The barrel of the burner sits 19.1 mm (3/4 in.) below the lower edge of the sample, and the flame is adjusted to extend 38.1 mm (1 1/2 in.). The sample is exposed for 3 s.<ref name="SC-6-90" /> Edge ignition follows the reasoning of the committee that drafted the former NFPA 702 apparel test, which concluded that the lower edge of a fabric should be easier to ignite than its surface.<ref name="SC-6-89" /> | The barrel of the burner sits 19.1 mm (3/4 in.) below the lower edge of the sample, and the flame is adjusted to extend 38.1 mm (1 1/2 in.). The sample is exposed for 3 s.<ref name="SC-6-90" /> Edge ignition follows the reasoning of the committee that drafted the former NFPA 702 apparel test, which concluded that the lower edge of a fabric should be easier to ignite than its surface.<ref name="SC-6-89" /> | ||
[[File:fse-childrens-sleepwear-flammability-v1.svg|thumb|upright=1.5|alt=Vertical fabric specimen in a test cabinet with a small burner flame at its lower edge and the char length marked from the edge|Children's sleepwear test of 16 CFR Parts 1615 and 1616: a vertical specimen is exposed at its lower edge to a 38.1 mm flame for 3 s, and the char length is measured from the lower edge | [[File:fse-childrens-sleepwear-flammability-v1.svg|thumb|upright=1.5|alt=Vertical fabric specimen in a test cabinet with a small burner flame at its lower edge and the char length marked from the edge|Children's sleepwear test of 16 CFR Parts 1615 and 1616: a vertical specimen is exposed at its lower edge to a 38.1 mm flame for 3 s, and the char length is measured from the lower edge.]] | ||
The result is expressed as char length. This is the distance from the lower edge of the fabric to the end of the void or tear in the charred, burned or damaged area.<ref name="SC-6-90" /> The tear is made by attaching weights near one lower corner and lifting the sample by the opposite corner.<ref name="SC-6-90" /> A fabric passes if the average char length of five specimens does not exceed 178 mm (7 in.) and no single specimen reaches a char length of 254 mm (10 in.).<ref name="SC-6-90" /> | The result is expressed as char length. This is the distance from the lower edge of the fabric to the end of the void or tear in the charred, burned or damaged area.<ref name="SC-6-90" /> The tear is made by attaching weights near one lower corner and lifting the sample by the opposite corner.<ref name="SC-6-90" /> A fabric passes if the average char length of five specimens does not exceed 178 mm (7 in.) and no single specimen reaches a char length of 254 mm (10 in.).<ref name="SC-6-90" /> | ||
| Line 43: | Line 43: | ||
The general clothing test of Part 1610 is gentler. It touches the face of a specimen held at 45 degrees with a 15.9 mm (5/8 in.) flame for 1 s. The fabric is classified by the time the flame takes to spread 127 mm (5 in.).<ref name="SC-6-89" /> A further method, ASTM D6545, ''Standard Test Method for Flammability of Textiles Used in Children's Sleepwear'', appears among the ASTM fabric fire test standards listed by Hirschler (2008a).<ref name="H8a-6-59">Hirschler (2008a), p. 6-59.</ref> | The general clothing test of Part 1610 is gentler. It touches the face of a specimen held at 45 degrees with a 15.9 mm (5/8 in.) flame for 1 s. The fabric is classified by the time the flame takes to spread 127 mm (5 in.).<ref name="SC-6-89" /> A further method, ASTM D6545, ''Standard Test Method for Flammability of Textiles Used in Children's Sleepwear'', appears among the ASTM fabric fire test standards listed by Hirschler (2008a).<ref name="H8a-6-59">Hirschler (2008a), p. 6-59.</ref> | ||
[[File:fse-childrens-sleepwear-flammability-v2.svg|thumb|upright=1.5|alt=Two schematics: fabric at 45 degrees with a small flame on its face for 1 s, and vertical fabric with a larger flame on its lower edge for 3 s|General clothing test (16 CFR Part 1610) and children's sleepwear test (16 CFR Parts 1615 and 1616) compared | [[File:fse-childrens-sleepwear-flammability-v2.svg|thumb|upright=1.5|alt=Two schematics: fabric at 45 degrees with a small flame on its face for 1 s, and vertical fabric with a larger flame on its lower edge for 3 s|General clothing test (16 CFR Part 1610) and children's sleepwear test (16 CFR Parts 1615 and 1616) compared.]] | ||
== Fabrics and garment design == | == Fabrics and garment design == | ||
| Line 53: | Line 53: | ||
Oxygen available on both sides of a loosely fitting garment accelerates flame spread. This principle underlies the later snug-fit change to the requirements.<ref name="SC-6-86" /> Braun and co-workers, as cited by Stull and Chines (2008), had earlier suggested that fabrics with short ignition times and a higher heat release rate be used only in tightly fitting garments.<ref name="SC-6-91" /> | Oxygen available on both sides of a loosely fitting garment accelerates flame spread. This principle underlies the later snug-fit change to the requirements.<ref name="SC-6-86" /> Braun and co-workers, as cited by Stull and Chines (2008), had earlier suggested that fabrics with short ignition times and a higher heat release rate be used only in tightly fitting garments.<ref name="SC-6-91" /> | ||
[[File:fse-childrens-sleepwear-flammability-v3.svg|thumb|upright=1.5|alt=Side-by-side outline of a child in a loose nightgown with air on both sides of the fabric and a child in snug pyjamas|Loose and snug sleepwear: a loose gown has more fabric, touches ignition sources more easily and has air on both sides of the fabric, which speeds up flame spread | [[File:fse-childrens-sleepwear-flammability-v3.svg|thumb|upright=1.5|alt=Side-by-side outline of a child in a loose nightgown with air on both sides of the fabric and a child in snug pyjamas|Loose and snug sleepwear: a loose gown has more fabric, touches ignition sources more easily and has air on both sides of the fabric, which speeds up flame spread.]] | ||
Thermoplastic garments have their own failure mode. A nylon or polyester garment that does not itself ignite may become limp, shrink and stick to the skin, and cause a [[burn injury]] without burning.<ref name="SC-6-83" /> When shrinkage brings fabric into contact with the skin, the insulating air layer disappears and much more heat reaches the skin.<ref name="SC-6-84">Stull and Chines (2008), p. 6-84.</ref> Blends behave differently again: polyester/cotton blends burn more like 100 % cotton than like 100 % polyester.<ref name="SC-6-83" /> | Thermoplastic garments have their own failure mode. A nylon or polyester garment that does not itself ignite may become limp, shrink and stick to the skin, and cause a [[burn injury]] without burning.<ref name="SC-6-83" /> When shrinkage brings fabric into contact with the skin, the insulating air layer disappears and much more heat reaches the skin.<ref name="SC-6-84">Stull and Chines (2008), p. 6-84.</ref> Blends behave differently again: polyester/cotton blends burn more like 100 % cotton than like 100 % polyester.<ref name="SC-6-83" /> | ||
| Line 63: | Line 63: | ||
The problem has not been solved for older adults. From 1983 through 1985, clothing ignition caused roughly one of every 20 fire deaths overall, but one of every eight fire deaths of people aged 65 and over.<ref name="SC-6-86" /> Because people aged 65 and over also have twice the fire death rate of the whole population, their death rate from clothing ignition fires is five times the overall rate.<ref name="SC-6-86" /> Gamache (2008) listed advocacy for flame-resistant sleepwear, together with home sprinklers and fire-safe cigarettes, as a priority in reducing fire deaths and injuries among older adults.<ref name="GA-5-69">Gamache (2008), p. 5-69.</ref> | The problem has not been solved for older adults. From 1983 through 1985, clothing ignition caused roughly one of every 20 fire deaths overall, but one of every eight fire deaths of people aged 65 and over.<ref name="SC-6-86" /> Because people aged 65 and over also have twice the fire death rate of the whole population, their death rate from clothing ignition fires is five times the overall rate.<ref name="SC-6-86" /> Gamache (2008) listed advocacy for flame-resistant sleepwear, together with home sprinklers and fire-safe cigarettes, as a priority in reducing fire deaths and injuries among older adults.<ref name="GA-5-69">Gamache (2008), p. 5-69.</ref> | ||
[[File:fse-childrens-sleepwear-flammability-v4.svg|thumb|upright=1.5|alt=Bar chart: clothing ignition caused 5 percent of all US fire deaths and 12.5 percent of fire deaths of people aged 65 and over, 1983 to 1985|Share of United States fire deaths caused by clothing ignition, 1983–1985: about one in 20 overall and one in eight for people aged 65 and over | [[File:fse-childrens-sleepwear-flammability-v4.svg|thumb|upright=1.5|alt=Bar chart: clothing ignition caused 5 percent of all US fire deaths and 12.5 percent of fire deaths of people aged 65 and over, 1983 to 1985|Share of United States fire deaths caused by clothing ignition, 1983–1985: about one in 20 overall and one in eight for people aged 65 and over.]] | ||
== Snug-fit revision and limitations == | == Snug-fit revision and limitations == | ||
Revision as of 08:25, 8 November 2026
Children's sleepwear flammability is the tendency of nightgowns, pyjamas, robes and similar garments worn by children to ignite and burn, and the set of United States federal flammability standards written to limit it. The standards were promulgated for sizes 0 through 6X in 1971 and for sizes 7 through 14 three years later. The 2008 edition of the Fire Protection Handbook lists them as 16 CFR Parts 1615 and 1616.[1][2] The test described for these standards exposes a vertical fabric specimen at its lower edge to a small gas flame for 3 s and limits the resulting char length.[3] This test is much more restrictive than the general test for clothing fabrics, which only excludes inordinately flammable fabrics.[3][4]
Manufacturers met it by moving from cotton to mainly thermoplastic and flame-retardant fabrics. The 2008 handbook reports a significant fall in incidents in which nightwear was the first item ignited. It says annual burn deaths of children under 15 from clothing ignition had dropped to five or fewer.[5][1] A later change allowed untreated cotton garments that pass a test for snug fit. That change raised new concerns about the risk to small children.[5]
Definition and scope
The term covers both a fire property and a regulation. As a property, it is the textile flammability of garments worn for sleeping, which depends on the fibre, the fabric and the cut of the garment.[1] As a regulation, it refers to the Consumer Product Safety Commission standards for the flammability of children's sleepwear. The handbook lists them as Part 1615 for sizes 0 through 6X (designated FF 3-71) and Part 1616 for sizes 7 through 14 (FF 5-74).[2] The Commission also issues flammability rules for carpets, rugs, mattresses and mattress pads.[6]
Sleepwear is part of a wider problem of clothing fires. In United States nonconfined structure fires in 1999–2003, clothing or wearing apparel was the first item ignited in about 14,100 fires a year. These fires caused about 190 civilian deaths and 720 injuries a year.[7] The handbook tables imply about 13 deaths per 1,000 fires in each period, although the 1994–1998 table covers all reported structure fires and the 1999–2003 table covers nonconfined fires only.[7] All data and requirements in this article describe United States practice as reported in the 2008 edition of the Fire Protection Handbook.
Origins of the standard
The United States Congress passed the Flammable Fabrics Act in 1953 after a series of serious fires involving rayon-pile fabric made into children's cowboy chaps and sweaters.[1] The 2008 handbook describes apparel sold under the Act as subject to the Commission's Standard for the Flammability of Clothing Textiles, designated 16 CFR Part 1610. That test excluded the rayon-pile fabrics and other extremely flammable fabrics, such as very high-pile cotton flannels, stiffened nylon nets and very light fabrics.[1] It was not designed to separate ordinary fabrics. Pile fabrics such as cotton flannel made into gowns, robes and pajamas passed it easily, yet gave high burn injury estimates on an instrumented mannequin.[4]
Several studies showed that young and old people needed more protection. In a study of 463 fire deaths in the State of Maryland from 1972 through 1977, clothing ignitions caused 5.5 % of the deaths, or about 25 people.[1] Of the victims in that study, 21.6 % were 9 years old or younger and 20.5 % were 60 years old or older.[1] The study linked the high share of victims at both ends of the age range to their inability to cope quickly with a fire and their lower tolerance of toxic combustion products.[1]
Many victims of garment fires were wearing sleepwear when the fire started.[1] In the United States data discussed by Gamache (2008), preschool children and older adults were two main high-risk populations for fire deaths.[8] For the 1999–2002 period, children under 5 were 74 % more likely to die in a home fire than the average person, and adults aged 65 and over were roughly twice as likely.[8] Purser (2002) describes children and older people as especially vulnerable to burns. In that source, the estimated 50 % survival threshold is a burn covering 20 % of body surface for an older person, compared with 50 % for a young adult.[9]
A children's sleepwear standard was therefore promulgated for sizes 0 through 6X in 1971, followed three years later by a standard for sizes 7 through 14.[1] When it was introduced, the standard strained the state of the art. Thermoplastic and flame-retardant garments that passed this rather severe test were nevertheless soon produced.[1]
Test method
As described in the 2008 edition of the Fire Protection Handbook, the test for Parts 1615 and 1616 suspends fabric samples vertically in a cabinet and applies a test flame along the bottom edge.[3] The cabinet has ventilation ports, a guided specimen holder and a burner below the specimen.[10] The samples are 254 mm (10 in.) long. Their width is printed as 3 in. (89 mm), although 89 mm corresponds to 3.5 in.[3]
The barrel of the burner sits 19.1 mm (3/4 in.) below the lower edge of the sample, and the flame is adjusted to extend 38.1 mm (1 1/2 in.). The sample is exposed for 3 s.[3] Edge ignition follows the reasoning of the committee that drafted the former NFPA 702 apparel test, which concluded that the lower edge of a fabric should be easier to ignite than its surface.[4]
The result is expressed as char length. This is the distance from the lower edge of the fabric to the end of the void or tear in the charred, burned or damaged area.[3] The tear is made by attaching weights near one lower corner and lifting the sample by the opposite corner.[3] A fabric passes if the average char length of five specimens does not exceed 178 mm (7 in.) and no single specimen reaches a char length of 254 mm (10 in.).[3]
The test is severe because of its geometry. Fabrics generally burn faster when vertical than when horizontal, and an edge ignites much more easily than a surface because the flame reaches both sides.[11] Upward flame spread is fast because the flame preheats the material above the burning zone.[12] Garments are also thin: Quintiere (2002b) notes that, unlike most solids, items such as paper, garments and draperies behave as thermally thin materials during flame spread.[13]
| Feature | 16 CFR Part 1610 (clothing textiles) | 16 CFR Parts 1615 and 1616 (children's sleepwear) |
|---|---|---|
| Specimen orientation | 45 degrees | Vertical |
| Flame | 16 mm butane | 38 mm butane |
| Part of fabric exposed | Fabric face | Cut edge |
| Exposure time | 1 s | 3 s |
| Measurement | Rate of flame spread | Char length |
The general clothing test of Part 1610 is gentler. It touches the face of a specimen held at 45 degrees with a 15.9 mm (5/8 in.) flame for 1 s. The fabric is classified by the time the flame takes to spread 127 mm (5 in.).[4] A further method, ASTM D6545, Standard Test Method for Flammability of Textiles Used in Children's Sleepwear, appears among the ASTM fabric fire test standards listed by Hirschler (2008a).[14]
Fabrics and garment design
The standard changed the materials of children's nightwear. Garments moved from cotton to primarily thermoplastic fabrics, at no additional cost to the garment.[5] With some exceptions, many thermoplastics can be considered relatively safe against small-flame ignition compared with cellulosic fibres, when they are worn as single-layer apparel.[5] Modacrylic fibre is used for fire-retardant sleepwear. It has low heat conductivity, is weaker than acrylic, recovers well from stretching, is extremely sensitive to heat and is inherently flame retardant, so that it extinguishes itself.[5]
Other garments passed by using a flame retardant finish or fibre. Such treatments can be durable or nondurable, and normal laundering and dry cleaning may reduce their effect.[11] Concern that some flame retardants may be skin irritants or carcinogens, or too expensive, can deter wider use.[15] A treatment that protects against small flames also does not necessarily give resistance to smouldering ignition by a cigarette.[1]
The cut of a garment strongly affects its hazard. A full-length gown containing several yards of flammable fabric can be quite hazardous, whereas a tightly fitting garment of the same material might be far less dangerous.[1] The gown offers more fuel, and its size and loose shape make contact with ignition sources more likely, often without the wearer noticing. Flared skirts, large bows and full-sleeved kimonos are other easily ignitable designs.[1]
Oxygen available on both sides of a loosely fitting garment accelerates flame spread. This principle underlies the later snug-fit change to the requirements.[1] Braun and co-workers, as cited by Stull and Chines (2008), had earlier suggested that fabrics with short ignition times and a higher heat release rate be used only in tightly fitting garments.[16]
Thermoplastic garments have their own failure mode. A nylon or polyester garment that does not itself ignite may become limp, shrink and stick to the skin, and cause a burn injury without burning.[5] When shrinkage brings fabric into contact with the skin, the insulating air layer disappears and much more heat reaches the skin.[17] Blends behave differently again: polyester/cotton blends burn more like 100 % cotton than like 100 % polyester.[5]
Effectiveness
Stull and Chines (2008) describe the results of the standard as unexpectedly beneficial.[1] Incidents in which children's nightwear was the first item ignited were significantly reduced after the standard was introduced.[5] The handbook reports that annual burn deaths among children under 15 due to ignition of any type of clothing had dropped to five or fewer by the time it was published.[1] The handbook sums up the sleepwear standard as one that greatly reduced the incidence of accidents but restricted the choice of fabrics.[16]
Other chapters of the handbook use the standard as an example of engineered fire prevention. In juvenile firesetting programmes, sleepwear and bedding with flame-retardant fabrics are listed alongside child-resistant lighters and residential sprinklers.[18] Behrman (2000), as cited in Kirtley (2008a), lists flame-retardant children's sleepwear alongside child restraints and child-resistant medicine caps as examples of public policies that together save thousands of children's lives each year.[19] Bush (2008) expects stringent flammability standards of the kind the Commission issued for children's sleepwear and mattresses to give long-term fire safety benefits.[20]
The problem has not been solved for older adults. From 1983 through 1985, clothing ignition caused roughly one of every 20 fire deaths overall, but one of every eight fire deaths of people aged 65 and over.[1] Because people aged 65 and over also have twice the fire death rate of the whole population, their death rate from clothing ignition fires is five times the overall rate.[1] Gamache (2008) listed advocacy for flame-resistant sleepwear, together with home sprinklers and fire-safe cigarettes, as a priority in reducing fire deaths and injuries among older adults.[21]
Snug-fit revision and limitations
The standard was later revised to allow untreated cotton sleepwear for children if it passes a test for snug fit when sold. In the handbook's words, this has "reraised concerns" about the risks to small children.[5] The handbook adds that no evidence of a renewed problem had surfaced.[1] It also warns that there is no guarantee that a garment sold as snug will still be snug after many wearings, washings and hand-me-downs.[1]
The handbook is not consistent about the legal status of the test. It describes the snug-fit change as a revision of the standard.[5] Elsewhere it states that the test "is no longer required for U.S. children's sleepwear" and that the sleepwear standard "has been withdrawn".[3][16] The 2008 handbook therefore leaves the status of the test after the snug-fit revision unclear.
The test has the limits of all small-flame tests. It measures char length under one exposure and does not measure heat release.[3] Burning behaviour found in small-scale tests may mislead when large fires or strong radiation sources are involved, and fabrics considered flame retardant may then burn readily.[11] Flame-retardant effects may also be lost through laundering.[11] Finally, flame spread rates measured on the remains of garments from real fires did not correlate with the size of the victims' burns. Ranking apparel hazard with laboratory tests is therefore difficult.[16]
See also
Notes
- ↑ 1.00 1.01 1.02 1.03 1.04 1.05 1.06 1.07 1.08 1.09 1.10 1.11 1.12 1.13 1.14 1.15 1.16 1.17 1.18 1.19 1.20 Stull and Chines (2008), p. 6-86.
- ↑ 2.0 2.1 Stull and Chines (2008), p. 6-99.
- ↑ 3.00 3.01 3.02 3.03 3.04 3.05 3.06 3.07 3.08 3.09 3.10 Stull and Chines (2008), p. 6-90.
- ↑ 4.0 4.1 4.2 4.3 Stull and Chines (2008), p. 6-89.
- ↑ 5.00 5.01 5.02 5.03 5.04 5.05 5.06 5.07 5.08 5.09 Stull and Chines (2008), p. 6-83.
- ↑ Benedetti and Colonna (2008), p. 6-228.
- ↑ 7.0 7.1 Stull and Chines (2008), p. 6-78.
- ↑ 8.0 8.1 Gamache (2008), p. 5-63.
- ↑ Purser (2002), p. 2-128.
- ↑ Stull and Chines (2008), p. 6-92.
- ↑ 11.0 11.1 11.2 11.3 Stull and Chines (2008), p. 6-81.
- ↑ Van Rossum (2027), §4.3.
- ↑ Quintiere (2002b), p. 2-249.
- ↑ Hirschler (2008a), p. 6-59.
- ↑ Stull and Chines (2008), p. 6-85.
- ↑ 16.0 16.1 16.2 16.3 Stull and Chines (2008), p. 6-91.
- ↑ Stull and Chines (2008), p. 6-84.
- ↑ Schwartzman (2008), p. 5-97.
- ↑ Behrman (2000), as cited in Kirtley (2008a), p. 12-310.
- ↑ Bush (2008), p. 20-42.
- ↑ Gamache (2008), p. 5-69.
References
- Benedetti, R. P., & Colonna, G. R. (2008). Polymeric materials. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-209–6-231). National Fire Protection Association.
- Bush, K. (2008). Apartment buildings. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 20-37–20-47). National Fire Protection Association.
- Gamache, S. (2008). Reaching high-risk groups. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 5-63–5-85). National Fire Protection Association.
- Hirschler, M. M. (2008a). Concepts and protocols of fire testing. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-35–6-60). National Fire Protection Association.
- Kirtley, E. (2008a). Community risk reduction. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 12-309–12-315). National Fire Protection Association.
- Purser, D. A. (2002). Toxicity assessment of combustion products. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-83–2-171). National Fire Protection Association; Society of Fire Protection Engineers.
- Quintiere, J. G. (2002b). Surface flame spread. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-246–2-257). National Fire Protection Association; Society of Fire Protection Engineers.
- Schwartzman, P. (2008). Juvenile firesetting. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 5-87–5-102). National Fire Protection Association.
- Stull, J. O., & Chines, S. A. (2008). Fibers and textiles. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-75–6-102). National Fire Protection Association.
- Van Rossum, E. (2027). Introduction to Fire Safety Engineering. Fire Safety Academy.