Summary
Side elevation of the flooring radiant panel test: a gas-fired panel inclined at 30° heats a horizontal specimen about 1 m long, from about 11 kW/m² at the pilot end to about 1 kW/m² at the far end. Based on Hirschler (2008b), p. 18-34, and Stull and Chines (2008), p. 6-97.
Original illustration for Flooring radiant panel test.
- Source basis: Hirschler (2008b), p. 18-34, Figure 18.2.8 (side elevation; chamber 140 cm long, 71 cm high, panel 30°, pilot burner, radiation pyrometer) and text (39 in./1000 mm specimen, 11 to 1 kW/m², calibration curve of flux against distance); Stull and Chines (2008), p. 6-97, Figure 6.5.10 (same apparatus); Madrzykowski and Stroup (2008), p. 2-43 (air-gas-fuelled panel, 10 to 1 kW/m²). Redraw, do not copy.
- Alt text: Side view of a closed chamber with a gas-fired panel tilted at 30 degrees over a horizontal floor-covering specimen and a pilot burner at its hot end.
Licensing
New drawing by Fire Safety Academy. © Fire Safety Academy.