NFPA 30 limits the largest container for each container type and class of liquid. The system of classes is described in [[ | NFPA 30 limits the largest container for each container type and class of liquid. The system of classes is described in [[flammable and combustible liquid classification]].<ref name="Ordile-7-28" /> Ordile (2008) reproduces the table of the 2003 edition, and NUREG-1805, a 2004 report of the US Nuclear Regulatory Commission, quotes the 2000 edition.<ref name="Ordile-7-28" /><ref name="IS-B-20" /> | ||
{| class="wikitable" | {| class="wikitable" | ||
Latest revision as of 00:38, 16 November 2026
A safety can is a container for handling small quantities of flammable and combustible liquids. It is built to avoid leakage and designed to limit spillage, vapour release and rupture in a fire.[1] A typical safety can has a pouring outlet with a tight-fitting cap or a valve that a spring keeps closed unless it is held open by hand. The contents therefore do not spill if the can tips over, and the cap also acts as an emergency vent when the can is exposed to fire.[1]

Ordile (2008) calls safety cans the preferred container for small quantities of these liquids.[1] In the United States, NFPA 30 (2000 and 2003 editions) permitted larger safety cans than ordinary metal containers for Class IA liquids.[2][3] Laboratory rules allow more liquid when it is kept in safety cans, and handbook guidance for some occupancies asks for safety cans for all liquid inside the building.[4][5] The limits in this article come from summaries of NFPA codes of around 2000 to 2008. They are historical US values, not current or universal requirements.
Design features
Ordile's description contains three aims for the design of a safety can. It should avoid leakage, minimise the likelihood of spillage and vapour release, and minimise the likelihood of rupture of the container in a fire.[1] Substantial construction serves the first aim. The self-closing cap or spring-loaded valve limits spillage, because the outlet is open only while a person holds it, and the contents stay in when the can tips over.[1] The cap also provides an emergency vent when the can is exposed to fire.[1]
Venting matters because overpressure failure is the main hazard of closed containers in a fire. A container that bursts releases liquid that feeds the fire and can rupture further containers, so that the fire spreads quickly.[6] Slye (2008) adds that any closed container may rupture violently when it is exposed to a severe fire.[7] Storage of liquids in closed containers is nevertheless one of the basic principles of fire and explosion prevention, together with excluding ignition sources and ventilating against vapour build-up.[7]
Ordile's description of the safety can names no flame arrester. Another handbook chapter does ask for flame arresters on containers in one process. For spray finishing, Scarbrough (2008b) recommends closed containers with suitable pressure relief devices and flame arresters at all openings. The quantity kept near the process should be limited to one working shift, and the containers are best kept outside the spray booth, 1 to 2 m away from it.[8]
Why a closed can matters
A liquid can ignite only when it is at or above its flash point.[9] Class I liquids have flash points below 37.8 °C (100 °F) and can therefore give off an ignitable vapour at ordinary room temperatures.[7][10] Inside a closed container, the share of vapour in the space above the liquid follows from the vapour pressure of the liquid. Slye (2008) gives the vapour fraction as the vapour pressure divided by the total pressure:[11] The density of the vapour-air mixture relative to air then follows from the vapour fraction and the vapour density ratio of the pure vapour:[11]
| Symbol | Description | Unit |
|---|---|---|
| volume fraction of vapour in the closed space above the liquid | – | |
| vapour pressure of the liquid at its temperature | kPa | |
| total (atmospheric) pressure, about 101 kPa | kPa | |
| vapour density ratio of the pure vapour, molecular weight divided by 29 | – | |
| density of the vapour-air mixture relative to air | – |
The relations hold for a liquid in equilibrium with its vapour in a closed space at atmospheric pressure.[11]
Worked example. Slye (2008) uses ethyl acetate at 21 °C (70 °F), where its vapour pressure is about 16.2 kPa (2.35 psi).[11] In a closed container at 101 kPa, the vapour fraction is 16.2/101 = 0.16, or 16 % vapour and 84 % air. The pure vapour is 3.0 times as dense as air, so the mixture has a relative density of 0.16 × 3.0 + 0.84 × 1 = 1.32.[11] For acetone at 37.8 °C, with a vapour pressure of 52 kPa (7.6 psia), the same relation gives 52 % vapour.[11]
A mixture heavier than air tends to collect in low areas and can travel a considerable distance to an unprotected ignition source.[11] The self-closing outlet of a safety can is designed to keep such vapour release small.[1]
Size limits in NFPA 30
NFPA 30 limits the largest container for each container type and class of liquid. The system of classes is described in flammable and combustible liquid classification.[2] Ordile (2008) reproduces the table of the 2003 edition, and NUREG-1805, a 2004 report of the US Nuclear Regulatory Commission, quotes the 2000 edition.[2][3]
| Container | Edition | Class IA | Class IB | Class IC | Class II | Class IIIA |
|---|---|---|---|---|---|---|
| Safety can | 2003 | 10 L (2.6 gal) | 20 L (5.3 gal) | 20 L (5.3 gal) | 20 L (5.3 gal) | 20 L (5.3 gal) |
| Metal (other than drums) or approved plastic | 2003 | 5 L (1.3 gal) | 20 L (5.3 gal) | 20 L (5.3 gal) | 20 L (5.3 gal) | 20 L (5.3 gal) |
| Safety can | 2000 | 2 gal (7.6 L) | 5 gal (18.9 L) | 5 gal (18.9 L) | 5 gal (18.9 L) | 5 gal (18.9 L) |
| Metal (other than DOT drum) or approved plastic | 2000 | 1 gal (3.8 L) | 5 gal (18.9 L) | 5 gal (18.9 L) | 5 gal (18.9 L) | 5 gal (18.9 L) |
The 2003 values follow Ordile (2008) and the 2000 values follow NUREG-1805, where the last column covers all Class III liquids.[2][3]
For Class IA liquids, both editions allow a safety can twice the size of an ordinary metal container. The limits are 10 L against 5 L in 2003, and 2 gal against 1 gal in 2000.[2][3] For the other classes the limits for the two container types are equal. Glass is far more restricted, with only 0.5 L allowed for Class IA liquids in the 2003 edition, a twentieth of the safety can limit.[2] The two editions also differ in their numbers. The 2003 table gives metric sizes such as 10 L and 20 L, while the 2000 table gives the gallon sizes 2 gal and 5 gal, which are about 7.6 L and 18.9 L.[2][3]
Use in laboratories and other occupancies
In laboratories, NFPA 45 (2004 edition), as summarised by Anderson (2008a), raises the permitted quantities when liquids are kept in storage cabinets or safety cans.[4] In a laboratory unit of moderate fire hazard (Class B), the allowance of Class I liquid rises from 20 L to 38 L per 9.3 m² (100 ft²). This higher value includes the liquid in cabinets and safety cans.[12] Safety cans and flammable liquid storage cabinets are thus the two ways in which the standard allows a laboratory to hold about twice the quantity it may hold in other containers.[12] For Class I liquids in containers up to 20 L (5 gal), Anderson (2008a) describes three dispensing locations.[12] One is a chemical fume hood. Another is an area ventilated to keep flammable vapour below 25 % of the lower flammable limit. The third is an inside liquid storage area designed and protected for dispensing Class I liquids under NFPA 30.[12]
McDaniel (2008) applies the same idea to libraries and museums. All flammable or combustible liquids permitted inside such a building should be in safety cans.[5] Only the quantity needed for one 8-hour shift should be outside the storage cabinet, and it should remain in safety cans until it is used.[5] For dipping and coating processes, Katunar (2008) lists approved safety cans among the acceptable ways of moving liquids, next to closed containers, approved portable tanks, intermediate bulk containers and piping.[13] NFPA 34, as summarised by Katunar (2008), described five ways to transfer Class I and II liquids from shipping containers to process equipment.[13] They were containers of at most 19 L (5 gal), approved safety containers, closed piping, an approved pump on a portable tank or container, and gravity through a listed self-closing valve or faucet.[13] On construction sites, Davis (2008a) asks for approved metal containers or the original shipping containers, kept tightly closed when not in use.[14]
Filling and static electricity
Filling a can from a larger vessel can create a static electricity hazard.[15] Ordile (2008) states that flammable liquids should be dispensed in a well-ventilated area free of ignition sources. Bonding should connect the dispensing equipment and the container being filled.[1] In laboratories, Class I liquids should not be transferred between conductive containers larger than 4 L (1 gal) unless the containers are bonded directly or through a common grounding system. Nonconductive containers of that size need special dispensing procedures.[12]
Scarbrough (2008a) explains why a can standing on an insulating surface is a particular problem. When charged liquid flows into a metal can that rests on a plastic surface, the charge in the liquid attracts an opposite charge to the inside of the can. An equal "free" charge of the same sign as the liquid remains on the outside, and it can escape to ground as a spark.[15]
This source of sparking is suspected of creating an ignition potential in some situations, when a gasoline can is filled while it stands on the plastic bedliner of a pickup truck. The spark jumps from the edge of the fill opening to the grounded fill pipe.[15] Scarbrough notes that the hazard is easily controlled by taking the can off the vehicle and placing it on the ground, where the charge can leak away.[15] Bonding and grounding cannot remove the charge on the liquid surface inside a container. That charge decays over a relaxation time of a fraction of a second to several minutes, depending on the conductivity of the liquid.[15]
Ordile (2008) also names practices that safety cans replace. Open pails and open buckets should never be used for storing or transferring liquids.[1] Liquids may instead be dispensed from their original shipping containers. From drums, an approved hand pump drawing through the top is preferred to a self-closing faucet, because it reduces the hazard of leakage.[1]
Limits of the sources
The source folder contains no product standard or test method for safety cans and no fire test data on their performance. The handbook describes typical designs, not minimum specifications.[1] The size limits are second-hand summaries of two editions of NFPA 30 that differ from each other, and the folder does not contain the code itself.[2][3] Neither the SFPE handbook nor Introduction to Fire Safety Engineering treats safety cans, so this article rests on the NFPA Fire Protection Handbook and NUREG-1805.
See also
Notes
- ↑ 1.00 1.01 1.02 1.03 1.04 1.05 1.06 1.07 1.08 1.09 1.10 Ordile (2008), p. 7-31.
- ↑ 2.0 2.1 2.2 2.3 2.4 2.5 2.6 2.7 Ordile (2008), p. 7-28.
- ↑ 3.0 3.1 3.2 3.3 3.4 3.5 Iqbal and Salley (2004), p. B-20.
- ↑ 4.0 4.1 Anderson (2008a), pp. 9-163–9-164.
- ↑ 5.0 5.1 5.2 McDaniel (2008), p. 20-185.
- ↑ Ordile (2008), p. 7-27.
- ↑ 7.0 7.1 7.2 Slye (2008), p. 6-198.
- ↑ Scarbrough (2008b), p. 9-33.
- ↑ Hurley and Bukowski (2008), p. 3-126.
- ↑ Iqbal and Salley (2004), p. B-17.
- ↑ 11.0 11.1 11.2 11.3 11.4 11.5 11.6 Slye (2008), p. 6-199.
- ↑ 12.0 12.1 12.2 12.3 12.4 Anderson (2008a), p. 9-164.
- ↑ 13.0 13.1 13.2 Katunar (2008), p. 9-42.
- ↑ Davis (2008a), p. 11-54.
- ↑ 15.0 15.1 15.2 15.3 15.4 Scarbrough (2008a), p. 11-64.
References
- Anderson, R. R. (2008a). Fire protection of laboratories using chemicals. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-157–9-166). National Fire Protection Association.
- Davis, R. J. (2008a). Fire hazards of construction, alteration, and demolition of buildings. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 11-47–11-58). National Fire Protection Association.
- Hurley, M. J., & Bukowski, R. W. (2008). Fire hazard analysis techniques. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 3-121–3-134). National Fire Protection Association.
- Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.
- Katunar, J., III (2008). Dipping and coating processes. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-39–9-51). National Fire Protection Association.
- McDaniel, D. L. (2008). Library and museum collections. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 20-179–20-202). National Fire Protection Association.
- Ordile, A. M. (2008). Storage of flammable and combustible liquids. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 7-15–7-33). National Fire Protection Association.
- Scarbrough, D. R. (2008a). Control of electrostatic ignition sources. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 11-59–11-68). National Fire Protection Association.
- Scarbrough, D. R. (2008b). Spray finishing and powder coating. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-27–9-37). National Fire Protection Association.
- Slye, O. M., Jr. (2008). Flammable and combustible liquids. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-197–6-208). National Fire Protection Association.