Summary
Constant-rate models for 208 L of gasoline: unconfined spill (about 56 MW for 121 s) and an assumed 4 m² bund (about 9.6 MW for about 700 s). Both release about 6.7 GJ. Actual fires grow and decay. Based on Gottuk and White (2002), pp. 2-313–2-314, and Budnick et al. (2008), p. 3-149.
Original illustration for Spill fire.
- Source basis: Gottuk and White (2002), p. 2-314; Budnick et al. (2008), p. 3-149; Iqbal and Salley (2004), p. 3-5 (large area: high HRR, short duration)
- Alt text: Two idealised rectangles of heat release rate against time: spill at 56 MW for 121 s and bunded pool at 9.6 MW for about 700 s.
Licensing
New drawing by Fire Safety Academy. © Fire Safety Academy.
File history
Click on a date/time to view the file as it appeared at that time.
| Date/Time | Thumbnail | Dimensions | User | Comment | |
|---|---|---|---|---|---|
| current | 08:06, 8 November 2026 | 1,200 × 840 (9 KB) | Lisa (talk | contribs) | Watermark: Fire Safety Academy logo icon, 70 px, 45 % opacity | |
| 07:41, 8 November 2026 | 1,200 × 750 (9 KB) | Lisa (talk | contribs) | Watermark: Fire Safety Academy logo icon, 70 px, 45 % opacity |
You cannot overwrite this file.
File usage
The following page uses this file: