== Summary ==
== Summary ==
Radiant heat flux from a 5 m² transformer oil pool fire (8950 kW) by the point source model, for radiative fractions of 0.30 and 0.60. Based on Iqbal and Salley (2004), p. 5-3; Budnick et al. (2008), p. 3-150; Nowlen et al. (2005b), p. H-1.
Radiant heat flux from a 5 m² transformer oil pool fire (8950 kW) by the point source model, for radiative fractions of 0.30 and 0.60.


Original illustration for [[Transformer fire]].
Original illustration for [[Transformer fire]].

Latest revision as of 09:33, 13 November 2026

Summary

Radiant heat flux from a 5 m² transformer oil pool fire (8950 kW) by the point source model, for radiative fractions of 0.30 and 0.60.

Original illustration for Transformer fire.

  • Alt text: Radiant heat flux versus distance from a 9 MW transformer oil pool fire for radiative fractions 0.30 and 0.60, with cable damage criteria