Critical velocity to stop smoke backflow in a corridor at full scale and in a 1/4 scale model, from Thomas's relation. Based on Klote (2002), pp. 4-279–4-280.
Critical velocity to stop smoke backflow in a corridor at full scale and in a 1/4 scale model, from Thomas's relation.


Original illustration for [[Froude scaling]], level 4 Expert.
Original illustration for [[Froude scaling]], level 4 Expert.


* Source basis: Klote (2002), p. 4-279 (Equations 4 and 4a) and p. 4-280 (wastebasket example); Milke (2002b), p. 4-294 (scaling relations)
* Alt text: Two corridors in side view: full scale 1.22 m wide with 150 kW fire and 1.45 m/s airflow; model 0.31 m wide, 4.7 kW, 0.73 m/s.
* Alt text: Two corridors in side view: full scale 1.22 m wide with 150 kW fire and 1.45 m/s airflow; model 0.31 m wide, 4.7 kW, 0.73 m/s.


== Licensing ==
== Licensing ==
New drawing by Fire Safety Academy. © Fire Safety Academy.
New drawing by Fire Safety Academy. © Fire Safety Academy.

Latest revision as of 09:06, 13 November 2026

Summary

Critical velocity to stop smoke backflow in a corridor at full scale and in a 1/4 scale model, from Thomas's relation.

Original illustration for Froude scaling, level 4 Expert.

  • Alt text: Two corridors in side view: full scale 1.22 m wide with 150 kW fire and 1.45 m/s airflow; model 0.31 m wide, 4.7 kW, 0.73 m/s.