Maximum ceiling jet temperature rise under a 5 m ceiling for steady fires of 0.5, 1 and 2.5 MW, with a 10 °C smoke detector criterion and the 37 °C rise for a 57 °C heat detector in a 20 °C room. Based on National Research Council of Canada et al. (2005), p. 2.7-3, and Iqbal and Salley (2004), p. 11-7.
Maximum ceiling jet temperature rise under a 5 m ceiling for steady fires of 0.5, 1 and 2.5 MW, with a 10 °C smoke detector criterion and the 37 °C rise for a 57 °C heat detector in a 20 °C room.


Original vector illustration for [[Ceiling jet]], level 2 Intermediate.
Original vector illustration for [[Ceiling jet]], level 2 Intermediate.


* Source basis: National Research Council of Canada et al. (2005), p. 2.7-3 (correlation and constants); Alpert (2002), p. 2-19 (validity: steady fires, unconfined ceilings); Iqbal and Salley (2004), p. 11-7; Ministry of Business, Innovation and Employment (2025b), p. 27
* Alt text: Line chart: ceiling jet temperature rise under a 5 m ceiling falls with distance for fires of 0.5, 1 and 2.5 MW, crossing detector thresholds.
* Alt text: Line chart: ceiling jet temperature rise under a 5 m ceiling falls with distance for fires of 0.5, 1 and 2.5 MW, crossing detector thresholds.


== Licensing ==
== Licensing ==
New drawing by Fire Safety Academy. © Fire Safety Academy.
New drawing by Fire Safety Academy. © Fire Safety Academy.

Latest revision as of 08:45, 13 November 2026

Summary

Maximum ceiling jet temperature rise under a 5 m ceiling for steady fires of 0.5, 1 and 2.5 MW, with a 10 °C smoke detector criterion and the 37 °C rise for a 57 °C heat detector in a 20 °C room.

Original vector illustration for Ceiling jet, level 2 Intermediate.

  • Alt text: Line chart: ceiling jet temperature rise under a 5 m ceiling falls with distance for fires of 0.5, 1 and 2.5 MW, crossing detector thresholds.