== Summary ==
== Summary ==
Davoodi's example: flames about 5.2 m high above a burning section, tilted 45° by the wind, radiate about 66 kW/m²; with a view factor of about 0.3 the wood roof beyond a 0.9 m parapet receives about 20 kW/m², above the 12.5 kW/m² for pilot ignition. Based on Davoodi (2008), p. 18-14.
Davoodi's example: flames about 5.2 m high above a burning section, tilted 45° by the wind, radiate about 66 kW/m²; with a view factor of about 0.3 the wood roof beyond a 0.9 m parapet receives about 20 kW/m², above the 12.5 kW/m² for pilot ignition.


Original illustration for [[Roof covering fire test]].
Original illustration for [[Roof covering fire test]].


* Source basis: Davoodi (2008), p. 18-14 (text and Figure 18.1.9); Van Rossum (2027), §5.4 (view factor and Stefan–Boltzmann relation); Janssens (2008), p. 2-69 (12.5 kW/m² piloted ignition of wood). Redraw, do not copy Figure 18.1.9.
* Alt text: Section through a one-storey building split by a fire wall with a parapet; flames tilted 45 degrees over the parapet radiate onto the neighbouring wood roof.
* Alt text: Section through a one-storey building split by a fire wall with a parapet; flames tilted 45 degrees over the parapet radiate onto the neighbouring wood roof.


== Licensing ==
== Licensing ==
New drawing by Fire Safety Academy. © Fire Safety Academy.
New drawing by Fire Safety Academy. © Fire Safety Academy.

Latest revision as of 08:31, 8 November 2026

Summary

Davoodi's example: flames about 5.2 m high above a burning section, tilted 45° by the wind, radiate about 66 kW/m²; with a view factor of about 0.3 the wood roof beyond a 0.9 m parapet receives about 20 kW/m², above the 12.5 kW/m² for pilot ignition.

Original illustration for Roof covering fire test.

  • Alt text: Section through a one-storey building split by a fire wall with a parapet; flames tilted 45 degrees over the parapet radiate onto the neighbouring wood roof.