== Use in laboratories ==
== Use in laboratories ==
The [[chemical laboratory]] is the occupancy in which the handbook treats cabinets most fully. Designers are expected to plan the location of flammable storage cabinets together with the laboratory hoods, spill containment, means of egress and emergency showers.<ref name="Anderson-9-158">Anderson (2008a), p. 9-158.</ref> The classes of liquid in NFPA 45 are the same as in NFPA 30 and essentially the same as those of the US Occupational Safety and Health Administration (OSHA).<ref name="Anderson-9-163" /> Storage cabinets help to keep a laboratory fire from spreading to the products inside them.<ref name="Anderson-9-163" />
The [[chemical laboratory]] is the occupancy in which the handbook treats cabinets most fully. Designers are expected to plan the location of flammable storage cabinets together with the laboratory hoods, spill containment, means of egress and emergency showers.<ref name="Anderson-9-158">Anderson (2008a), p. 9-158.</ref> The classes of liquid in NFPA 45 are the same as in NFPA 30 and essentially the same as those of the US Occupational Safety and Health Administration (OSHA).<ref name="Anderson-9-163" /> Storage cabinets help to keep a laboratory fire from spreading to the products inside them.<ref name="Anderson-9-163" />
[[File:fse-flammable-liquid-storage-cabinet-v4.jpg|thumb|upright=1.5|alt=Yellow metal flammable liquid storage cabinet with warning label standing in a laboratory|Metal flammable liquid storage cabinet in a laboratory. Based on Anderson (2008a), p. 9-158.]]


NFPA 45 (2004 edition), as reproduced by Anderson (2008a), limits the quantity of liquid in a sprinklered laboratory unit in two ways. A quantity is allowed for every 9.3 m² (100 ft²) of floor area, and a maximum applies to the whole unit, whatever its size.<ref name="Anderson-9-164">Anderson (2008a), p. 9-164.</ref> Both values depend on the fire hazard class of the laboratory, from A (high) to D (minimal), and on the class of liquid.<ref name="Anderson-9-164" /> The table gives one pair of values that excludes the liquid kept in storage cabinets or [[safety can]]s and one pair that includes it. The second pair is about twice the first, so cabinets and safety cans roughly double what a laboratory may hold.<ref name="Anderson-9-164" />
NFPA 45 (2004 edition), as reproduced by Anderson (2008a), limits the quantity of liquid in a sprinklered laboratory unit in two ways. A quantity is allowed for every 9.3 m² (100 ft²) of floor area, and a maximum applies to the whole unit, whatever its size.<ref name="Anderson-9-164">Anderson (2008a), p. 9-164.</ref> Both values depend on the fire hazard class of the laboratory, from A (high) to D (minimal), and on the class of liquid.<ref name="Anderson-9-164" /> The table gives one pair of values that excludes the liquid kept in storage cabinets or [[safety can]]s and one pair that includes it. The second pair is about twice the first, so cabinets and safety cans roughly double what a laboratory may hold.<ref name="Anderson-9-164" />

Revision as of 08:18, 8 November 2026

A flammable liquid storage cabinet is a specially designed cabinet for keeping a limited quantity of flammable and combustible liquids in their containers inside a building.[1] In the United States, NFPA 30, the Flammable and Combustible Liquids Code, limits such a cabinet to 454 L (120 gal) of Class I, II and IIIA liquids. This is the limit as summarised in the Fire Protection Handbook (2008).[1] The typical cabinet described there has a double steel wall with an air space, a latched door, a raised sill that holds spilled liquid, and a warning label.[1] Its purpose is to keep a fire in the room from reaching the liquids stored inside and to contain small leaks.[2][1]

Cabinets appear in US codes and handbook guidance for laboratories, construction sites, dipping and coating processes, aerosol storage and other occupancies.[3][4] The laboratory standard NFPA 45 (2004 edition, as described in the 2008 handbook) lets more liquid be kept in a laboratory unit when part of it is in cabinets or safety cans.[2] The limits quoted in this article come from summaries of the NFPA codes of around 2000 to 2008 in the handbook and in a report of the US Nuclear Regulatory Commission. They are therefore historical US values, not current or universal requirements.

Construction and marking

According to Ordile (2008), cabinets for flammable liquids are typically made of No. 18 gauge sheet steel. The wall is double, with an air space of 38 mm (1½ in.) between the two sheets.[1] Wooden cabinets are also permitted when they are built to the requirements of NFPA 30.[1] The bibliography of Ordile's chapter lists a 1993 report of the US Department of Energy on the development of wooden flammable liquid storage cabinets for chemical laboratories.[5]

The door should have a three-point latch. The sill is raised at least 51 mm (2 in.) above the bottom of the cabinet, so that the cabinet floor forms a shallow tray that keeps spilled liquid inside.[1] The cabinet should be marked in conspicuous lettering with the warning "FLAMMABLE" followed by "KEEP FIRE AWAY".[1] McDaniel (2008) describes the cabinets for small quantities of liquid in libraries and museums as approved and self-closing.[6]

The handbook does not quantify the protection that the double wall gives, and it gives no test method, temperature limit or duration for cabinets.[1]

Capacity limits

As described in the 2008 handbook, the cabinet limit in NFPA 30 applies to Class I, Class II and Class IIIA liquids, the classes with a flash point below 93 °C (200 °F).[1][2] The classes themselves are explained in Flammable and combustible liquid classification. NUREG-1805, a 2004 report of the US Nuclear Regulatory Commission, adds a sub-limit without naming the code edition. Of the total of 454 L (120 gal) in one cabinet, no more than 227 L (60 gal) may be Class I and Class II liquids.[7] The reference list of that appendix section cites the 2000 edition of NFPA 30 and the 1997 Flammable and Combustible Liquids Code Handbook.[8] The same report notes that most commercially available approved cabinets hold 227 L (60 gal) or less.[7]

Other NFPA documents add limits on the number of cabinets. Katunar (2008) summarises NFPA 34, the standard for dipping and coating processes, for liquids of Class I, II and IIIA in listed cabinets.[3] In that summary, which names no edition of NFPA 34, a process area may hold one cabinet with a total of 454 L (120 gal). A single fire area may hold 360 gal in cabinets in total.[3] In an industrial occupancy, each group of cabinets may hold 360 gal if the groups are at least 30 m (100 ft) apart. A single group may hold 720 gal (2,700 L) if the building has an approved automatic sprinkler system.[3] The handbook converts 360 gal once as 1,350 L and once as 1,365 L; the exact conversion is 1,363 L.[3]

On construction sites, Davis (2008a) recommends approved flammable liquid storage cabinets, or other acceptable structures, for any quantity above 95 L (25 gal). He refers to Section 4.3 of NFPA 30 for the maximum quantities in cabinets.[4] Stores of more than 227 L (60 gal) of Class I and Class II liquids should be kept at least 15 m (50 ft) from the building under construction.[4]

Venting and contents

As described by Anderson (2008a), venting of a cabinet was not mandatory. Neither NFPA 30 nor NFPA 45, the standard for laboratories using chemicals, required it, and both allowed venting where it was judged necessary or desirable.[2] The handbook gives no rule for how a vent should be arranged.

What goes into a cabinet matters as much as the cabinet itself. Anderson (2008a) states that products stored together in a cabinet must be compatible, and that incompatible materials must be segregated in all storage.[2] The liquids should be in approved containers within the cabinets.[2] Container sizes are limited separately by NFPA 30, according to container type and liquid class.[1] Products that need refrigeration need a refrigerator approved for that purpose and hazard rating.[2]

Cabinets are also used for products that are not liquids. Fredrickson (2008) summarises the limits for aerosol products in assembly, business, educational, industrial and institutional occupancies. A single fire area there may hold up to 454 kg (1,000 lb) of Level 2 and 227 kg (500 lb) of Level 3 aerosol products. Larger amounts go into separate inside storage areas or flammable liquid cabinets.[9]

J. Moore (2008) recommends cabinets or a specially protected room for smaller quantities of flammable aerosols in storage occupancies.[10] He cites a 1982 fire in a distribution warehouse in Falls Township, Pennsylvania. There, rocketing aerosol cans overwhelmed the sprinklers and the 111,500 m² (1.2 million ft²) building was destroyed.[10]

Use in laboratories

The chemical laboratory is the occupancy in which the handbook treats cabinets most fully. Designers are expected to plan the location of flammable storage cabinets together with the laboratory hoods, spill containment, means of egress and emergency showers.[11] The classes of liquid in NFPA 45 are the same as in NFPA 30 and essentially the same as those of the US Occupational Safety and Health Administration (OSHA).[2] Storage cabinets help to keep a laboratory fire from spreading to the products inside them.[2]

Yellow metal flammable liquid storage cabinet with warning label standing in a laboratory
Metal flammable liquid storage cabinet in a laboratory. Based on Anderson (2008a), p. 9-158.

NFPA 45 (2004 edition), as reproduced by Anderson (2008a), limits the quantity of liquid in a sprinklered laboratory unit in two ways. A quantity is allowed for every 9.3 m² (100 ft²) of floor area, and a maximum applies to the whole unit, whatever its size.[12] Both values depend on the fire hazard class of the laboratory, from A (high) to D (minimal), and on the class of liquid.[12] The table gives one pair of values that excludes the liquid kept in storage cabinets or safety cans and one pair that includes it. The second pair is about twice the first, so cabinets and safety cans roughly double what a laboratory may hold.[12]

The allowance for the whole unit follows from the smaller of the two limits: Qmax=min⁡(qA9.3,Qunit)

Symbols
Symbol Description Unit
Qmax maximum quantity of the liquid class in the laboratory unit L
q permitted quantity per 9.3 m² (100 ft²) of laboratory unit L
A floor area of the laboratory unit m²
Qunit maximum quantity per laboratory unit, regardless of size L

The quantities per 9.3 m² serve only to calculate the total. They do not mean that the liquid has to be spread over the floor area.[12]

Class I liquids in sprinklered laboratory units, NFPA 45 (2004 edition, Table 10.1.1), selected rows
Laboratory fire hazard class Excluding cabinets and safety cans: per 9.3 m² per unit Including cabinets and safety cans: per 9.3 m² per unit
A (high) 38 L (10 gal) 2,270 L (600 gal) 76 L (20 gal) 4,540 L (1,200 gal)
B (moderate) 20 L (5 gal) 1,136 L (300 gal) 38 L (10 gal) 2,270 L (600 gal)
C (low) 7.5 L (2 gal) 570 L (150 gal) 15 L (4 gal) 1,136 L (300 gal)
D (minimal) 4 L (1 gal) 284 L (75 gal) 7.5 L (2 gal) 570 L (150 gal)

The values follow Anderson (2008a), where the Class I row also covers liquefied flammable gases.[12]

Worked example. A Class B laboratory unit has a floor area of 186 m² (2,000 ft²), or 20 units of 9.3 m². Outside cabinets and safety cans, it may hold 20 L × 20 = 400 L of Class I liquid, well below the unit maximum of 1,136 L.[12] Including cabinets and safety cans, it may hold 38 L × 20 = 760 L.

If the unit holds the full 760 L, at least 360 L of it must be in cabinets or safety cans. If all of that were kept in cabinets, and the per-cabinet sub-limit of 227 L of Class I and II liquid quoted in NUREG-1805 applied, 360/227 = 1.6 would round up to two cabinets.[7] No source in the folder says which cabinet limit applies inside an NFPA 45 laboratory. For Class I, II and IIIA liquids together, the same unit may hold 760 L outside cabinets and 1,520 L in total.[12] The example combines a 2004 laboratory standard with a cabinet limit of uncertain edition and only illustrates the method.

The 2004 edition of NFPA 45, as described by Anderson (2008a), set no density limit for each 9.3 m². Part of the reason is that the chemicals are often in a cabinet, which may hold more than the quantity allowed for 9.3 m².[13] The committee also expected that a density rule would lead to schemes to split up the floor area. Anderson adds that NFPA codes are minimum requirements and not always best practice.[13] Where a laboratory needs more liquid than these limits allow, the extra storage is placed outside the laboratory unit, in a liquid storage area or room that meets NFPA 30.[12]

Other occupancies

The same idea of keeping small working quantities in a cabinet appears in several other handbook chapters. In semiconductor manufacturing, flammable liquids that are not in use should be kept in listed flammable liquid storage cabinets, whatever their container.[14] In libraries and museums, liquids should be stored where possible in fire-resistant structures isolated from the building. Where that is not feasible, small quantities may be kept in approved, self-closing cabinets.[6] Only the quantity needed for one 8-hour shift should then be outside the cabinet, and it should stay in safety cans until it is used.[6]

Ordile (2008) places cabinets within the wider range of NFPA 30 storage options. Containers such as bottles and drums can be stored in flammable liquid storage cabinets, inside liquid storage rooms and warehouses, in yard areas or in hazardous material storage lockers.[15] Hazardous material storage lockers are movable, prefabricated storage buildings with spill containment. As described by Ordile (2008), NFPA 30 permitted them as inside liquid storage rooms if they were built with the fire resistance ratings it lists. It limited their gross floor area to 140 m² (1,500 ft²).[1] Inside rooms are limited in the quantity they may hold, whereas a liquid warehouse is not.[16]

Limits of the sources

The source folder does not contain NFPA 30, NFPA 45 or NFPA 34. All requirements in this article are second-hand summaries from the 2008 handbook and from NUREG-1805, which names no edition for its cabinet sub-limit.[7] The handbook chapters describe the 2004 edition of NFPA 45 and do not name the edition of NFPA 30 they follow for cabinets.[12][1] The sources give no fire test data for cabinets. They state no time for which a cabinet protects its contents, and no performance of wooden against steel cabinets.[1] The construction details above describe a typical cabinet, not a minimum specification.[1]

See also

Notes

  1. ↑ 1.00 1.01 1.02 1.03 1.04 1.05 1.06 1.07 1.08 1.09 1.10 1.11 1.12 1.13 1.14 Ordile (2008), p. 7-28.
  2. ↑ 2.0 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 Anderson (2008a), pp. 9-163–9-164.
  3. ↑ 3.0 3.1 3.2 3.3 3.4 Katunar (2008), p. 9-42.
  4. ↑ 4.0 4.1 4.2 Davis (2008a), p. 11-54.
  5. ↑ Ordile (2008), p. 7-33.
  6. ↑ 6.0 6.1 6.2 McDaniel (2008), p. 20-185.
  7. ↑ 7.0 7.1 7.2 7.3 Iqbal and Salley (2004), p. B-21.
  8. ↑ Iqbal and Salley (2004), p. B-23.
  9. ↑ Fredrickson (2008), p. 6-262.
  10. ↑ 10.0 10.1 J. Moore (2008), p. 20-160.
  11. ↑ Anderson (2008a), p. 9-158.
  12. ↑ 12.0 12.1 12.2 12.3 12.4 12.5 12.6 12.7 12.8 Anderson (2008a), p. 9-164.
  13. ↑ 13.0 13.1 Anderson (2008a), p. 9-165.
  14. ↑ DeGiorgio and Peterkin (2008), p. 9-126.
  15. ↑ Ordile (2008), pp. 7-32–7-33.
  16. ↑ Ordile (2008), p. 7-27.

References

  • Anderson, R. R. (2008a). Fire protection of laboratories using chemicals. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-157–9-166). National Fire Protection Association.
  • Davis, R. J. (2008a). Fire hazards of construction, alteration, and demolition of buildings. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 11-47–11-58). National Fire Protection Association.
  • DeGiorgio, V., & Peterkin, H. (2008). Semiconductor manufacturing. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-119–9-129). National Fire Protection Association.
  • Fredrickson, D. L. (2008). Manufacture and storage of aerosol products. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-257–6-267). National Fire Protection Association.
  • Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.
  • Katunar, J., III (2008). Dipping and coating processes. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-39–9-51). National Fire Protection Association.
  • McDaniel, D. L. (2008). Library and museum collections. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 20-179–20-202). National Fire Protection Association.
  • Moore, J. (2008). Storage occupancies. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 20-157–20-178). National Fire Protection Association.
  • Ordile, A. M. (2008). Storage of flammable and combustible liquids. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 7-15–7-33). National Fire Protection Association.