The boiling point separates Class IA from Class IB. For mixtures, which have no single boiling point, the handbook states that most NFPA standards use the 10 percent point of a distillation to ASTM D86.<ref name="S202">Slye (2008), p. 6-202.</ref> The definitions in NUREG-1805 instead take the 20 percent evaporated point of the same test.<ref name="IS-B21">Iqbal and Salley (2004), p. B-21.</ref>
The boiling point separates Class IA from Class IB. For mixtures, which have no single boiling point, the handbook states that most NFPA standards use the 10 percent point of a distillation to ASTM D86.<ref name="S202">Slye (2008), p. 6-202.</ref> The definitions in NUREG-1805 instead take the 20 percent evaporated point of the same test.<ref name="IS-B21">Iqbal and Salley (2004), p. B-21.</ref>
[[File:fse-flammable-and-combustible-liquid-classification-v1.svg|thumb|upright=1.5|alt=Flash point scale with class bands IA/IB, IC, II, IIIA and IIIB at 22.8, 37.8, 60 and 93.3 degrees C, and a boiling point split for IA and IB.|NFPA 30 classes of flammable and combustible liquids by closed-cup flash point; below 22.8 °C the boiling point separates Class IA from IB. United States practice as described in 2008. Based on Slye (2008), p. 6-198.]]


NUREG-1805 lists examples drawn from the 2000 edition of NFPA 30. Ethyl ether, acetaldehyde, dimethyl sulfide and furan are given as Class IA, and ethyl alcohol, 92-octane [[gasoline]] and cyclohexane as Class IB.<ref name="IS-B17" /> Butyl ether is given as Class IC.<ref name="IS-B17" /> Kerosene (No. 1 fuel oil), diesel fuel oils, glacial acetic acid and Jet A fuel appear as Class II.<ref name="IS-B18">Iqbal and Salley (2004), p. B-18.</ref> A handbook chapter on service stations uses gasoline as its example of a Class I liquid and diesel fuel as its example of a Class II liquid.<ref name="R2133">Rivkin (2008a), p. 21-33.</ref>
NUREG-1805 lists examples drawn from the 2000 edition of NFPA 30. Ethyl ether, acetaldehyde, dimethyl sulfide and furan are given as Class IA, and ethyl alcohol, 92-octane [[gasoline]] and cyclohexane as Class IB.<ref name="IS-B17" /> Butyl ether is given as Class IC.<ref name="IS-B17" /> Kerosene (No. 1 fuel oil), diesel fuel oils, glacial acetic acid and Jet A fuel appear as Class II.<ref name="IS-B18">Iqbal and Salley (2004), p. B-18.</ref> A handbook chapter on service stations uses gasoline as its example of a Class I liquid and diesel fuel as its example of a Class II liquid.<ref name="R2133">Rivkin (2008a), p. 21-33.</ref>


Flash points of common liquids span a wide range. A table in NUREG-1805, taken from Benedetti (1997), runs from −43 °C for gasoline to 243 °C.<ref name="IS-B19">Benedetti (1997), as cited in Iqbal and Salley (2004), p. B-19.</ref> In that table, n-hexane has a flash point of −26 °C, acetone −16 °C, toluene 9 °C, methanol 11 °C and ethanol 12 °C.<ref name="IS-B19" /> Kerosene has 52 °C and diesel fuel 40 to 50 °C, both within Class II, while the jet fuel JP-5 has 66 °C and falls in Class IIIA.<ref name="IS-B19" /> SAE No. 10 lubricating oil, at 171 °C, is in Class IIIB.<ref name="IS-B19" />
Flash points of common liquids span a wide range. A table in NUREG-1805, taken from Benedetti (1997), runs from −43 °C for gasoline to 243 °C.<ref name="IS-B19">Benedetti (1997), as cited in Iqbal and Salley (2004), p. B-19.</ref> In that table, n-hexane has a flash point of −26 °C, acetone −16 °C, toluene 9 °C, methanol 11 °C and ethanol 12 °C.<ref name="IS-B19" /> Kerosene has 52 °C and diesel fuel 40 to 50 °C, both within Class II, while the jet fuel JP-5 has 66 °C and falls in Class IIIA.<ref name="IS-B19" /> SAE No. 10 lubricating oil, at 171 °C, is in Class IIIB.<ref name="IS-B19" />
[[File:fse-flammable-and-combustible-liquid-classification-v2.svg|thumb|upright=1.5|alt=Dot chart of flash points from gasoline at minus 43 degrees C to lubricating oil at 171 degrees C over shaded class bands.|Flash points of common liquids against the NFPA 30 class limits of 22.8, 37.8, 60 and 93.3 °C. Based on Benedetti (1997), as cited in Iqbal and Salley (2004), p. B-19.]]


=== Worked example ===
=== Worked example ===
Line 60: Line 62:


The result depends on the apparatus. Open-cup flash points are generally higher than closed-cup values for the same substance.<ref name="S201" /> Kanury reports that the differences between methods are neither small nor systematic.<ref name="K190" /> For kerosene, data from the ''International Critical Tables'' range from 52.8 °C in the Abel tester to 57.2 °C in the Pensky-Martens tester and 60.0 °C in the Cleveland open cup.<ref name="K191">Kanury (2002b), p. 2-191.</ref> On the NFPA 30 limits, the Abel and Pensky-Martens values place kerosene in Class II, while the Cleveland open-cup value would fall on the 60 °C boundary of Class IIIA.<ref name="S198" /> NFPA 30 bases its classes on the closed-cup flash point.<ref name="IS-B17" /><ref name="A9163" />
The result depends on the apparatus. Open-cup flash points are generally higher than closed-cup values for the same substance.<ref name="S201" /> Kanury reports that the differences between methods are neither small nor systematic.<ref name="K190" /> For kerosene, data from the ''International Critical Tables'' range from 52.8 °C in the Abel tester to 57.2 °C in the Pensky-Martens tester and 60.0 °C in the Cleveland open cup.<ref name="K191">Kanury (2002b), p. 2-191.</ref> On the NFPA 30 limits, the Abel and Pensky-Martens values place kerosene in Class II, while the Cleveland open-cup value would fall on the 60 °C boundary of Class IIIA.<ref name="S198" /> NFPA 30 bases its classes on the closed-cup flash point.<ref name="IS-B17" /><ref name="A9163" />
[[File:fse-flammable-and-combustible-liquid-classification-v3.svg|thumb|upright=1.5|alt=Bar chart of kerosene flash points by six test methods, 52.8 to 60.0 degrees C, with a line at the 60 degrees C class limit.|Flash point of kerosene measured with six different testers, from the International Critical Tables, with the 60 °C limit between Class II and IIIA. Based on Kanury (2002b), p. 2-191.]]


The flash point also varies with pressure, with the oxygen content of the atmosphere, with the purity of the product and with the skill of the operator.<ref name="S201" /> A flammable mixture can exist far below the stated flash point if the pressure is well below one atmosphere.<ref name="S201" /> NUREG-1805 notes that tabulated flash points are meaningful only for bulk liquids. A high flash point liquid in the form of a spray, froth or foam can be ignited by a very small flame.<ref name="IS-B19" />
The flash point also varies with pressure, with the oxygen content of the atmosphere, with the purity of the product and with the skill of the operator.<ref name="S201" /> A flammable mixture can exist far below the stated flash point if the pressure is well below one atmosphere.<ref name="S201" /> NUREG-1805 notes that tabulated flash points are meaningful only for bulk liquids. A high flash point liquid in the form of a spray, froth or foam can be ignited by a very small flame.<ref name="IS-B19" />
Line 65: Line 68:
== Use in regulation and design ==
== Use in regulation and design ==
The 2008 handbook shows the classes at work throughout United States practice. Under NFPA 30 (2003 edition), the largest glass container allowed is 0.5 L for Class IA, 1 L for Class IB, 5 L for Classes IC and II and 20 L for Class IIIA.<ref name="O728" /> Metal drums of up to 450 L and approved metal portable tanks of up to 3000 L are allowed for all these classes. Rigid plastic intermediate bulk containers and fibre drums are not permitted for Class I liquids.<ref name="O728" />
The 2008 handbook shows the classes at work throughout United States practice. Under NFPA 30 (2003 edition), the largest glass container allowed is 0.5 L for Class IA, 1 L for Class IB, 5 L for Classes IC and II and 20 L for Class IIIA.<ref name="O728" /> Metal drums of up to 450 L and approved metal portable tanks of up to 3000 L are allowed for all these classes. Rigid plastic intermediate bulk containers and fibre drums are not permitted for Class I liquids.<ref name="O728" />
[[File:fse-flammable-and-combustible-liquid-classification-v4.svg|thumb|upright=1.5|alt=Grouped bars of maximum container size for glass, metal and safety cans for Classes IA to IIIA, from 0.5 L to 20 L.|Maximum allowable container size by liquid class for glass, metal or approved plastic, and safety cans, United States, NFPA 30 (2003 edition). Based on Ordile (2008), p. 7-28.]]


Quantity limits follow the same logic. A [[flammable liquid storage cabinet]] may hold not more than 454 L (120 gal) of Class I, Class II and Class IIIA liquids.<ref name="O728" /> NUREG-1805 adds that not more than 227 L (60 gal) of this total may be Class I and Class II liquids.<ref name="IS-B21" /> For outdoor container storage, NFPA 30 (2003 edition) allows piles of 4160 L (1100 gal) of Class IA liquid but 83,300 L (22,000 gal) of Class III liquid. The distance to a property line falls from 15.2 m (50 ft) for Class I to 7.62 m (25 ft) for Class II and 3.05 m (10 ft) for Class III.<ref name="O729">Ordile (2008), p. 7-29.</ref> Tank vehicle loading racks should be at least 7.6 m (25 ft) from tanks when Class I liquids are handled and 4.6 m (15 ft) for Class II and Class III liquids.<ref name="O722" />
Quantity limits follow the same logic. A [[flammable liquid storage cabinet]] may hold not more than 454 L (120 gal) of Class I, Class II and Class IIIA liquids.<ref name="O728" /> NUREG-1805 adds that not more than 227 L (60 gal) of this total may be Class I and Class II liquids.<ref name="IS-B21" /> For outdoor container storage, NFPA 30 (2003 edition) allows piles of 4160 L (1100 gal) of Class IA liquid but 83,300 L (22,000 gal) of Class III liquid. The distance to a property line falls from 15.2 m (50 ft) for Class I to 7.62 m (25 ft) for Class II and 3.05 m (10 ft) for Class III.<ref name="O729">Ordile (2008), p. 7-29.</ref> Tank vehicle loading racks should be at least 7.6 m (25 ft) from tanks when Class I liquids are handled and 4.6 m (15 ft) for Class II and Class III liquids.<ref name="O722" />

Revision as of 08:00, 8 November 2026

Flammable and combustible liquid classification is the system that sorts liquids into hazard classes by their flash point. This is the lowest temperature at which a liquid gives off enough vapour to form an ignitable mixture with air. In the United States, NFPA 30, as described by Slye (2008), calls liquids with a flash point below 37.8 °C (100 °F) flammable (Class I). Liquids with a higher flash point are combustible (Class II and III).[1] Class I is subdivided by flash point and boiling point into IA, IB and IC, and Class III by flash point into IIIA and IIIB.[1]

The classification exists because the hazard of these liquids comes from their vapour, not from the liquid itself.[2] Under ordinary closed-cup test conditions, a liquid at its flash point has enough vapour for a momentary flash; well below it, the vapour is usually too lean to carry a flame.[3] The class then sets many practical rules in the codes that use it, such as the largest permitted container, the quantity allowed in a laboratory and the separation distance of a loading rack.[4][5][6] The class describes how easily a liquid ignites. It says little about how fiercely the liquid burns once a fire is established.[1]

Basis of the classification

Slye's handbook chapter calls the flash point the most commonly used means of judging the relative hazard of flammable and combustible liquids.[1] Other properties also affect the hazard, including the ignition temperature, the flammable range, the rate of evaporation, reactivity, density and the rate at which the vapour diffuses.[1] At atmospheric pressure, the flash point corresponds roughly to the lowest temperature at which the liquid's vapour pressure yields a mixture at the lower flammable limit.[7] Below that temperature its vapour is generally too lean for flame propagation under those conditions.

The NUREG-1805 fire dynamics tools of the U.S. Nuclear Regulatory Commission explain the two words in everyday terms. A flammable liquid produces vapour at normal room temperature in concentrations that a small spark or flame can ignite. A combustible liquid does not, unless it is heated to or above its flash point.[3] Once heated in this way, a combustible liquid can be just as dangerous as a flammable one, and some hydrocarbon fuels then burn as rapidly and release as much heat.[3]

The class boundaries follow from ordinary temperatures in buildings. The handbook explains that in most areas the indoor temperature could reach 37.8 °C (100 °F) at some time during the year, so all liquids with a lower flash point are placed in Class I.[1] In some areas the ambient temperature could exceed 37.8 °C, so only moderate heating would bring a liquid with a somewhat higher flash point to the point of ignition. An arbitrary band from 37.8 to 60 °C (100 to 140 °F) was therefore set for Class II.[1] Liquids with flash points at or above 60 °C form Class III.[1]

NFPA 30 also draws a line between liquids and gases, and between liquids and solids. A liquid is a fluid with a vapour pressure not exceeding 40 psia (2068 mm Hg) at 37.8 °C, which is 275.8 kPa.[1] A liquid must also be more fluid than 300 penetration asphalt.[1] Solids that melt should, once liquid, be treated like liquids with similar flash points.[8]

Classes in NFPA 30

The table summarises the classes as Slye gives them from NFPA 30. All flash points are closed-cup values, and the same limits appear in the handbook chapter on laboratories.[1][5] Each upper class starts at, not above, its lower limit.[1]

Classes of flammable and combustible liquids (United States, NFPA 30, as described by Slye, 2008)
Class Group Flash point Boiling point
IA Flammable below 22.8 °C (73 °F) below 37.8 °C (100 °F)
IB Flammable below 22.8 °C (73 °F) at or above 37.8 °C (100 °F)
IC Flammable at or above 22.8 °C and below 37.8 °C any
II Combustible at or above 37.8 °C and below 60 °C (140 °F) any
IIIA Combustible at or above 60 °C and below 93.3 °C (200 °F) any
IIIB Combustible at or above 93.3 °C (200 °F) any

The boiling point separates Class IA from Class IB. For mixtures, which have no single boiling point, the handbook states that most NFPA standards use the 10 percent point of a distillation to ASTM D86.[9] The definitions in NUREG-1805 instead take the 20 percent evaporated point of the same test.[10]

Flash point scale with class bands IA/IB, IC, II, IIIA and IIIB at 22.8, 37.8, 60 and 93.3 degrees C, and a boiling point split for IA and IB.
NFPA 30 classes of flammable and combustible liquids by closed-cup flash point; below 22.8 °C the boiling point separates Class IA from IB. United States practice as described in 2008. Based on Slye (2008), p. 6-198.

NUREG-1805 lists examples drawn from the 2000 edition of NFPA 30. Ethyl ether, acetaldehyde, dimethyl sulfide and furan are given as Class IA, and ethyl alcohol, 92-octane gasoline and cyclohexane as Class IB.[3] Butyl ether is given as Class IC.[3] Kerosene (No. 1 fuel oil), diesel fuel oils, glacial acetic acid and Jet A fuel appear as Class II.[11] A handbook chapter on service stations uses gasoline as its example of a Class I liquid and diesel fuel as its example of a Class II liquid.[12]

Flash points of common liquids span a wide range. A table in NUREG-1805, taken from Benedetti (1997), runs from −43 °C for gasoline to 243 °C.[13] In that table, n-hexane has a flash point of −26 °C, acetone −16 °C, toluene 9 °C, methanol 11 °C and ethanol 12 °C.[13] Kerosene has 52 °C and diesel fuel 40 to 50 °C, both within Class II, while the jet fuel JP-5 has 66 °C and falls in Class IIIA.[13] SAE No. 10 lubricating oil, at 171 °C, is in Class IIIB.[13]

Dot chart of flash points from gasoline at minus 43 degrees C to lubricating oil at 171 degrees C over shaded class bands.
Flash points of common liquids against the NFPA 30 class limits of 22.8, 37.8, 60 and 93.3 °C. Based on Benedetti (1997), as cited in Iqbal and Salley (2004), p. B-19.

Worked example

The class follows from two numbers, the closed-cup flash point and, for the lowest flash points, the boiling point. Table 6.12.1 of the handbook gives closed-cup flash points of −15 °F for n-hexane, 3 °F for acetone, 95 °F for turpentine, 104 °F for No. 10 mineral spirits and 202 °F for meta-para cresol.[14] Converted to SI units, these are −26.1, −16.1, 35.0, 40.0 and 94.4 °C.

n-Hexane and acetone both have flash points below 22.8 °C, so the boiling point decides between IA and IB. The handbook tables give normal boiling points of 68.7 °C for n-hexane and 56.5 °C for acetone.[15][16] Both are above 37.8 °C, so both liquids are Class IB. Turpentine, at 35.0 °C, lies between 22.8 and 37.8 °C and is Class IC. No. 10 mineral spirits, at 40.0 °C, lies just above the dividing line and is a Class II combustible liquid. Meta-para cresol, at 94.4 °C, is Class IIIB.

Diethyl ether shows the other branch. Its boiling point of 34.6 °C lies below 37.8 °C, which is consistent with its listing as a Class IA example in NUREG-1805.[16][3] A liquid on a boundary goes into the higher class. Normal butyl alcohol, with a closed-cup flash point of 100 °F (37.8 °C) in Table 6.12.1, therefore falls just inside Class II.[1][14]

Physical basis

In a closed container, the share of vapour in the space above the liquid equals the vapour pressure of the liquid divided by the total pressure.[8] Acetone at 37.8 °C has a vapour pressure of about 52 kPa, so at atmospheric pressure the vapour space holds about 52 percent acetone vapour.[8] This is far above the upper flammable limit of acetone, since its flammable range in air runs from 2.6 to 12.8 percent by volume.[9]

Storage tanks show how vapour pressure and class work together. According to Ordile, the vapour space of a tank holding a liquid with a vapour pressure above 28 kPa (4 psia), such as gasoline, is normally too rich to burn.[17] Above a liquid with a vapour pressure below about 14 kPa (2 psia), such as kerosene, it is normally too lean.[17] Ethyl and methyl alcohol and JP-4 jet fuel, with vapour pressures of about 14 to 28 kPa at 38 °C, present an unusual hazard because their vapour space is normally within the flammable range.[17]

Mixtures can move between classes as they evaporate. Slye describes gasoline mixed with enough carbon tetrachloride to have no flash point. In an open container the carbon tetrachloride evaporates faster, so the residue shows a progressively lower flash point.[18] Fractional evaporation tests measure the flash point after 10, 20, 40, 60 and 90 percent of a sample has evaporated. They show the class to use when appreciable evaporation is likely in service.[18]

The class matters for fire growth as well as for ignition. Liquids with vapour in the flammable range above the surface at the storage temperature have a rapid rate of flame propagation. Liquids stored below their flash point spread flame more slowly, because the fire must first heat the surface to form a flammable mixture.[18] Gottuk and White identify liquid temperature relative to flash point as a main factor in flame spread.[19] Liquid-controlled spread runs at about 1 to 12 cm/s and gas-phase spread at 130 to 220 cm/s.[19] In their JP-5 and JP-8 tests, the transition occurred near 18 °C above the closed-cup flash point.[20]

Measuring the flash point

In the SFPE Handbook, Kanury defines the flash point as the liquid temperature at which the vapour and air mixture just above the surface supports a momentary flash of flame from a small pilot.[21] The related fire point is the lowest temperature at which burning is sustained, for at least 5 seconds after a test flame is applied in the handbook definition.[7] For high flash point liquids, the fire point is typically reported as 5 to 15 °C above the flash point.[7]

Several standard testers are used. The handbook names the Tag closed tester (ASTM D56) and the Pensky-Martens closed tester (ASTM D93). The latter is specified for flash points above 93.3 °C and for some viscous or film-forming materials.[22] The open-cup methods ASTM D1310 and ASTM D92 (Cleveland) are sometimes used to grade flammable liquids in transportation.[22]

The result depends on the apparatus. Open-cup flash points are generally higher than closed-cup values for the same substance.[22] Kanury reports that the differences between methods are neither small nor systematic.[21] For kerosene, data from the International Critical Tables range from 52.8 °C in the Abel tester to 57.2 °C in the Pensky-Martens tester and 60.0 °C in the Cleveland open cup.[23] On the NFPA 30 limits, the Abel and Pensky-Martens values place kerosene in Class II, while the Cleveland open-cup value would fall on the 60 °C boundary of Class IIIA.[1] NFPA 30 bases its classes on the closed-cup flash point.[3][5]

Bar chart of kerosene flash points by six test methods, 52.8 to 60.0 degrees C, with a line at the 60 degrees C class limit.
Flash point of kerosene measured with six different testers, from the International Critical Tables, with the 60 °C limit between Class II and IIIA. Based on Kanury (2002b), p. 2-191.

The flash point also varies with pressure, with the oxygen content of the atmosphere, with the purity of the product and with the skill of the operator.[22] A flammable mixture can exist far below the stated flash point if the pressure is well below one atmosphere.[22] NUREG-1805 notes that tabulated flash points are meaningful only for bulk liquids. A high flash point liquid in the form of a spray, froth or foam can be ignited by a very small flame.[13]

Use in regulation and design

The 2008 handbook shows the classes at work throughout United States practice. Under NFPA 30 (2003 edition), the largest glass container allowed is 0.5 L for Class IA, 1 L for Class IB, 5 L for Classes IC and II and 20 L for Class IIIA.[4] Metal drums of up to 450 L and approved metal portable tanks of up to 3000 L are allowed for all these classes. Rigid plastic intermediate bulk containers and fibre drums are not permitted for Class I liquids.[4]

Grouped bars of maximum container size for glass, metal and safety cans for Classes IA to IIIA, from 0.5 L to 20 L.
Maximum allowable container size by liquid class for glass, metal or approved plastic, and safety cans, United States, NFPA 30 (2003 edition). Based on Ordile (2008), p. 7-28.

Quantity limits follow the same logic. A flammable liquid storage cabinet may hold not more than 454 L (120 gal) of Class I, Class II and Class IIIA liquids.[4] NUREG-1805 adds that not more than 227 L (60 gal) of this total may be Class I and Class II liquids.[10] For outdoor container storage, NFPA 30 (2003 edition) allows piles of 4160 L (1100 gal) of Class IA liquid but 83,300 L (22,000 gal) of Class III liquid. The distance to a property line falls from 15.2 m (50 ft) for Class I to 7.62 m (25 ft) for Class II and 3.05 m (10 ft) for Class III.[24] Tank vehicle loading racks should be at least 7.6 m (25 ft) from tanks when Class I liquids are handled and 4.6 m (15 ft) for Class II and Class III liquids.[6]

Many handling rules apply only to Class I liquids, or to other classes when they are heated. In Ordile's 2008 account, NFPA 30 requires normally closed vent devices for Class IA liquids, and flame arresters or pressure-vacuum vents for the storage of all Class I liquids.[25] Only inert gas should be used to transfer Class I liquids under pressure, while air is acceptable for Class II and III liquids unless they are heated above their flash point.[26] Bonding against static sparks is required when Class I liquids are loaded or unloaded. Special bonding is unnecessary with closed metal piping that prevents air exposure or for Class II and III transfers at ambient temperature.[26] Before switching a tank compartment from Class I to Class II or III, drain it to avoid a static spark in flammable vapour.[27]

Ventilation and electrical rules follow the same pattern. Storage tank buildings holding Class I liquids, or Class II and IIIA liquids above their flash points, must be ventilated to keep vapours at or below 25 percent of the lower flammable limit.[28] In dipping and coating processes, Katunar says electrical equipment should conform to National Electrical Code (NEC) rules for hazardous locations where Class I liquids are used, subject to a small-installation exception. The same applies where Class II or III liquids are used at or above their flash points.[29] This links the liquid class to hazardous area classification. Where vapour explosions may occur, Slye recommends explosion venting for rooms or buildings involving at least Class IA or unstable liquids.[30]

Other codes and regulations reuse the classes. NFPA 45 for laboratories uses the same classification as NFPA 30, which Anderson describes as essentially the same system used by the Occupational Safety and Health Administration (OSHA).[5] Severson's 2008 account says that the Environmental Protection Agency (EPA) treats liquid waste with a closed-cup flash point below 60 °C as ignitable, with exceptions for wine and latex paint.[31] Before a separate system was developed, NFPA 30 treated aerosol products as equivalent to Class IA liquids.[32]

The class also guides fire protection. Water without additives has a limited ability to extinguish fires in Class I liquids. Sprinklers and water spray are usually effective on liquids with flash points of 93.3 °C and higher.[33] In the SFPE Handbook, Scheffey lists NFPA 30 foam-sprinkler criteria for palletised Class IB, IC and II liquids in nonrelieving metal containers of 18.9 L or less. The ceiling application rates are 16.4 L/min/m² for cartoned and 12.3 L/min/m² for uncartoned packages.[34]

Other classification systems

Slye notes that other systems use different breakpoints between classes, rely on the open-cup tester or take solubility in water into account.[1] The international transport system places flammable liquids in Class 3. In Wright's 2008 account, these have a flash point of not more than 60 °C (140 °F).[35]

Wright also describes a U.S. and Canadian combustible-liquid transport class above 60 °C and below about 93.3 °C. In his account, U.S. shippers may also reclassify liquids with flash points above 38 °C as combustible liquids.[35] NUREG-1805 (2004) shows an older Department of Transportation table that split Class 3 into three divisions by flash point, at 0 °F and 73 °F.[36]

The NFPA 704 marking used on facilities rates flammability on a scale from 0 to 4 in the red quadrant of a diamond. Degree 3 covers liquids and solids that can be ignited under almost all ambient temperature conditions. Degree 2 covers materials that must be moderately heated before ignition can occur.[37] The 704 rating is a separate system from the NFPA 30 classes. Its diamond-shaped markings are used within facilities to alert people to the type and degree of hazard.[38]

Limits and common misconceptions

A low class number does not mean a liquid burns harder. Slye states that the flash point and the other factors that govern ignition have minimal influence on how a liquid burns once the fire has been burning for a short time.[1] In a pool fire, gasoline burns down at 150 to 300 mm of depth per hour and kerosene at 130 to 200 mm per hour, although their flash points differ by about 95 °C.[39][13] NUREG-1805 gives the example of a spill on ground heated by the sun to 35 °C. A Class I spill is then extremely hazardous. A Class II spill is dangerous only if a heat source can moderately warm it, and a Class III spill only if it is strongly heated.[11]

A higher class can give a false sense of security. Slye describes Stoddard solvent, a refined petroleum product with fire properties similar to kerosene. Users who believe it carries no fire hazard may neglect ordinary precautions. When heated above its flash point of about 37.8 °C, it produces vapour as flammable as that of gasoline at its flash point.[30] NUREG-1805 notes that mineral spirits and paint thinners are often blended to lie just above the dividing line between flammable and combustible liquids.[3]

Two further points cause confusion. The "Class I liquid" of NFPA 30 is not the same as a "Class I location" of the NEC. The NEC divides hazardous locations into three classes by the kind of material and into two divisions by the likelihood of a hazard, even though its definition of a flammable liquid matches Class I.[40] In addition, the flash point of a fuel mixture is not fixed. In JP-8 jet fuel tests reviewed by Gottuk and White, ignition delays of 3 to 460 s gave results consistent with a rise in flash point of about 10 °C.[20] They attribute such shifts in part to the loss of light ends from volatile mixtures.[41]

The scheme described here is United States practice as presented in the 2008 handbook, with tables from the 2000 and 2003 editions of NFPA 30. Other countries and later editions may use other limits, and Slye advises checking with local authorities for alternative systems.[1] Introduction to Fire Safety Engineering notes that a liquid fuel must first turn into a gas or a mist before it can burn, in a pool fire by evaporation.[42] This matches the handbook's view that the hazard of these liquids lies in their vapour.[2]

See also

Notes

  1. ↑ 1.00 1.01 1.02 1.03 1.04 1.05 1.06 1.07 1.08 1.09 1.10 1.11 1.12 1.13 1.14 1.15 1.16 Slye (2008), p. 6-198.
  2. ↑ 2.0 2.1 Slye (2008), p. 6-197.
  3. ↑ 3.0 3.1 3.2 3.3 3.4 3.5 3.6 3.7 Iqbal and Salley (2004), p. B-17.
  4. ↑ 4.0 4.1 4.2 4.3 Ordile (2008), p. 7-28.
  5. ↑ 5.0 5.1 5.2 5.3 Anderson (2008a), p. 9-163.
  6. ↑ 6.0 6.1 Ordile (2008), p. 7-22.
  7. ↑ 7.0 7.1 7.2 Slye (2008), p. 6-200.
  8. ↑ 8.0 8.1 8.2 Slye (2008), p. 6-199.
  9. ↑ 9.0 9.1 Slye (2008), p. 6-202.
  10. ↑ 10.0 10.1 Iqbal and Salley (2004), p. B-21.
  11. ↑ 11.0 11.1 Iqbal and Salley (2004), p. B-18.
  12. ↑ Rivkin (2008a), p. 21-33.
  13. ↑ 13.0 13.1 13.2 13.3 13.4 13.5 Benedetti (1997), as cited in Iqbal and Salley (2004), p. B-19.
  14. ↑ 14.0 14.1 Slye (2008), p. 6-203.
  15. ↑ Babrauskas (2008a), p. 6-271.
  16. ↑ 16.0 16.1 Babrauskas (2008a), p. 6-270.
  17. ↑ 17.0 17.1 17.2 Ordile (2008), p. 7-16.
  18. ↑ 18.0 18.1 18.2 Slye (2008), p. 6-205.
  19. ↑ 19.0 19.1 Gottuk and White (2002), p. 2-300.
  20. ↑ 20.0 20.1 Gottuk and White (2002), p. 2-304.
  21. ↑ 21.0 21.1 Kanury (2002b), p. 2-190.
  22. ↑ 22.0 22.1 22.2 22.3 22.4 Slye (2008), p. 6-201.
  23. ↑ Kanury (2002b), p. 2-191.
  24. ↑ Ordile (2008), p. 7-29.
  25. ↑ Ordile (2008), p. 7-18.
  26. ↑ 26.0 26.1 Ordile (2008), p. 7-30.
  27. ↑ Ordile (2008), p. 7-32.
  28. ↑ Ordile (2008), p. 7-25.
  29. ↑ Katunar (2008), p. 9-45.
  30. ↑ 30.0 30.1 Slye (2008), p. 6-207.
  31. ↑ Severson (2008), p. 7-60.
  32. ↑ Fredrickson (2008), p. 6-257.
  33. ↑ Frank (2008), p. 17-38.
  34. ↑ Scheffey (2002), p. 4-116.
  35. ↑ 35.0 35.1 C. J. Wright (2008a), p. 13-120.
  36. ↑ Iqbal and Salley (2004), p. B-22.
  37. ↑ C. J. Wright (2008a), p. 13-123.
  38. ↑ C. J. Wright (2008a), pp. 13-122–13-123.
  39. ↑ Slye (2008), p. 6-206.
  40. ↑ Milatovich (2008), p. 8-164.
  41. ↑ Gottuk and White (2002), p. 2-306.
  42. ↑ Van Rossum (2027), §4.1.

References

  • Anderson, R. R. (2008a). Fire protection of laboratories using chemicals. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-157–9-166). National Fire Protection Association.
  • Babrauskas, V. (2008a). Tables and charts. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-269–6-294). National Fire Protection Association.
  • Frank, J. A. (2008). Characteristics and hazards of water and water additives for fire suppression. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 17-31–17-43). National Fire Protection Association.
  • Fredrickson, D. L. (2008). Manufacture and storage of aerosol products. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-257–6-267). National Fire Protection Association.
  • Gottuk, D. T., & White, D. A. (2002). Liquid fuel fires. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-297–2-316). National Fire Protection Association; Society of Fire Protection Engineers.
  • Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.
  • Kanury, A. M. (2002b). Ignition of liquid fuels. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-188–2-199). National Fire Protection Association; Society of Fire Protection Engineers.
  • Katunar, J., III (2008). Dipping and coating processes. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-39–9-51). National Fire Protection Association.
  • Milatovich, R. M. (2008). Electrical systems and appliances. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 8-127–8-173). National Fire Protection Association.
  • Ordile, A. M. (2008). Storage of flammable and combustible liquids. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 7-15–7-33). National Fire Protection Association.
  • Rivkin, C. H. (2008a). Automotive and marine service station operations. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 21-29–21-40). National Fire Protection Association.
  • Scheffey, J. L. (2002). Foam agents and AFFF system design considerations. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 4-88–4-122). National Fire Protection Association; Society of Fire Protection Engineers.
  • Severson, P. R. (2008). Hazardous waste control. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 7-57–7-69). National Fire Protection Association.
  • Slye, O. M., Jr. (2008). Flammable and combustible liquids. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-197–6-208). National Fire Protection Association.
  • Van Rossum, E. (2027). Introduction to Fire Safety Engineering. Fire Safety Academy.
  • Wright, C. J. (2008a). Managing the response to hazardous material incidents. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 13-117–13-144). National Fire Protection Association.