Summary

Plume mass flow against height above the fuel for a 1,000 kW fire (700 kW convective) in the open (k = 1), against a wall (k = 1/2) and in an interior corner (k = 1/4). Based on Milke and Klote (2008), p. 18-44.

Original illustration for Corner fire.

  • Source basis: Milke and Klote (2008), pp. 18-44–18-45
  • Alt text: Line chart of plume mass flow against height for a 1 MW fire: highest in the open, lower against a wall, lowest in a corner.