== Summary ==
Pressure difference between the stairwell and the building in the worked example, against height. Based on Klote (2002), p. 4-288.
Pressure difference between the stairwell and the building in the worked example, against height.


Original illustration for [[Network model]], level 4 Expert.
Original illustration for [[Network model]], level 4 Expert.


* Source basis: Klote (2002), p. 4-288 (Equation 14 and Example 4; 13 Pa minimum, 137 Pa maximum)
* Alt text: Line chart: pressure difference across stair doors rises linearly from 20 Pa at the bottom to 106 Pa at 66 m, between limits of 13 and 137 Pa.
* Alt text: Line chart: pressure difference across stair doors rises linearly from 20 Pa at the bottom to 106 Pa at 66 m, between limits of 13 and 137 Pa.


== Licensing ==
== Licensing ==
New drawing by Fire Safety Academy. © Fire Safety Academy.
New drawing by Fire Safety Academy. © Fire Safety Academy.

Latest revision as of 09:15, 13 November 2026

Summary

Pressure difference between the stairwell and the building in the worked example, against height.

Original illustration for Network model, level 4 Expert.

  • Alt text: Line chart: pressure difference across stair doors rises linearly from 20 Pa at the bottom to 106 Pa at 66 m, between limits of 13 and 137 Pa.