Opposed-flow spread rate over 1.27 cm Douglas fir particleboard against the surface temperature ahead of the flame, from the LIFT formula and data. Below 210 °C spread does not continue; at 382 °C the surface ignites | Opposed-flow spread rate over 1.27 cm Douglas fir particleboard against the surface temperature ahead of the flame, from the LIFT formula and data. Below 210 °C spread does not continue; at 382 °C the surface ignites. | ||
Original illustration for [[Opposed-flow flame spread]], level 4 Expert. | Original illustration for [[Opposed-flow flame spread]], level 4 Expert. | ||
* Alt text: Rising curve of spread rate against surface temperature for particleboard, from 0.46 mm/s at 210 °C to about 94 mm/s at 370 °C, on a log scale. | * Alt text: Rising curve of spread rate against surface temperature for particleboard, from 0.46 mm/s at 210 °C to about 94 mm/s at 370 °C, on a log scale. | ||
== Licensing == | == Licensing == | ||
New drawing by Fire Safety Academy. © Fire Safety Academy. | New drawing by Fire Safety Academy. © Fire Safety Academy. | ||
Latest revision as of 09:17, 13 November 2026
Summary
Opposed-flow spread rate over 1.27 cm Douglas fir particleboard against the surface temperature ahead of the flame, from the LIFT formula and data. Below 210 °C spread does not continue; at 382 °C the surface ignites.
Original illustration for Opposed-flow flame spread, level 4 Expert.
- Alt text: Rising curve of spread rate against surface temperature for particleboard, from 0.46 mm/s at 210 °C to about 94 mm/s at 370 °C, on a log scale.
Licensing
New drawing by Fire Safety Academy. © Fire Safety Academy.