Recommended unreliability values for automatic suppression systems in fire risk studies of US nuclear power plants. Based on Parkinson et al. (1994), as cited in Nowlen et al. (2005b), p. P-6.
Recommended unreliability values for automatic suppression systems in fire risk studies of US nuclear power plants.


Original vector illustration for [[Deluge system]], level 2 Intermediate.
Original vector illustration for [[Deluge system]], level 2 Intermediate.


* Source basis: Nowlen et al. (2005b), p. P-6
* Alt text: Bar chart of unreliability: wet pipe 0.02, carbon dioxide 0.04, halon 0.05, deluge or preaction 0.05.
* Alt text: Bar chart of unreliability: wet pipe 0.02, carbon dioxide 0.04, halon 0.05, deluge or preaction 0.05.


== Licensing ==
== Licensing ==
New drawing by Fire Safety Academy. © Fire Safety Academy.
New drawing by Fire Safety Academy. © Fire Safety Academy.

Latest revision as of 08:49, 13 November 2026

Summary

Recommended unreliability values for automatic suppression systems in fire risk studies of US nuclear power plants.

Original vector illustration for Deluge system, level 2 Intermediate.

  • Alt text: Bar chart of unreliability: wet pipe 0.02, carbon dioxide 0.04, halon 0.05, deluge or preaction 0.05.

Licensing

New drawing by Fire Safety Academy. © Fire Safety Academy.