== Summary ==
== Summary ==
Plume centreline temperature above a 500 kW fire 1 m in diameter at 20 °C ambient, compared with the cable damage criteria. Trays at 2.5 m and 7 m are marked. Based on Budnick et al. (2008), pp. 3-153–3-155.
Plume centreline temperature above a 500 kW fire 1 m in diameter at 20 °C ambient, compared with the cable damage criteria. Trays at 2.5 m and 7 m are marked.


Original illustration for [[Cable fire]].
Original illustration for [[Cable fire]].

Latest revision as of 08:43, 13 November 2026

Summary

Plume centreline temperature above a 500 kW fire 1 m in diameter at 20 °C ambient, compared with the cable damage criteria. Trays at 2.5 m and 7 m are marked.

Original illustration for Cable fire.

  • Alt text: Curve of plume centreline temperature against height above a 500 kW fire, crossing 330 °C near 2.2 m and 205 °C near 3.0 m