'''Bernoulli equation''' is the energy relation connecting pressure, velocity and elevation along a flowing-fluid path under stated assumptions. <ref name="T_4-47_4-48">Titus (2002), ch. 4-2, pp. 4-47–4-48.</ref> For real fire-water systems, the balance also includes pump work and energy losses. It explains why pressure changes do not all represent friction and why a nozzle can convert pressure into jet velocity. Steady-flow use must be distinguished from transient pressure-wave analysis. <ref name="T_4-47_4-52_4-65_4-67">Titus (2002), ch. 4-2, pp. 4-47–4-52,4-65–4-67.</ref> | '''Bernoulli equation''' is the energy relation connecting pressure, velocity and elevation along a flowing-fluid path under stated assumptions. <ref name="T_4-47_4-48">Titus (2002), ch. 4-2, pp. 4-47–4-48.</ref> For real fire-water systems, the balance also includes pump work and energy losses. It explains why pressure changes do not all represent friction and why a nozzle can convert pressure into jet velocity. Steady-flow use must be distinguished from transient pressure-wave analysis. <ref name="T_4-47_4-52_4-65_4-67">Titus (2002), ch. 4-2, pp. 4-47–4-52,4-65–4-67.</ref> | ||
The underlying hydraulic assessment follows water from a defined source to its intended outlet. Elevation, velocity changes and irreversible losses must be distinguished. Observations also need the flow and network conditions under which they were obtained. A mathematically correct result can still be misleading if a source condition, connecting segment or component loss has been omitted from the description. <ref name="T_4-47_4-56">Titus (2002), ch. 4-2, pp. 4-47–4-56.</ref><ref name="F_4-81_4-83">Fleming (2002), ch. 4-3, pp. 4-81–4-83.</ref> Static pressure and flowing pressure describe different conditions. <ref name="F_4-81">Fleming (2002), ch. 4-3, | The underlying hydraulic assessment follows water from a defined source to its intended outlet. Elevation, velocity changes and irreversible losses must be distinguished. Observations also need the flow and network conditions under which they were obtained. A mathematically correct result can still be misleading if a source condition, connecting segment or component loss has been omitted from the description. <ref name="T_4-47_4-56">Titus (2002), ch. 4-2, pp. 4-47–4-56.</ref><ref name="F_4-81_4-83">Fleming (2002), ch. 4-3, pp. 4-81–4-83.</ref> Static pressure and flowing pressure describe different conditions. <ref name="F_4-81">Fleming (2002), ch. 4-3, p. 4-81.</ref> | ||
== Conservation of mechanical energy == | == Conservation of mechanical energy == | ||
The relation underlies [[Hydraulic calculation|hydraulic calculation]] from the source to a sprinkler or a [[Fire stream|fire stream]]; a [[Pitot tube|pitot tube]] uses the conversion between velocity and stagnation pressure in a suitable jet. The sprinkler [[K-factor]] packages discharge geometry and losses into a measured flow-pressure relationship. These applications share an energy basis but require their own coefficients and boundary conditions. <ref name="T_4-47_4-48" /><ref name="H_15_3_15-40_15-46_15-47">Cote (2008), ch. 15.3, pp. 15-40,15-46–15-47.</ref><ref name="F_4-75">Fleming (2002), ch. 4-3, | The relation underlies [[Hydraulic calculation|hydraulic calculation]] from the source to a sprinkler or a [[Fire stream|fire stream]]; a [[Pitot tube|pitot tube]] uses the conversion between velocity and stagnation pressure in a suitable jet. The sprinkler [[K-factor]] packages discharge geometry and losses into a measured flow-pressure relationship. These applications share an energy basis but require their own coefficients and boundary conditions. <ref name="T_4-47_4-48" /><ref name="H_15_3_15-40_15-46_15-47">Cote (2008), ch. 15.3, pp. 15-40,15-46–15-47.</ref><ref name="F_4-75">Fleming (2002), ch. 4-3, p. 4-75.</ref> | ||
[[File:fse-bernoulli-equation-v1.svg|thumb|upright=1.5|alt=Bernoulli equation: functional relationships. Measurement and water paths are distinct.|Bernoulli equation: functional relationships. Schematic explanation; dimensions are not installation instructions.]] | [[File:fse-bernoulli-equation-v1.svg|thumb|upright=1.5|alt=Bernoulli equation: functional relationships. Measurement and water paths are distinct.|Bernoulli equation: functional relationships. Schematic explanation; dimensions are not installation instructions.]] | ||
The handbook gives an example with 4,200 L/min passing from an 80 mm bore into a 70 mm bore. Upstream flowing pressure is 300 kPa, the outlet is 5 m higher, and the stated loss is 12 m of water head. Recalculation using section-average velocities gives approximately 64.8 kPa downstream pressure. The reduction includes velocity change and elevation as well as [[Friction loss|friction loss]]. <ref name="H_15_3_15-40">Cote (2008), ch. 15.3, | The handbook gives an example with 4,200 L/min passing from an 80 mm bore into a 70 mm bore. Upstream flowing pressure is 300 kPa, the outlet is 5 m higher, and the stated loss is 12 m of water head. Recalculation using section-average velocities gives approximately 64.8 kPa downstream pressure. The reduction includes velocity change and elevation as well as [[Friction loss|friction loss]]. <ref name="H_15_3_15-40">Cote (2008), ch. 15.3, p. 15-40.</ref> | ||
[[Turbulence]] and wall shear dissipate mechanical energy, so an ideal loss-free equation is insufficient for the complete pipe route; a pump supplies additional energy, while fittings introduce further losses. The resulting balance remains useful only when the selected steady-flow assumptions fit the event. Rapid valve closure requires the separate pressure-wave treatment associated with water hammer. <ref name="T_4-49_4-56_4-65_4-67">Titus (2002), ch. 4-2, pp. 4-49–4-56,4-65–4-67.</ref> | [[Turbulence]] and wall shear dissipate mechanical energy, so an ideal loss-free equation is insufficient for the complete pipe route; a pump supplies additional energy, while fittings introduce further losses. The resulting balance remains useful only when the selected steady-flow assumptions fit the event. Rapid valve closure requires the separate pressure-wave treatment associated with water hammer. <ref name="T_4-49_4-56_4-65_4-67">Titus (2002), ch. 4-2, pp. 4-49–4-56,4-65–4-67.</ref> | ||
| Line 47: | Line 47: | ||
At fixed diameter and roughness coefficient, Hazen-Williams loss increases approximately with flow raised to the power 1.85; doubling flow therefore produces considerably more than twice the loss. Increasing bore has a strong opposite effect because diameter appears with an exponent of 4.87. This explains why a short restricted connection can materially influence an otherwise generous water supply. <ref name="T_4-52_4-53">Titus (2002), ch. 4-2, pp. 4-52–4-53.</ref><ref name="F_4-75_4-81" /> | At fixed diameter and roughness coefficient, Hazen-Williams loss increases approximately with flow raised to the power 1.85; doubling flow therefore produces considerably more than twice the loss. Increasing bore has a strong opposite effect because diameter appears with an exponent of 4.87. This explains why a short restricted connection can materially influence an otherwise generous water supply. <ref name="T_4-52_4-53">Titus (2002), ch. 4-2, pp. 4-52–4-53.</ref><ref name="F_4-75_4-81" /> | ||
Fittings can be represented by local resistance coefficients or by equivalent pipe lengths where the selected method permits; equivalent length is a calculation device, not an extra measured length on the drawing. Its use must remain consistent with the pipe and friction assumptions behind the published value. A special valve's measured pressure-loss curve may provide a better representation than a generic fitting allowance. <ref name="T_4-56">Titus (2002), ch. 4-2, | Fittings can be represented by local resistance coefficients or by equivalent pipe lengths where the selected method permits; equivalent length is a calculation device, not an extra measured length on the drawing. Its use must remain consistent with the pipe and friction assumptions behind the published value. A special valve's measured pressure-loss curve may provide a better representation than a generic fitting allowance. <ref name="T_4-56">Titus (2002), ch. 4-2, p. 4-56.</ref><ref name="H_15_3_15-59">Cote (2008), ch. 15.3, p. 15-59.</ref> | ||
Age and deposits introduce further uncertainty; corrosion can increase roughness, reduce the effective bore and release material that later obstructs a smaller passage. These mechanisms are distinct, so changing a roughness coefficient does not necessarily represent a local blockage. Inspection findings and flow measurements help determine whether the calculation still describes the installation. <ref name="H_15_5_15-79_15-81">Cote (2008), ch. 15.5, pp. 15-79–15-81.</ref><ref name="H_16_11_16-212">Cote (2008), ch. 16.11, | Age and deposits introduce further uncertainty; corrosion can increase roughness, reduce the effective bore and release material that later obstructs a smaller passage. These mechanisms are distinct, so changing a roughness coefficient does not necessarily represent a local blockage. Inspection findings and flow measurements help determine whether the calculation still describes the installation. <ref name="H_15_5_15-79_15-81">Cote (2008), ch. 15.5, pp. 15-79–15-81.</ref><ref name="H_16_11_16-212">Cote (2008), ch. 16.11, p. 16-212.</ref> | ||
A sound comparison keeps elevation, flow and valve state consistent between observations; a high static pressure can coexist with poor flowing performance because frictional loss emerges when water moves. Conversely, a pressure difference caused by elevation does not establish pipe deterioration. The interpretation depends on the physical route and the condition under which each reading was taken. <ref name="T_4-47_4-52" /><ref name="F_4-81" /> | A sound comparison keeps elevation, flow and valve state consistent between observations; a high static pressure can coexist with poor flowing performance because frictional loss emerges when water moves. Conversely, a pressure difference caused by elevation does not establish pipe deterioration. The interpretation depends on the physical route and the condition under which each reading was taken. <ref name="T_4-47_4-52" /><ref name="F_4-81" /> | ||
| Line 89: | Line 89: | ||
A main-drain test provides a different kind of evidence; the handbook uses changes from previous static and flowing readings to identify possible deterioration or obstruction. This is useful for detecting change, but it does not independently establish the full sprinkler demand. Test opening, supply state and instrument condition affect whether successive observations are comparable. <ref name="H_16_11_16-210_16-211">Cote (2008), ch. 16.11, pp. 16-210–16-211.</ref> | A main-drain test provides a different kind of evidence; the handbook uses changes from previous static and flowing readings to identify possible deterioration or obstruction. This is useful for detecting change, but it does not independently establish the full sprinkler demand. Test opening, supply state and instrument condition affect whether successive observations are comparable. <ref name="H_16_11_16-210_16-211">Cote (2008), ch. 16.11, pp. 16-210–16-211.</ref> | ||
Pump testing likewise separates a start test from a flow-performance test; running successfully without substantial discharge demonstrates some operating functions but does not establish the entire pump curve. Flowing observations across the relevant operating range give evidence about delivery capability. The handbook describes retaining records so that deterioration and the ability to meet system demand can be assessed. <ref name="H_16_11_16-220">Cote (2008), ch. 16.11, | Pump testing likewise separates a start test from a flow-performance test; running successfully without substantial discharge demonstrates some operating functions but does not establish the entire pump curve. Flowing observations across the relevant operating range give evidence about delivery capability. The handbook describes retaining records so that deterioration and the ability to meet system demand can be assessed. <ref name="H_16_11_16-220">Cote (2008), ch. 16.11, p. 16-220.</ref> | ||
== Pump operation and selection == | == Pump operation and selection == | ||
| Line 98: | Line 98: | ||
A centrifugal pump normally develops its greatest head near shutoff and less head at higher flows; the closed-outlet condition therefore needs assessment for maximum system pressure. At the other end of the operating range, the remaining head must meet the required discharge pressure after losses. Driver capability and suction conditions can constrain operation even where the plotted head appears adequate. <ref name="H_15_6_15-91_15-98">Cote (2008), ch. 15.6, pp. 15-91–15-98.</ref><ref name="T_4-68_4-69">Titus (2002), ch. 4-2, pp. 4-68–4-69.</ref> | A centrifugal pump normally develops its greatest head near shutoff and less head at higher flows; the closed-outlet condition therefore needs assessment for maximum system pressure. At the other end of the operating range, the remaining head must meet the required discharge pressure after losses. Driver capability and suction conditions can constrain operation even where the plotted head appears adequate. <ref name="H_15_6_15-91_15-98">Cote (2008), ch. 15.6, pp. 15-91–15-98.</ref><ref name="T_4-68_4-69">Titus (2002), ch. 4-2, pp. 4-68–4-69.</ref> | ||
The handbook's account of United States NFPA 20 practice describes a rated point, a high-flow point and a shutoff limit. It reports at least 65% of rated head at 150% of rated flow, with shutoff head no greater than 140%. These are historical criteria reported in the 2008 handbook. They are not a substitute for a selected pump's actual curve or a statement of a current adopted standard. <ref name="H_15_6_15-92">Cote (2008), ch. 15.6, | The handbook's account of United States NFPA 20 practice describes a rated point, a high-flow point and a shutoff limit. It reports at least 65% of rated head at 150% of rated flow, with shutoff head no greater than 140%. These are historical criteria reported in the 2008 handbook. They are not a substitute for a selected pump's actual curve or a statement of a current adopted standard. <ref name="H_15_6_15-92">Cote (2008), ch. 15.6, p. 15-92.</ref> | ||
Connecting pumps in series adds their heads at a common flow; connecting them in parallel combines flow at a common head. Neither arrangement automatically doubles delivery through the installed network, because the operating intersection changes. Shared suction piping and power dependencies also remain part of the installation rather than disappearing through duplication. <ref name="T_4-70">Titus (2002), ch. 4-2, | Connecting pumps in series adds their heads at a common flow; connecting them in parallel combines flow at a common head. Neither arrangement automatically doubles delivery through the installed network, because the operating intersection changes. Shared suction piping and power dependencies also remain part of the installation rather than disappearing through duplication. <ref name="T_4-70">Titus (2002), ch. 4-2, p. 4-70.</ref><ref name="H_15_6_15-93_15-95">Cote (2008), ch. 15.6, pp. 15-93–15-95.</ref> | ||
The water source must be assessed alongside the pump; a booster can overcome insufficient pressure but cannot create an absent water reserve. A powerful driver cannot correct an obstructed intake or inadequate suction conditions. Selection therefore brings together the source, suction route, performance curve, driver, controls and downstream demand. <ref name="H_15_6_15-91_15-99">Cote (2008), ch. 15.6, pp. 15-91–15-99.</ref><ref name="T_4-68_4-69" /> | The water source must be assessed alongside the pump; a booster can overcome insufficient pressure but cannot create an absent water reserve. A powerful driver cannot correct an obstructed intake or inadequate suction conditions. Selection therefore brings together the source, suction route, performance curve, driver, controls and downstream demand. <ref name="H_15_6_15-91_15-99">Cote (2008), ch. 15.6, pp. 15-91–15-99.</ref><ref name="T_4-68_4-69" /> | ||
| Line 121: | Line 121: | ||
|} | |} | ||
The round-trip time compares the duration of a flow change with the time taken for a wave to travel and return. It explains why the same valve movement can behave differently in different pipe systems. The simple rapid-change estimate is not a prediction of every later pressure peak. Reflections and interacting waves can alter the subsequent history. <ref name="T_4-65_4-67" /><ref name="H_15_3_15-60">Cote (2008), ch. 15.3, | The round-trip time compares the duration of a flow change with the time taken for a wave to travel and return. It explains why the same valve movement can behave differently in different pipe systems. The simple rapid-change estimate is not a prediction of every later pressure peak. Reflections and interacting waves can alter the subsequent history. <ref name="T_4-65_4-67" /><ref name="H_15_3_15-60">Cote (2008), ch. 15.3, p. 15-60.</ref> | ||
A normalised illustration uses water density of 1,000 kg/m³ and an assumed wave speed of 1,000 m/s. Arresting 1 m/s of flow gives an initial pressure rise of 1,000 kPa from the equation. These deliberately stated illustrative inputs show the scale of the mechanism, rather than describing a measured installation. Actual wave speed and boundary conditions require their own determination. <ref name="T_4-44_4-65_4-67">Titus (2002), ch. 4-2, pp. 4-44,4-65–4-67.</ref> | A normalised illustration uses water density of 1,000 kg/m³ and an assumed wave speed of 1,000 m/s. Arresting 1 m/s of flow gives an initial pressure rise of 1,000 kPa from the equation. These deliberately stated illustrative inputs show the scale of the mechanism, rather than describing a measured installation. Actual wave speed and boundary conditions require their own determination. <ref name="T_4-44_4-65_4-67">Titus (2002), ch. 4-2, pp. 4-44,4-65–4-67.</ref> | ||
The handbook also describes column separation and subsequent reversal as potential sources of damaging surge; a relief valve responding to pressure does not necessarily remove a fast transient before it develops. Pipe supports and pressure ratings address consequences but do not determine the pressure history. Complex networks require an analysis that represents the relevant valves, pumps, reflections and operating sequence. <ref name="H_15_3_15-59_15-60" /><ref name="T_4-67">Titus (2002), ch. 4-2, | The handbook also describes column separation and subsequent reversal as potential sources of damaging surge; a relief valve responding to pressure does not necessarily remove a fast transient before it develops. Pipe supports and pressure ratings address consequences but do not determine the pressure history. Complex networks require an analysis that represents the relevant valves, pumps, reflections and operating sequence. <ref name="H_15_3_15-59_15-60" /><ref name="T_4-67">Titus (2002), ch. 4-2, p. 4-67.</ref> | ||
== See also == | == See also == | ||
Latest revision as of 01:31, 16 November 2026
Bernoulli equation is the energy relation connecting pressure, velocity and elevation along a flowing-fluid path under stated assumptions. [1] For real fire-water systems, the balance also includes pump work and energy losses. It explains why pressure changes do not all represent friction and why a nozzle can convert pressure into jet velocity. Steady-flow use must be distinguished from transient pressure-wave analysis. [2]
The underlying hydraulic assessment follows water from a defined source to its intended outlet. Elevation, velocity changes and irreversible losses must be distinguished. Observations also need the flow and network conditions under which they were obtained. A mathematically correct result can still be misleading if a source condition, connecting segment or component loss has been omitted from the description. [3][4] Static pressure and flowing pressure describe different conditions. [5]
Conservation of mechanical energy
The relation underlies hydraulic calculation from the source to a sprinkler or a fire stream; a pitot tube uses the conversion between velocity and stagnation pressure in a suitable jet. The sprinkler K-factor packages discharge geometry and losses into a measured flow-pressure relationship. These applications share an energy basis but require their own coefficients and boundary conditions. [1][6][7]
The handbook gives an example with 4,200 L/min passing from an 80 mm bore into a 70 mm bore. Upstream flowing pressure is 300 kPa, the outlet is 5 m higher, and the stated loss is 12 m of water head. Recalculation using section-average velocities gives approximately 64.8 kPa downstream pressure. The reduction includes velocity change and elevation as well as friction loss. [8]
Turbulence and wall shear dissipate mechanical energy, so an ideal loss-free equation is insufficient for the complete pipe route; a pump supplies additional energy, while fittings introduce further losses. The resulting balance remains useful only when the selected steady-flow assumptions fit the event. Rapid valve closure requires the separate pressure-wave treatment associated with water hammer. [9]
Pressure, flow and energy
Water pressure describes only one part of the energy available in a pipe; elevation contributes potential energy, while movement contributes velocity head. Titus describes these quantities using head, expressed as an equivalent height of water. A hydraulic calculation must therefore compare locations through a common energy balance, rather than subtracting unrelated gauge readings. [10]
For steady, incompressible flow, the energy balance adds pump head and subtracts irreversible losses between two sections; the following form assumes that section-average velocity adequately represents kinetic energy. It describes a defined flow path, with all elevations measured from the same datum. Sudden changes require a different, transient analysis. [11]
| Symbol | Description | Unit |
|---|---|---|
| Pressure at the section | Pa | |
| Water density | kg/m³ | |
| Gravitational acceleration | m/s² | |
| Mean velocity | m/s | |
| Elevation, added pump head and head loss | m |
Pressure can decrease because water rises, because velocity increases, or because energy is dissipated; these effects have different physical meanings. An elevation change can be recovered on a descending route, whereas friction dissipates mechanical energy. A larger pipe can reduce friction but cannot remove the elevation difference between the source and the outlet. [12]
Continuity provides the corresponding flow constraint: volume flow equals cross-sectional area multiplied by mean velocity; the same flow moves faster through a smaller internal bore. At a junction, incoming and outgoing flows balance, while losses depend on the flow assigned to each connected segment. Nominal pipe size alone does not supply the internal diameter needed for this calculation. [11][13]
The pressure at a sprinkler is the pressure remaining after the complete upstream route has been considered; it is not the pressure indicated beside a remote pump or street hydrant. The route includes connecting mains, valves, elevation and distribution piping. Leaving out an inconvenient section creates an apparently favourable calculation without providing the corresponding water at the outlet. [14][15]
Pipe resistance and internal condition
Moving water loses mechanical energy through interaction with pipe walls and through changes in direction or section; turbulent mixing contributes to this dissipation. The resistance depends on the actual internal bore and its condition, not simply the name printed on the pipe. Valves, elbows, entries and other fittings introduce additional local losses. [16]
The Darcy-Weisbach equation expresses distributed loss through a dimensionless friction factor; that factor depends on the flow regime and, for turbulent flow, on relative roughness. The Hazen-Williams formula instead uses an empirical coefficient for water service. These methods describe related hydraulic behaviour, but their coefficients do not have interchangeable meanings. [17]
At fixed diameter and roughness coefficient, Hazen-Williams loss increases approximately with flow raised to the power 1.85; doubling flow therefore produces considerably more than twice the loss. Increasing bore has a strong opposite effect because diameter appears with an exponent of 4.87. This explains why a short restricted connection can materially influence an otherwise generous water supply. [18][14]
Fittings can be represented by local resistance coefficients or by equivalent pipe lengths where the selected method permits; equivalent length is a calculation device, not an extra measured length on the drawing. Its use must remain consistent with the pipe and friction assumptions behind the published value. A special valve's measured pressure-loss curve may provide a better representation than a generic fitting allowance. [19][20]
Age and deposits introduce further uncertainty; corrosion can increase roughness, reduce the effective bore and release material that later obstructs a smaller passage. These mechanisms are distinct, so changing a roughness coefficient does not necessarily represent a local blockage. Inspection findings and flow measurements help determine whether the calculation still describes the installation. [21][22]
A sound comparison keeps elevation, flow and valve state consistent between observations; a high static pressure can coexist with poor flowing performance because frictional loss emerges when water moves. Conversely, a pressure difference caused by elevation does not establish pipe deterioration. The interpretation depends on the physical route and the condition under which each reading was taken. [12][5]
Applying the Darcy-Weisbach relation
The Darcy-Weisbach relation describes distributed pipe loss using mean velocity and a friction factor; the factor represents the effect of the flow regime and pipe condition. Reynolds number connects velocity and diameter with the fluid's kinematic viscosity. Relative roughness compares the wall's characteristic roughness with the internal diameter. [23]
The equation below gives head loss in metres of the flowing fluid; pressure loss follows by multiplying head loss by density and gravitational acceleration. The factor is the Darcy friction factor used in the cited handbook equation. Keeping its convention explicit prevents confusion with other friction-factor definitions. [24]
| Symbol | Description | Unit |
|---|---|---|
| Head loss, length and internal diameter | m | |
| Darcy friction factor and Reynolds number | dimensionless | |
| Mean velocity and gravitational acceleration | m/s; m/s² | |
| Kinematic viscosity | m²/s |
For laminar pipe flow below a Reynolds number of about 2,000, Titus gives the factor as 64 divided by Reynolds number; transitional flow does not have the same simple certainty. In turbulent flow, roughness and Reynolds number determine the appropriate factor through correlations or a Moody diagram. A constant factor cannot be assumed valid through every change of flow or liquid condition. [17]
Titus's comparison example uses approximately 1,893 L/min in a 102.26 mm internal bore over 30.48 m. With the stated friction factor of 0.0188, recalculation gives approximately 4.21 m of head loss. These values are converted from the example's original customary units. The result differs from its Hazen-Williams example because the selected assumptions represent resistance differently. [19]
The method still requires a defensible pipe model; deposits, local restrictions and uncertain internal diameter can dominate uncertainty even when the formula is correct. Local fitting losses are added through appropriate coefficients or compatible equivalent lengths. Elevation changes remain energy terms rather than being counted as friction. [3][25]
Measuring the available supply
A supply test relates an observed discharge to the pressure remaining elsewhere in the connected system; the initial static reading describes the condition before the test discharge begins. The residual reading describes the pressure while the measured discharge is flowing. Both belong to the same test arrangement and must be recorded with its location and operating conditions. [5][26]
The flowing outlet and the pressure observation have different functions; a pitot measurement in an appropriate free jet supports an estimate of outlet flow. A gauge at the residual hydrant measures pressure in the distribution system during that discharge. Substituting jet pressure for residual system pressure confuses two different physical quantities. [26][5]
The discharge estimate depends on outlet geometry and the coefficient representing its losses; a disturbed or nonuniform jet makes a single point reading less representative. Probe alignment and position also influence the measurement. For some discharge devices, a calibrated nozzle or suitable flowmeter provides a more appropriate method than applying a simple pitot relation. [26]
Test results describe a network state, rather than an unlimited promise of future supply; domestic demand, pumps, source levels and closed valves can change that state. The pressure reference must also be carried correctly to the building calculation. A test performed at a different elevation or upstream of additional resistance needs hydraulic interpretation before comparison with system demand. [27][4]
A main-drain test provides a different kind of evidence; the handbook uses changes from previous static and flowing readings to identify possible deterioration or obstruction. This is useful for detecting change, but it does not independently establish the full sprinkler demand. Test opening, supply state and instrument condition affect whether successive observations are comparable. [28]
Pump testing likewise separates a start test from a flow-performance test; running successfully without substantial discharge demonstrates some operating functions but does not establish the entire pump curve. Flowing observations across the relevant operating range give evidence about delivery capability. The handbook describes retaining records so that deterioration and the ability to meet system demand can be assessed. [29]
Pump operation and selection
A centrifugal pump transfers shaft energy to water through a rotating impeller; its performance varies with flow, speed and pump geometry. The selected duty belongs on a curve showing this relationship, rather than being defined by a single pressure reading. The complete operating point also depends on the resistance and supply conditions of the connected installation. [30][31]
The pump head is the energy added across the pump; discharge pressure alone is not that quantity when suction pressure, elevation or velocity differ between measuring points. Horizontal pumps and vertical turbine arrangements require appropriate references for their respective configurations. A test comparison can be misleading if the water level or suction reference has changed without being recorded. [32]
A centrifugal pump normally develops its greatest head near shutoff and less head at higher flows; the closed-outlet condition therefore needs assessment for maximum system pressure. At the other end of the operating range, the remaining head must meet the required discharge pressure after losses. Driver capability and suction conditions can constrain operation even where the plotted head appears adequate. [33][34]
The handbook's account of United States NFPA 20 practice describes a rated point, a high-flow point and a shutoff limit. It reports at least 65% of rated head at 150% of rated flow, with shutoff head no greater than 140%. These are historical criteria reported in the 2008 handbook. They are not a substitute for a selected pump's actual curve or a statement of a current adopted standard. [35]
Connecting pumps in series adds their heads at a common flow; connecting them in parallel combines flow at a common head. Neither arrangement automatically doubles delivery through the installed network, because the operating intersection changes. Shared suction piping and power dependencies also remain part of the installation rather than disappearing through duplication. [36][37]
The water source must be assessed alongside the pump; a booster can overcome insufficient pressure but cannot create an absent water reserve. A powerful driver cannot correct an obstructed intake or inadequate suction conditions. Selection therefore brings together the source, suction route, performance curve, driver, controls and downstream demand. [38][34]
Rapid changes and pressure waves
Water hammer results from rapid changes in water velocity; the water and the surrounding pipe deform as a pressure disturbance travels through the system. Valve movements, pump transitions and reversal of flow can initiate the disturbance. A steady hydraulic calculation does not describe this sequence because it omits wave travel and changing boundary conditions. [39][40]
For a simple rapid velocity change, the Joukowsky relation estimates the initial pressure change; the wave speed depends on the water and the elastic response of the pipe. It is not the same as the much slower bulk flow velocity. The sign of the velocity change and the system boundaries determine whether a pressure rise or reduction develops. [39]
| Symbol | Description | Unit |
|---|---|---|
| Initial pressure change | Pa | |
| Density, wave speed and velocity change | kg/m³; m/s; m/s | |
| Critical round-trip time and relevant pipe length | s; m |
The round-trip time compares the duration of a flow change with the time taken for a wave to travel and return. It explains why the same valve movement can behave differently in different pipe systems. The simple rapid-change estimate is not a prediction of every later pressure peak. Reflections and interacting waves can alter the subsequent history. [39][41]
A normalised illustration uses water density of 1,000 kg/m³ and an assumed wave speed of 1,000 m/s. Arresting 1 m/s of flow gives an initial pressure rise of 1,000 kPa from the equation. These deliberately stated illustrative inputs show the scale of the mechanism, rather than describing a measured installation. Actual wave speed and boundary conditions require their own determination. [42]
The handbook also describes column separation and subsequent reversal as potential sources of damaging surge; a relief valve responding to pressure does not necessarily remove a fast transient before it develops. Pipe supports and pressure ratings address consequences but do not determine the pressure history. Complex networks require an analysis that represents the relevant valves, pumps, reflections and operating sequence. [40][43]
See also
Notes
- ↑ 1.0 1.1 Titus (2002), ch. 4-2, pp. 4-47–4-48.
- ↑ Titus (2002), ch. 4-2, pp. 4-47–4-52,4-65–4-67.
- ↑ 3.0 3.1 Titus (2002), ch. 4-2, pp. 4-47–4-56.
- ↑ 4.0 4.1 Fleming (2002), ch. 4-3, pp. 4-81–4-83.
- ↑ 5.0 5.1 5.2 5.3 Fleming (2002), ch. 4-3, p. 4-81.
- ↑ Cote (2008), ch. 15.3, pp. 15-40,15-46–15-47.
- ↑ Fleming (2002), ch. 4-3, p. 4-75.
- ↑ Cote (2008), ch. 15.3, p. 15-40.
- ↑ Titus (2002), ch. 4-2, pp. 4-49–4-56,4-65–4-67.
- ↑ Titus (2002), ch. 4-2, pp. 4-45–4-48.
- ↑ 11.0 11.1 Titus (2002), ch. 4-2, pp. 4-47–4-50.
- ↑ 12.0 12.1 Titus (2002), ch. 4-2, pp. 4-47–4-52.
- ↑ Cote (2008), ch. 16.3, pp. 16-41–16-42.
- ↑ 14.0 14.1 Fleming (2002), ch. 4-3, pp. 4-75–4-81.
- ↑ Hopkins et al. (2005), pp. xxxvii–xxxviii.
- ↑ Titus (2002), ch. 4-2, pp. 4-49–4-56.
- ↑ 17.0 17.1 Titus (2002), ch. 4-2, pp. 4-50–4-53.
- ↑ Titus (2002), ch. 4-2, pp. 4-52–4-53.
- ↑ 19.0 19.1 Titus (2002), ch. 4-2, p. 4-56.
- ↑ Cote (2008), ch. 15.3, p. 15-59.
- ↑ Cote (2008), ch. 15.5, pp. 15-79–15-81.
- ↑ Cote (2008), ch. 16.11, p. 16-212.
- ↑ Titus (2002), ch. 4-2, pp. 4-49–4-52.
- ↑ Titus (2002), ch. 4-2, pp. 4-50–4-52.
- ↑ Cote (2008), ch. 15.5, pp. 15-80–15-81.
- ↑ 26.0 26.1 26.2 Cote (2008), ch. 15.3, pp. 15-46–15-47.
- ↑ Cote (2008), ch. 15.2, pp. 15-23–15-24.
- ↑ Cote (2008), ch. 16.11, pp. 16-210–16-211.
- ↑ Cote (2008), ch. 16.11, p. 16-220.
- ↑ Cote (2008), ch. 15.6, pp. 15-85,15-89–15-92.
- ↑ Titus (2002), ch. 4-2, pp. 4-67–4-69.
- ↑ Cote (2008), ch. 15.6, pp. 15-89–15-90.
- ↑ Cote (2008), ch. 15.6, pp. 15-91–15-98.
- ↑ 34.0 34.1 Titus (2002), ch. 4-2, pp. 4-68–4-69.
- ↑ Cote (2008), ch. 15.6, p. 15-92.
- ↑ Titus (2002), ch. 4-2, p. 4-70.
- ↑ Cote (2008), ch. 15.6, pp. 15-93–15-95.
- ↑ Cote (2008), ch. 15.6, pp. 15-91–15-99.
- ↑ 39.0 39.1 39.2 Titus (2002), ch. 4-2, pp. 4-65–4-67.
- ↑ 40.0 40.1 Cote (2008), ch. 15.3, pp. 15-59–15-60.
- ↑ Cote (2008), ch. 15.3, p. 15-60.
- ↑ Titus (2002), ch. 4-2, pp. 4-44,4-65–4-67.
- ↑ Titus (2002), ch. 4-2, p. 4-67.
References
- Cote, A. E. (Ed.). (2008). Fire protection handbook (20th ed.). National Fire Protection Association.
- Fleming, R. P. (2002). Automatic sprinkler system calculations. In P. J. DiNenno (Ed.), SFPE handbook of fire protection engineering (3rd ed., pp. 4-72–4-87). National Fire Protection Association.
- Hopkins, M., Schoenrock, J., & Budnick, E. (2005). Fire suppression systems (NIST NCSTAR 1-4B). National Institute of Standards and Technology.
- Titus, J. J. (2002). Hydraulics. In P. J. DiNenno (Ed.), SFPE handbook of fire protection engineering (3rd ed., pp. 4-44–4-71). National Fire Protection Association.