Visibility of light-emitting and light-reflecting signs against the extinction coefficient of the smoke, with the 10 m and 5 m design limits. Based on Mulholland (2002), p. 2-265, and Australian Building Codes Board (2022), p. 10.
Visibility of light-emitting and light-reflecting signs against the extinction coefficient of the smoke, with the 10 m and 5 m design limits.


Original vector illustration for [[Visibility in smoke]], level 2 Intermediate.
Original vector illustration for [[Visibility in smoke]], level 2 Intermediate.


* Source basis: Mulholland (2002), p. 2-265 (Eq. 14 and 15, Figure 2-13.5); Jin (2002), p. 2-45 (irritant region 0.25 1/m); Australian Building Codes Board (2022), p. 10 (10 m and 5 m). New chart, do not copy Figure 2-13.5.
* Alt text: Falling lines on log scales: visibility of light-emitting signs is 8 divided by K, of reflecting signs 3 divided by K, with 10 m and 5 m limits.
* Alt text: Falling lines on log scales: visibility of light-emitting signs is 8 divided by K, of reflecting signs 3 divided by K, with 10 m and 5 m limits.


== Licensing ==
== Licensing ==
New drawing by Fire Safety Academy. © Fire Safety Academy.
New drawing by Fire Safety Academy. © Fire Safety Academy.

Latest revision as of 09:36, 13 November 2026

Summary

Visibility of light-emitting and light-reflecting signs against the extinction coefficient of the smoke, with the 10 m and 5 m design limits.

Original vector illustration for Visibility in smoke, level 2 Intermediate.

  • Alt text: Falling lines on log scales: visibility of light-emitting signs is 8 divided by K, of reflecting signs 3 divided by K, with 10 m and 5 m limits.

Licensing

New drawing by Fire Safety Academy. © Fire Safety Academy.