energy through interaction with pipe walls and through changes in direction or section; turbulent mixing contributes to this dissipation. The resistance depends on the actual internal bore and its condition, not simply the name printed on the pipe. Valves, elbows, entries and other fittings introduce additional local losses. [24]

The Darcy-Weisbach equation expresses distributed loss through a dimensionless friction factor; that factor depends on the flow regime and, for turbulent flow, on relative roughness. The Hazen-Williams formula instead uses an empirical coefficient for water service. These methods describe related hydraulic behaviour, but their coefficients do not have interchangeable meanings. [25]

At fixed diameter and roughness coefficient, Hazen-Williams loss increases approximately with flow raised to the power 1.85; doubling flow therefore produces considerably more than twice the loss. Increasing bore has a strong opposite effect because diameter appears with an exponent of 4.87. This explains why a short restricted connection can materially influence an otherwise generous water supply. [26][22]

Fittings can be represented by local resistance coefficients or by equivalent pipe lengths where the selected method permits; equivalent length is a calculation device, not an extra measured length on the drawing. Its use must remain consistent with the pipe and friction assumptions behind the published value. A special valve's measured pressure-loss curve may provide a better representation than a generic fitting allowance. [27][28]

Age and deposits introduce further uncertainty; corrosion can increase roughness, reduce the effective bore and release material that later obstructs a smaller passage. These mechanisms are distinct, so changing a roughness coefficient does not necessarily represent a local blockage. Inspection findings and flow measurements help determine whether the calculation still describes the installation. [29][30]

A sound comparison keeps elevation, flow and valve state consistent between observations; a high static pressure can coexist with poor flowing performance because frictional loss emerges when water moves. Conversely, a pressure difference caused by elevation does not establish pipe deterioration. The interpretation depends on the physical route and the condition under which each reading was taken. [20][31]

Measuring the available supply

A supply test relates an observed discharge to the pressure remaining elsewhere in the connected system; the initial static reading describes the condition before the test discharge begins. The residual reading describes the pressure while the measured discharge is flowing. Both belong to the same test arrangement and must be recorded with its location and operating conditions. [31][32]

The flowing outlet and the pressure observation have different functions; a pitot measurement in an appropriate free jet supports an estimate of outlet flow. A gauge at the residual hydrant measures pressure in the distribution system during that discharge. Substituting jet pressure for residual system pressure confuses two different physical quantities. [32][31]

The discharge estimate depends on outlet geometry and the coefficient representing its losses; a disturbed or nonuniform jet makes a single point reading less representative. Probe alignment and position also influence the measurement. For some discharge devices, a calibrated nozzle or suitable flowmeter provides a more appropriate method than applying a simple pitot relation. [32]

Test results describe a network state, rather than an unlimited promise of future supply; domestic demand, pumps, source levels and closed valves can change that state. The pressure reference must also be carried correctly to the building calculation. A test performed at a different elevation or upstream of additional resistance needs hydraulic interpretation before comparison with system demand. [33][34]

A main-drain test provides a different kind of evidence; the handbook uses changes from previous static and flowing readings to identify possible deterioration or obstruction. This is useful for detecting change, but it does not independently establish the full sprinkler demand. Test opening, supply state and instrument condition affect whether successive observations are comparable. [35]

Pump testing likewise separates a start test from a flow-performance test; running successfully without substantial discharge demonstrates some operating functions but does not establish the entire pump curve. Flowing observations across the relevant operating range give evidence about delivery capability. The handbook describes retaining records so that deterioration and the ability to meet system demand can be assessed. [6]

Flow, pressure and duration

A fire water supply has several necessary characteristics: adequate flow, sufficient pressure at that flow, an appropriate duration and availability when needed; these characteristics cannot replace one another. A large reservoir may have insufficient delivery capacity, while a high-pressure connection may offer too little sustained flow. The required combination depends on the fire protection demand being assessed. [33][36]

Demand must identify which outlets operate together; sprinkler calculations assemble the flows of individual operating sprinklers and include other applicable demands under the selected design basis. Municipal fire-flow planning addresses a different question and may include wider firefighting activity. Treating every quoted fire-flow value as a sprinkler demand obscures these differences. [37][38]

The supply location also matters; a pressure measured in a street main is not automatically available at a building riser. Connecting pipework, backflow assemblies and changes in elevation affect the transfer. The assessment follows the supply through these elements to the same reference point used for the calculated demand. [39][34]

Storage introduces a time dimension that a pressure-flow curve alone does not show; usable water is the quantity that the outlet or pump can actually draw while meeting its operating conditions. Water below the effective intake, or reserved for another purpose, cannot simply be counted as fire reserve. Replenishment contributes only through an identified source and a delivery arrangement that remains available. [40][41]

A constant-flow volume calculation multiplies flow by duration. In the following form, flow is in litres per minute and usable volume is in cubic metres. The factor converts litres to cubic metres. [41]

Vu=Qt1000

Symbol Description Unit
Vu Usable water volume m³
Q,t Constant discharge and duration L/min; min

A worked example separates usable water from gross capacity. Using Fleming's example of 530 L/min for 30 minutes gives 15,900 L, or 15.9 m³, of usable water. This arithmetic does not select a design duration or establish the gross tank volume. The example is a historical worked calculation, with tank configuration and unavailable volume assessed separately. [41]

Public supplies can change with domestic use, industrial demand, maintenance and seasonal conditions; tank levels and pump operation can change during a fire as well. The design record therefore needs the conditions represented by the available supply, including relevant adverse conditions. A favourable isolated reading does not establish availability throughout the required incident duration. [33][42]

See also

Notes

  1. ↑ 1.0 1.1 1.2 1.3 1.4 1.5 Titus (2002), ch. 4-2, p. 4-68.
  2. ↑ 2.0 2.1 2.2 Cote (2008), ch. 15.6, p. 15-91.
  3. ↑ 3.0 3.1 3.2 3.3 Titus (2002), ch. 4-2, pp. 4-68–4-69.
  4. ↑ 4.0 4.1 Cote (2008), ch. 15.6, pp. 15-91–15-92.
  5. ↑ Cote (2008), ch. 15.6, pp. 15-89–15-99.
  6. ↑ 6.0 6.1 6.2 Cote (2008), ch. 16.11, p. 16-220.
  7. ↑ Cote (2008), ch. 15.6, pp. 15-89–15-95.
  8. ↑ Cote (2008), ch. 13.4, pp. 13-43–13-45.
  9. ↑ Cote (2008), ch. 15.6, pp. 15-91–15-95.
  10. ↑ Cote (2008), ch. 15.6, pp. 15-85,15-89–15-92.
  11. ↑ Titus (2002), ch. 4-2, pp. 4-67–4-69.
  12. ↑ Cote (2008), ch. 15.6, pp. 15-89–15-90.
  13. ↑ Cote (2008), ch. 15.6, pp. 15-91–15-98.
  14. ↑ Cote (2008), ch. 15.6, p. 15-92.
  15. ↑ Titus (2002), ch. 4-2, p. 4-70.
  16. ↑ Cote (2008), ch. 15.6, pp. 15-93–15-95.
  17. ↑ Cote (2008), ch. 15.6, pp. 15-91–15-99.
  18. ↑ Titus (2002), ch. 4-2, pp. 4-45–4-48.
  19. ↑ 19.0 19.1 Titus (2002), ch. 4-2, pp. 4-47–4-50.
  20. ↑ 20.0 20.1 Titus (2002), ch. 4-2, pp. 4-47–4-52.
  21. ↑ Cote (2008), ch. 16.3, pp. 16-41–16-42.
  22. ↑ 22.0 22.1 Fleming (2002), ch. 4-3, pp. 4-75–4-81.
  23. ↑ Hopkins et al. (2005), pp. xxxvii–xxxviii.
  24. ↑ Titus (2002), ch. 4-2, pp. 4-49–4-56.
  25. ↑ Titus (2002), ch. 4-2, pp. 4-50–4-53.
  26. ↑ Titus (2002), ch. 4-2, pp. 4-52–4-53.
  27. ↑ Titus (2002), ch. 4-2, p. 4-56.
  28. ↑ Cote (2008), ch. 15.3, p. 15-59.
  29. ↑ Cote (2008), ch. 15.5, pp. 15-79–15-81.
  30. ↑ Cote (2008), ch. 16.11, p. 16-212.
  31. ↑ 31.0 31.1 31.2 Fleming (2002), ch. 4-3, p. 4-81.
  32. ↑ 32.0 32.1 32.2 Cote (2008), ch. 15.3, pp. 15-46–15-47.
  33. ↑ 33.0 33.1 33.2 Cote (2008), ch. 15.2, pp. 15-23–15-24.
  34. ↑ 34.0 34.1 Fleming (2002), ch. 4-3, pp. 4-81–4-83.
  35. ↑ Cote (2008), ch. 16.11, pp. 16-210–16-211.
  36. ↑ Cote (2008), ch. 15.4, pp. 15-63–15-67.
  37. ↑ Cote (2008), ch. 15.2, pp. 15-23–15-29.
  38. ↑ Fleming (2002), ch. 4-3, pp. 4-74–4-81.
  39. ↑ Cote (2008), ch. 15.4, pp. 15-63–15-65.
  40. ↑ Cote (2008), ch. 15.1, pp. 15-3–15-5.
  41. ↑ 41.0 41.1 41.2 Fleming (2002), ch. 4-3, pp. 4-83–4-84.
  42. ↑ Cote (2008), ch. 15.4, pp. 15-63–15-64.

References

  • Cote, A. E. (Ed.). (2008). Fire protection handbook (20th ed.). National Fire Protection Association.