The pallet fire calculation uses the base of the storage as its common height datum | The pallet fire calculation uses the base of the storage as its common height datum. | ||
Original illustration for [[Heskestad plume]], level 3 Advanced. | Original illustration for [[Heskestad plume]], level 3 Advanced. | ||
* Alt text: A 5 m plane lies above the 4.23 m mean flame height and carries a calculated 13.3 kg/s plume flow. | * Alt text: A 5 m plane lies above the 4.23 m mean flame height and carries a calculated 13.3 kg/s plume flow. | ||
* Accuracy notes: Virtual origin uses storage relationship L-0.175 Qc^0.4, not pool relationship; do not place a smoke interface below 5 m. | * Accuracy notes: Virtual origin uses storage relationship L-0.175 Qc^0.4, not pool relationship; do not place a smoke interface below 5 m. | ||
Latest revision as of 09:09, 13 November 2026
Summary
The pallet fire calculation uses the base of the storage as its common height datum.
Original illustration for Heskestad plume, level 3 Advanced.
- Alt text: A 5 m plane lies above the 4.23 m mean flame height and carries a calculated 13.3 kg/s plume flow.
- Accuracy notes: Virtual origin uses storage relationship L-0.175 Qc^0.4, not pool relationship; do not place a smoke interface below 5 m.
Licensing
New drawing by Fire Safety Academy. © Fire Safety Academy.
File history
Click on a date/time to view the file as it appeared at that time.
| Date/Time | Thumbnail | Dimensions | User | Comment | |
|---|---|---|---|---|---|
| current | 16:29, 2 November 2026 | 900 × 600 (8 KB) | Emma (talk | contribs) | Watermark: Fire Safety Academy logo icon, 70 px, 45 % opacity |
You cannot overwrite this file.
File usage
The following page uses this file: