A '''motor fuel dispensing facility''' is a location where gasoline, other volatile flammable liquids or liquefied petroleum gases are transferred into the fuel tanks of self-propelled vehicles.<ref name="Milatovich-8-172">Milatovich (2008), p. 8-172.</ref> They include public service stations, also called filling stations, many of which also repair vehicles. In the United States, design and construction requirements for these facilities are based on NFPA 30A, ''Code for Motor Fuel Dispensing Facilities and Repair Garages''.<ref name="Rivkin-21-29">Rivkin (2008a), p. 21-29.</ref><ref name="Rivkin-21-30">Rivkin (2008a), p. 21-30.</ref>
A '''motor fuel dispensing facility''' is a location where gasoline, other volatile flammable liquids or liquefied petroleum gases are transferred into the fuel tanks of self-propelled vehicles.<ref name="Milatovich-8-172">Milatovich (2008), p. 8-172.</ref> They include public service stations, also called filling stations, many of which also repair vehicles. In the 2008 handbook's account of United States practice, NFPA 30A, ''Code for Motor Fuel Dispensing Facilities and Repair Garages'', provided the design and construction requirements for these facilities.<ref name="Rivkin-21-29">Rivkin (2008a), p. 21-29.</ref><ref name="Rivkin-21-30">Rivkin (2008a), p. 21-30.</ref>


The fire risk comes from storing, transferring and using flammable and combustible liquids. Unlike in industry, the transfers are carried out by members of the public who have no training in the hazards, and they take place far more often.<ref name="Rivkin-21-29" /> In the United States in 1994–1998, 62 % of fires at public service stations were vehicle fires, some of which spread to the rest of the facility.<ref name="Rivkin-21-29" /> The requirements aim to prevent releases of liquid or vapour, to keep ignition sources away from flammable vapour, and to stop the flow quickly if something goes wrong.<ref name="Rivkin-21-34">Rivkin (2008a), p. 21-34.</ref><ref name="Rivkin-21-35">Rivkin (2008a), p. 21-35.</ref> Breakaway hose couplings, automatic-closing nozzles, emergency shutoff valves, classified electrical equipment and remote emergency disconnects serve these aims.<ref name="Rivkin-21-36">Rivkin (2008a), p. 21-36.</ref>
The fire risk comes from storing, transferring and using flammable and combustible liquids. Unlike in industry, the transfers are carried out by members of the public who have no training in the hazards, and they take place far more often.<ref name="Rivkin-21-29" /> In the United States in 1994–1998, 62 % of fires at public service stations were vehicle fires, some of which spread to the rest of the facility.<ref name="Rivkin-21-29" /> The 2008 requirements aimed to prevent releases of liquid or vapour, keep ignition sources away from flammable vapour, and stop the flow quickly if something went wrong.<ref name="Rivkin-21-34">Rivkin (2008a), p. 21-34.</ref><ref name="Rivkin-21-35">Rivkin (2008a), p. 21-35.</ref> Breakaway hose couplings, automatic-closing nozzles, emergency shutoff valves, classified electrical equipment and remote emergency disconnects serve these aims.<ref name="Rivkin-21-36">Rivkin (2008a), p. 21-36.</ref>


== Definition and scope ==
== Definition and scope ==
In the electrical code chapter of the NFPA ''Fire Protection Handbook'' (20th edition, 2008), motor fuel dispensing facilities form an occupancy group of their own. It covers locations where gasoline, other volatile flammable liquids or liquefied petroleum gases are transferred to the fuel tanks or auxiliary fuel tanks of self-propelled vehicles.<ref name="Milatovich-8-172" /> For the hazardous (classified) areas and other fire safety guidance at service stations, the chapter refers to NFPA 30, NFPA 30A and Article 514 of the [[National Electrical Code]].<ref name="Milatovich-8-172" /> The handbook chapter on service station operations covers both automotive and marine stations, whose operations include refuelling and repairs.<ref name="Rivkin-21-29" /> Under NFPA 101, ''Life Safety Code'', refuelling facilities and repair garages are special-purpose industrial occupancies.<ref name="Rivkin-21-31">Rivkin (2008a), p. 21-31.</ref>
In the electrical code chapter of the NFPA ''Fire Protection Handbook'' (20th edition, 2008), motor fuel dispensing facilities form an occupancy group of their own. It covers locations where gasoline, other volatile flammable liquids or liquefied petroleum gases are transferred to the fuel tanks or auxiliary fuel tanks of self-propelled vehicles.<ref name="Milatovich-8-172" /> For the hazardous (classified) areas and other fire safety guidance at service stations, the chapter refers to NFPA 30, NFPA 30A and Article 514 of the [[National Electrical Code]].<ref name="Milatovich-8-172" /> The handbook chapter on service station operations covers both automotive and marine stations, whose operations include refuelling and repairs.<ref name="Rivkin-21-29" /> Under NFPA 101, ''Life Safety Code'', refuelling facilities and repair garages are special-purpose industrial occupancies.<ref name="Rivkin-21-31">Rivkin (2008a), p. 21-31.</ref>


Facilities can be attended or unattended, and many offer both. An attended facility is in theory safer, because a person can see problems that would go unnoticed at an unattended one.<ref name="Rivkin-21-36" /> Unattended facilities therefore need automatic-closing hose nozzles and a telephone or other device to call the fire department.<ref name="Rivkin-21-36" /> Facilities can also dispense compressed natural gas (CNG), liquefied petroleum gas (LP-gas) or hydrogen to an [[Alternative fuel vehicle|alternative fuel vehicle]]. One urban example in the handbook stores and dispenses gasoline, CNG and LP-gas on a single site.<ref name="Rivkin-21-67">Rivkin (2008b), p. 21-67.</ref>
Facilities can be attended or unattended, and many offer both. An attended facility is in theory safer, because a person can see problems that would go unnoticed at an unattended one.<ref name="Rivkin-21-36" /> The 2008 handbook says unattended facilities need automatic-closing hose nozzles and a telephone or other device to call the fire department.<ref name="Rivkin-21-36" /> Facilities can also dispense compressed natural gas (CNG), liquefied petroleum gas (LP-gas) or hydrogen to an [[Alternative fuel vehicle|alternative fuel vehicle]]. One urban example in the handbook stores and dispenses gasoline, CNG and LP-gas on a single site.<ref name="Rivkin-21-67">Rivkin (2008b), p. 21-67.</ref>


== Fire experience ==
== Fire experience ==
Line 16: Line 16:


== Fuels and their hazards ==
== Fuels and their hazards ==
Flammable liquids differ in volatility, so they evaporate and spread to ignition sources at different rates.<ref name="Rivkin-21-30" /> The [[Flash point]] is the lowest temperature at which a liquid gives off enough vapour to form an ignitable mixture with air near its surface or within the vessel, as measured by a standard test.<ref name="Rivkin-21-30" /> NFPA 30 classifies liquids by flash point. Class I flammable liquids have flash points below 37.8 °C, and Class IB covers those with flash points below 22.8 °C and boiling points at or above 37.8 °C.<ref name="Slye-6-198">Slye (2008), p. 6-198.</ref> Combustible liquids of Class II flash between 37.8 °C and 60 °C, and Class IIIB liquids at or above 93 °C.<ref name="Slye-6-198" /> Several service station rules depend on this [[Flammable and combustible liquid classification|classification]], such as the vent height of underground tanks and the separation of heaters from areas where Class I liquids are dispensed.<ref name="Rivkin-21-33">Rivkin (2008a), p. 21-33.</ref>
Flammable liquids differ in volatility, so they evaporate and spread to ignition sources at different rates.<ref name="Rivkin-21-30" /> The [[Flash point]] is the lowest temperature at which a liquid gives off enough vapour to form an ignitable mixture with air near its surface or within the vessel, as measured by a standard test.<ref name="Rivkin-21-30" /> NFPA 30 classifies liquids principally by flash point and, for some sub-classes, boiling point.<ref name="Slye-6-198" />


[[Gasoline]] is the most hazardous liquid at a service station. Its flash point of −40 °C to −46 °C (−40 °F to −50 °F) places it in Class IB, and its minimum ignition temperature in air is about 441 °C.<ref name="Rivkin-21-32">Rivkin (2008a), p. 21-32 (Table 21.3.1).</ref> The flash point is about 83 K lower than that of diesel fuel No. 1, so only in severe cold does gasoline fail to form an ignitable mixture.<ref name="Rivkin-21-30" /> Diesel fuels No. 1, 2 and 4, with flash points of 38 °C to 54 °C, and kerosene at 38 °C are Class II liquids.<ref name="Rivkin-21-32" /> Pure methanol, used in windscreen washer fluid mixtures, flashes at 12 °C and is Class IB, while antifreeze, brake fluid, greases and lubricants are Class IIIB.<ref name="Rivkin-21-32" />
Under the NFPA 30 classification in the handbook, Class I liquids have flash points below 37.8 °C and vapour pressures no greater than 40 psia at that temperature. Class IB also requires a flash point below 22.8 °C and a boiling point at or above 37.8 °C.<ref name="Slye-6-198">Slye (2008), p. 6-198.</ref> Combustible Class II liquids flash at or above 37.8 °C but below 60 °C; Class IIIB liquids flash at or above 93 °C.<ref name="Slye-6-198" /> Several service station rules depend on this [[Flammable and combustible liquid classification|classification]], such as the vent height of underground tanks and the separation of heaters from areas where Class I liquids are dispensed.<ref name="Rivkin-21-33">Rivkin (2008a), p. 21-33.</ref>
 
[[Gasoline]] has the lowest flash point in the handbook's table of service-station liquids: −40 °C to −46 °C (−40 °F to −50 °F). The table classifies it as Class IB and gives a minimum ignition temperature in air of about 441 °C.<ref name="Rivkin-21-32">Rivkin (2008a), p. 21-32 (Table 21.3.1).</ref> That flash-point range is about 78 K to 84 K below the 38 °C value for diesel fuel No. 1; the handbook says only severe cold would prevent gasoline vapour forming an ignitable mixture.<ref name="Rivkin-21-30" /> Diesel fuels No. 1, 2 and 4, with flash points of 38 °C to 54 °C, and kerosene at 38 °C are Class II liquids.<ref name="Rivkin-21-32" /> Pure methanol, used in windscreen washer fluid mixtures, flashes at 12 °C and is Class IB, while antifreeze, brake fluid, greases and lubricants are Class IIIB.<ref name="Rivkin-21-32" />


Vapour that escapes in a part of a building free of ignition sources can travel to places where ignition sources exist. Serious accidents have happened through pathways that nobody had considered beforehand.<ref name="Rivkin-21-33" /> Spill control must prevent fuel from flowing through the floor or into other parts of a building. Drainage connected to public sewers or waterways needs an oil trap or separator.<ref name="Rivkin-21-32-text">Rivkin (2008a), p. 21-32.</ref>
Vapour that escapes in a part of a building free of ignition sources can travel to places where ignition sources exist. Serious accidents have happened through pathways that nobody had considered beforehand.<ref name="Rivkin-21-33" /> Spill control must prevent fuel from flowing through the floor or into other parts of a building. Drainage connected to public sewers or waterways needs an oil trap or separator.<ref name="Rivkin-21-32-text">Rivkin (2008a), p. 21-32.</ref>


== Storage tanks and piping ==
== Storage tanks and piping ==
All flammable liquids must be kept in approved closed containers or in tanks; at service stations a container may hold at most 227 L (60 gal).<ref name="Rivkin-21-33" /> Tanks may be underground, aboveground or in vaults. An [[Underground storage tank]] presents less fire hazard but a greater risk to the environment, and environmental rules for such tanks are stricter.<ref name="Rivkin-21-33" /> Ordile (2008) describes underground tanks as generally the safest form of storage, while noting the growing concern about groundwater contamination.<ref name="Ordile-7-23">Ordile (2008), p. 7-23.</ref> The handbook illustrates a system with double-walled, cathodically protected steel tanks on a concrete foundation, double-walled piping and monitoring wells.<ref name="Rivkin-21-30" />
Under the 2008 handbook's NFPA 30A account, all flammable liquids must be kept in approved closed containers or in tanks; at service stations a container may hold at most 227 L (60 gal).<ref name="Rivkin-21-33" /> Tanks may be underground, aboveground or in vaults. An [[Underground storage tank]] presents less fire hazard but a greater risk to the environment, and environmental rules for such tanks are stricter.<ref name="Rivkin-21-33" /> Ordile (2008) describes underground tanks as generally the safest form of storage, while noting the growing concern about groundwater contamination.<ref name="Ordile-7-23">Ordile (2008), p. 7-23.</ref> The handbook illustrates a system with double-walled, cathodically protected steel tanks on a concrete foundation, double-walled piping and monitoring wells.<ref name="Rivkin-21-30" />


Vent pipes of underground tanks must be wide enough to prevent blowback of vapour or liquid at the fill opening during filling. For Class I liquids such as gasoline, the vent must discharge at least 3.7 m (12 ft) above ground, away from building openings and air intakes, and higher than the fill pipe.<ref name="Rivkin-21-33" /><ref name="Rivkin-21-34" /> The tanks need external corrosion protection and must be at least 0.3 m (1 ft) from basement or pit walls and 0.91 m (3 ft) from property lines that can be built on.<ref name="Rivkin-21-34" /> Poor workmanship is one of the largest causes of leaks. A properly installed steel tank with a fibreglass outer wall or cathodic protection can be expected to last 25 to 30 years.<ref name="Ordile-7-24">Ordile (2008), p. 7-24.</ref> Leaking contents can travel substantial distances underground, or penetrate 610 mm (24 in.) of waterproofed concrete before appearing in a building.<ref name="Ordile-7-24" />
Vent pipes of underground tanks must be wide enough to prevent blowback of vapour or liquid at the fill opening during filling. For Class I liquids such as gasoline, the vent must discharge at least 3.7 m (12 ft) above ground, away from building openings and air intakes, and higher than the fill pipe.<ref name="Rivkin-21-33" /><ref name="Rivkin-21-34" /> The tanks need external corrosion protection and must be at least 0.3 m (1 ft) from basement or pit walls and 0.91 m (3 ft) from property lines that can be built on.<ref name="Rivkin-21-34" /> Poor workmanship is one of the largest causes of leaks. A properly installed steel tank with a fibreglass outer wall or cathodic protection can be expected to last 25 to 30 years.<ref name="Ordile-7-24">Ordile (2008), p. 7-24.</ref> Leaking contents can travel substantial distances underground, or penetrate 610 mm (24 in.) of waterproofed concrete before appearing in a building.<ref name="Ordile-7-24" />


Aboveground tanks need separation from property lines, buildings, dispensers, public ways and other tanks, according to their size and fire protection. They also need spill protection, an alarm at 90 % of capacity, and protection against vehicle impact and unauthorised access.<ref name="Rivkin-21-34" /> Tanks in vaults must have ventilation and vapour and liquid detection, with an alarm at 25 % of the lower flammable limit.<ref name="Rivkin-21-34" /> Vault walls and floors are of reinforced concrete at least 150 mm (6 in.) thick, and the top is designed to vent, relieve or contain an internal explosion.<ref name="Ordile-7-25">Ordile (2008), p. 7-25.</ref>
Aboveground tanks need separation from property lines, buildings, dispensers, public ways and other tanks, according to their size and fire protection. They also need spill protection, an alarm at 90 % of capacity, and protection against vehicle impact and unauthorised access.<ref name="Rivkin-21-34" /> Gasoline tanks in vaults must have ventilation and vapour and liquid detection in the handbook's 2008 account. The vapour detector should alarm at or above 25 % of the lower flammable limit.<ref name="Rivkin-21-34" /> Ordile describes vault walls and floors of reinforced concrete at least 150 mm (6 in.) thick. The top of an above-grade vault should vent an internal explosion; an at-grade or below-grade vault top should relieve or contain its force.<ref name="Ordile-7-25">Ordile (2008), p. 7-25.</ref>


Piping is one of the most vulnerable parts of the system, because vehicle impact can rupture it, corrosion can make it leak and stress can crack it. It must be protected against damage, enclosed in fire-resistant material inside buildings, and colour-coded by product.<ref name="Rivkin-21-34" /> Daily inventory records allow a mass balance, comparing fuel received with fuel dispensed, which can reveal a small leak before it becomes a large one.<ref name="Rivkin-21-36" />
Piping is one of the most vulnerable parts of the system, because vehicle impact can rupture it, corrosion can make it leak and stress can crack it. It must be protected against damage, enclosed in fire-resistant material inside buildings, and colour-coded by product.<ref name="Rivkin-21-34" /> Daily inventory records allow a mass balance, comparing fuel received with fuel dispensed, which can reveal a small leak before it becomes a large one.<ref name="Rivkin-21-36" />


== Dispensing equipment and ignition control ==
== Dispensing equipment and ignition control ==
Two general rules apply to every dispensing system. The whole vehicle being refuelled must stand on the facility's property, and fuel must be moved by pumps, never by pressurising the storage container.<ref name="Rivkin-21-34" /> A dispenser may not operate while its nozzle rests in the holder. It must be bolted to a concrete island that keeps other vehicles out of the refuelling area.<ref name="Rivkin-21-34" /> The fuel supply line needs an emergency shutoff valve that closes on severe impact or fire exposure, tested at least once a year.<ref name="Rivkin-21-34" /> Remote or submersible pumps need a leak detector and must be at least 1.5 m (5 ft) from building entrances and 3 m (10 ft) from property lines.<ref name="Rivkin-21-35" />
The 2008 handbook gives two general rules for liquid-fuel dispensing systems: the whole vehicle must stand on the facility's property, and pumps must transfer fuel without pressurising the storage container.<ref name="Rivkin-21-34" /> A dispenser may not operate while its nozzle rests in the holder. It must be bolted to a concrete island that keeps other vehicles out of the refuelling area.<ref name="Rivkin-21-34" /> The fuel supply line needs an emergency shutoff valve that closes on severe impact or fire exposure, tested at least once a year.<ref name="Rivkin-21-34" /> Remote or submersible pumps need a leak detector and must be at least 1.5 m (5 ft) from building entrances and 3 m (10 ft) from property lines.<ref name="Rivkin-21-35" />
 
Hoses must be listed and no longer than 5.5 m (18 ft). Gasoline hoses need a breakaway device that retains the fuel if a driver pulls away with the nozzle still in the fill pipe.<ref name="Rivkin-21-35" /> Gasoline nozzles must close automatically when released. Together with a breakaway device, this is intended to limit a drive-away release to a small amount of fuel.<ref name="Rivkin-21-35" />


Hoses must be listed and no longer than 5.5 m (18 ft). Gasoline hoses need a breakaway device that retains the fuel if a driver pulls away with the nozzle still in the fill pipe.<ref name="Rivkin-21-35" /> Nozzles must close automatically when released, so that together with the breakaway device only small amounts of gasoline can escape.<ref name="Rivkin-21-35" /> Remote emergency electrical disconnects must be 6.1 m to 30.5 m (20 ft to 100 ft) from the dispensers. They are interconnected, so that any one of them cuts power to all hazardous locations around the dispensers.<ref name="Rivkin-21-35" /><ref name="Rivkin-21-36" /> They remove ignition sources and can stop the flow if other safety devices fail.<ref name="Rivkin-21-35" />
Remote emergency electrical disconnects must be 6.1 m to 30.5 m (20 ft to 100 ft) from the dispensers. They are interconnected, so that any one of them cuts power to all hazardous locations around the dispensers.<ref name="Rivkin-21-35" /><ref name="Rivkin-21-36" /> They can remove electrical ignition sources and stop the flow if other safety devices fail.<ref name="Rivkin-21-35" />


The space around the dispensers is subject to [[Hazardous area classification|hazardous area classification]]. Special electrical equipment is required up to 457 mm (18 in.) above grade within a radius of 6.1 m (20 ft) of refuelling areas.<ref name="Rivkin-21-36" /> Article 514 of the National Electrical Code governs electrical equipment and wiring at gasoline dispensing stations.<ref name="Milatovich-8-162">Milatovich (2008), p. 8-162.</ref> In Class I, Division 1 locations, ignitable concentrations can exist in normal operation, whereas in Division 2 locations the flammable liquids are normally kept within closed containers or systems.<ref name="Milatovich-8-169">Milatovich (2008), p. 8-169.</ref> The Gadsden explosion shows what an unsuitable electrical fitting in such a zone can do.<ref name="Rivkin-21-36" />
The space around the dispensers is subject to [[Hazardous area classification|hazardous area classification]]. Special electrical equipment is required up to 457 mm (18 in.) above grade within a radius of 6.1 m (20 ft) of refuelling areas.<ref name="Rivkin-21-36" /> Article 514 of the National Electrical Code governs electrical equipment and wiring at gasoline dispensing stations.<ref name="Milatovich-8-162">Milatovich (2008), p. 8-162.</ref> In Class I, Division 1 locations, ignitable concentrations can exist in normal operation, whereas in Division 2 locations the flammable liquids are normally kept within closed containers or systems.<ref name="Milatovich-8-169">Milatovich (2008), p. 8-169.</ref> The Gadsden explosion shows what an unsuitable electrical fitting in such a zone can do.<ref name="Rivkin-21-36" />


[[Static electricity]] is a further ignition source. A person who gets back into the vehicle during refuelling can build up a charge sliding across the seat and then discharge it when removing the nozzle. At unattended facilities, customers must therefore stay outside the vehicle throughout refuelling.<ref name="Rivkin-21-36" /> Portable containers must be approved, labelled, filled by hand and placed on the ground, not in or on a vehicle.<ref name="Rivkin-21-36" /> A can filled on the plastic bedliner of a pickup truck is insulated from the earth, so its charge can spark from the edge of the fill opening to the grounded fill pipe.<ref name="Scarbrough-11-64">Scarbrough (2008a), p. 11-64.</ref>
[[Static electricity]] is a further ignition source. A person who gets back into the vehicle during refuelling can build up a charge sliding across the seat and then discharge it when removing the nozzle. The 2008 handbook therefore says customers at unattended facilities must stay outside the vehicle throughout refuelling.<ref name="Rivkin-21-36" /> It also requires portable containers to be approved, labelled, filled by hand and placed on the ground, not in or on a vehicle.<ref name="Rivkin-21-36" /> A can filled on the plastic bedliner of a pickup truck is insulated from the earth, so its charge can spark from the edge of the fill opening to the grounded fill pipe.<ref name="Scarbrough-11-64">Scarbrough (2008a), p. 11-64.</ref>


== Buildings, repair garages and fire protection ==
== Buildings, repair garages and fire protection ==
Most public service stations dispense fuel outdoors, but occasionally a parking garage includes fuel dispensing.<ref name="Rivkin-21-33" /> Indoor dispensing areas must be separated from the rest of the building by 2-hour fire-resistant construction, with fire doors and fire dampers in openings. They must be at street level, within 15.2 m (50 ft) of a building entrance or exit, and serve no more than four vehicles.<ref name="Rivkin-21-33" /> A dedicated mechanical exhaust system, interlocked with the dispensers, must move air across the whole floor to prevent ignitable vapour from building up.<ref name="Rivkin-21-33" />
Most public service stations dispense fuel outdoors, but occasionally a parking garage includes fuel dispensing.<ref name="Rivkin-21-33" /> In the 2008 handbook's NFPA 30A account, indoor dispensing areas must be separated from the rest of the building by 2-hour fire-resistant construction, with fire doors and fire dampers in openings. They must be at street level, within 15.2 m (50 ft) of a building entrance or exit, and serve no more than four vehicles.<ref name="Rivkin-21-33" /> A dedicated mechanical exhaust system, interlocked with the dispensers, must move air across the whole floor to prevent ignitable vapour from building up.<ref name="Rivkin-21-33" />
 
Repair garages add other hazards. Pits and below-grade work areas must be noncombustible and ventilated, and they can become oxygen-deficient when airflow is restricted.<ref name="Rivkin-21-33" /> The 2008 handbook says heat-producing appliances must be of approved types and separated from Class I liquid dispensing. It gives another room or a position at least 2.4 m (8 ft) above the floor as ways to achieve this separation.


Repair garages add other hazards. Pits and below-grade work areas must be noncombustible and ventilated, and they can become oxygen-deficient when airflow is restricted.<ref name="Rivkin-21-33" /> Heat-producing appliances must be of approved types and be in another room or at least 2.4 m (8 ft) above the floor, above any flammable vapour. Cleaning floors with gasoline is a common unsafe practice that can lead to fires and explosions.<ref name="Rivkin-21-33" /> [[Hot work]] must take place in specially designed areas, spray painting is limited to small parts at least 6.1 m (20 ft) from ignition sources, and parts cleaning should use nonflammable solvents.<ref name="Rivkin-21-37">Rivkin (2008a), p. 21-37.</ref>
Cleaning floors with gasoline is a common unsafe practice that can lead to fires and explosions.<ref name="Rivkin-21-33" /> [[Hot work]] must take place in specially designed areas, and spray painting is limited to small parts at least 6.1 m (20 ft) from ignition sources. The handbook recommends nonflammable parts-cleaning solvents whenever possible.<ref name="Rivkin-21-37">Rivkin (2008a), p. 21-37.</ref>


Fixed fire protection is often recommended for refuelling areas and is required in larger repair garages.<ref name="Rivkin-21-38">Rivkin (2008a), p. 21-38.</ref> A garage counts as larger if it has two or more storeys with any floor above 929 m² (10,000 ft²), or one storey above 1,390 m² (15,000 ft²), or lies in a basement.<ref name="Rivkin-21-33" /> Each facility should have listed fire extinguishers with a [[Fire extinguisher rating|rating]] of at least 40-B:C within 30 m (100 ft) of every pump, fill pipe opening and lubrication or service room.<ref name="Rivkin-21-38" />
The 2008 handbook often recommended fixed fire protection for refuelling areas and described it as required in larger repair garages.<ref name="Rivkin-21-38">Rivkin (2008a), p. 21-38.</ref> Its thresholds were two or more storeys with any floor above 10,000 ft² (approximately 930 m²), one storey above 15,000 ft² (approximately 1,400 m²), or a garage in a basement.<ref name="Rivkin-21-33" /> The handbook calls for listed fire extinguishers with a [[Fire extinguisher rating|rating]] of at least 40-B:C within 30 m (100 ft) of every pump, fill-pipe opening and lubrication or service room.<ref name="Rivkin-21-38" />


== Estimating the size of a spill fire ==
== Estimating the size of a spill fire ==
Spill control matters because a liquid released on a flat surface spreads into a thin layer. In the SFPE Handbook, Gottuk and White (2002) relate the depth of a spill to its volume and area, so that the area follows from the volume once a depth is assumed.<ref name="GW-2-298">Gottuk and White (2002), p. 2-298.</ref> Fires on unconfined spills were observed to spread the fuel further, so they suggest taking the fire area as about 155 % of the initial spill area.<ref name="GW-2-298" /> The area can then be expressed as the diameter of a circle of the same size.<ref name="Heskestad-2-4">Heskestad (2002), p. 2-4.</ref>
Spill control matters because a liquid released on a flat surface spreads into a thin layer. In the SFPE Handbook, Gottuk and White (2002) relate the depth of a spill to its volume and area, so that the area follows from the volume once a depth is assumed.<ref name="GW-2-298">Gottuk and White (2002), p. 2-298.</ref> In limited unconfined-spill tests, ignition expanded the fuel area; Gottuk and White suggest about 155 % of the initial area when estimating maximum fire size.<ref name="GW-2-298" /> The area can then be expressed as the diameter of a circle of the same size.<ref name="Heskestad-2-4">Heskestad (2002), p. 2-4.</ref>


<math display="block">A_\mathrm{s} = \frac{V}{\delta}</math>
<math display="block">A_\mathrm{s} = \frac{V}{\delta}</math>
Line 70: Line 76:
|}
|}


For releases of 95 L (25 gal) or more, the spill area per litre approaches about 0.3 m²/L, which corresponds to depths of 2.8 mm to 4 mm.<ref name="GW-2-298" /> As a worked example, a release of 95 L from a damaged dispenser line would therefore cover about 95 × 0.3 = 28.5 m². A fire on it could cover 1.55 × 28.5, or about 45 m², a circle about 7.6 m across. For comparison, the classified zone around a dispenser has a radius of 6.1 m.<ref name="Rivkin-21-36" /> If the conservative minimum depth of 0.7 mm is assumed instead, the same 95 L would cover about 136 m² and the fire more than 210 m².<ref name="GW-2-299">Gottuk and White (2002), p. 2-299.</ref>
For releases of 95 L (25 gal) or more, the spill area per litre approaches about 0.3 m²/L, which corresponds to depths of 2.8 mm to 4 mm.<ref name="GW-2-298" /> As an illustrative calculation, suppose 95 L escapes from a liquid-fuel dispenser line. Applying the SFPE large-spill value, drawn mostly from jet-fuel tests, gives 95 × 0.3 = 28.5 m². The suggested factor of 1.55 gives a possible fire area of about 44 m², with an equivalent-circle diameter of 7.5 m.<ref name="GW-2-298" />
 
For comparison only, the electrical classification extends 6.1 m from refuelling areas at a specified height.<ref name="Rivkin-21-36" /> As a bounding calculation, a depth of 0.7 mm gives about 136 m² of spill and 210 m² of possible fire area. That minimum came from smaller JP-8 spills and foam-solution tests, not a measured 95 L gasoline spill.<ref name="GW-2-299">Gottuk and White (2002), p. 2-299.</ref>


The data behind these estimates come mostly from jet fuels, water and foam solution on smooth concrete. The only gasoline data, for 0.25 L to 1 L on wood parquet and vinyl tile, gave depths of 0.5 mm to 0.7 mm and areas of 0.4 m² to 1.8 m².<ref name="GW-2-299" /> Spill depths can range from 0.7 mm to 4 mm, depending mainly on the quantity released.<ref name="GW-2-299" /> A [[Spill fire|spill fire]] also burns differently from a deep pool: for diameters above about 1 m, unconfined spills of jet fuel on concrete burned at about one-fifth of the maximum burning rate of confined pools.<ref name="GW-2-311">Gottuk and White (2002), p. 2-311.</ref> The estimate therefore indicates the area at risk, not the heat release rate.
The data behind these estimates come mostly from jet fuels, water and foam solution on smooth concrete. The only gasoline data, for 0.25 L to 1 L on wood parquet and vinyl tile, gave depths of 0.5 mm to 0.7 mm and areas of 0.4 m² to 1.8 m².<ref name="GW-2-299" /> Spill depths can range from 0.7 mm to 4 mm, depending mainly on the quantity released.<ref name="GW-2-299" /> A [[Spill fire|spill fire]] also burns differently from a deep pool: for diameters above about 1 m, unconfined spills of jet fuel on concrete burned at about one-fifth of the maximum burning rate of confined pools.<ref name="GW-2-311">Gottuk and White (2002), p. 2-311.</ref> The estimate therefore indicates the area at risk, not the heat release rate.


== Gaseous fuels and marine facilities ==
== Gaseous fuels and marine facilities ==
Gaseous fuels bring their own rules. Under NFPA 30A, LP-gas dispensers should be at least 6.1 m (20 ft) from gasoline or diesel dispensers, and LP-gas hoses need a listed emergency breakaway device.<ref name="Rivkin-21-68">Rivkin (2008b), p. 21-68.</ref> CNG dispensers need protection from vehicle impact and a nonconductive hose of at most 7.6 m (25 ft) with a breakaway device.<ref name="Rivkin-21-63">Rivkin (2008b), p. 21-63.</ref><ref name="Rivkin-21-64">Rivkin (2008b), p. 21-64.</ref> CNG is normally dispensed outdoors; indoors it requires a dedicated structure or a room behind walls of at least 2-hour fire resistance, explosion venting and gas detection. Public parking garages are commonly unacceptable for fuelling with any conventional or alternative fuel.<ref name="Rivkin-21-62">Rivkin (2008b), p. 21-62.</ref> Hydrogen dispensers add leak detection, emergency shutoff, breakaway protection and relief valves set at 1.38 times the vehicle's working pressure.<ref name="SC-21-88">Scheffler and Collins (2008), p. 21-88.</ref>
The 2008 handbook describes separate rules for gaseous fuels. In its NFPA 30A account, LP-gas dispensers should be at least 6.1 m (20 ft) from gasoline or diesel dispensers, and LP-gas hoses need a listed emergency breakaway device.<ref name="Rivkin-21-68">Rivkin (2008b), p. 21-68.</ref> CNG dispensers need protection from vehicle impact and a nonconductive hose of at most 7.6 m (25 ft) with a breakaway device.<ref name="Rivkin-21-63">Rivkin (2008b), p. 21-63.</ref><ref name="Rivkin-21-64">Rivkin (2008b), p. 21-64.</ref> CNG is normally dispensed outdoors; indoors it requires a dedicated structure or a room behind walls of at least 2-hour fire resistance, explosion venting and gas detection. The handbook notes that local approvals vary but public parking garages are commonly unacceptable for fuelling with conventional or alternative fuels.<ref name="Rivkin-21-62">Rivkin (2008b), p. 21-62.</ref> For hydrogen dispensers, the 2008 FCV chapter envisages leak detection, emergency shutoff, breakaway protection and station relief valves set at 1.38 times the vehicle's nominal working pressure.<ref name="SC-21-88">Scheffler and Collins (2008), p. 21-88.</ref>


At marine facilities, fuel usually runs from a tank on land to a dispenser on a pier, which increases the risk of a release. The extra requirements therefore focus on the supply line, with shutoff valves at the approach to the pier and at the shore end.<ref name="Rivkin-21-38" /> An attendant must always be present, and the nozzle must stay in contact with the vessel's fill pipe to keep them bonded.<ref name="Rivkin-21-38" /> Piers extending more than 152 m (500 ft) from shore should have a Class III standpipe system.<ref name="Rivkin-21-39">Rivkin (2008a), p. 21-39.</ref>
At marine facilities, fuel often runs from a tank on land to a dispenser on a pier, increasing the risk of a release. The extra requirements therefore focus on the supply line, with shutoff valves at the approach to the pier and at the shore end.<ref name="Rivkin-21-38" /> The 2008 handbook says an attendant should always be present, and the nozzle must stay in contact with the vessel's fill pipe to keep them bonded.<ref name="Rivkin-21-38" /> Piers extending more than 152 m (500 ft) from shore should have a Class III standpipe system.<ref name="Rivkin-21-39">Rivkin (2008a), p. 21-39.</ref>


All the requirements above are those of United States codes as summarised in a 2008 handbook, not current editions or the rules of other countries. Fire data were available only for public stations, not for private ones.<ref name="Rivkin-21-29" /> For LP-gas installations the handbook stresses that setback distances are minimum requirements that reduce risk, not safe distances that remove it.<ref name="Rivkin-21-67" />
All the requirements above are those of United States codes as summarised in a 2008 handbook, not current editions or the rules of other countries. Fire data were available only for public stations, not for private ones.<ref name="Rivkin-21-29" /> For LP-gas installations the handbook stresses that setback distances are minimum requirements that reduce risk, not safe distances that remove it.<ref name="Rivkin-21-67" />

Revision as of 02:44, 8 November 2026

A motor fuel dispensing facility is a location where gasoline, other volatile flammable liquids or liquefied petroleum gases are transferred into the fuel tanks of self-propelled vehicles.[1] They include public service stations, also called filling stations, many of which also repair vehicles. In the 2008 handbook's account of United States practice, NFPA 30A, Code for Motor Fuel Dispensing Facilities and Repair Garages, provided the design and construction requirements for these facilities.[2][3]

The fire risk comes from storing, transferring and using flammable and combustible liquids. Unlike in industry, the transfers are carried out by members of the public who have no training in the hazards, and they take place far more often.[2] In the United States in 1994–1998, 62 % of fires at public service stations were vehicle fires, some of which spread to the rest of the facility.[2] The 2008 requirements aimed to prevent releases of liquid or vapour, keep ignition sources away from flammable vapour, and stop the flow quickly if something went wrong.[4][5] Breakaway hose couplings, automatic-closing nozzles, emergency shutoff valves, classified electrical equipment and remote emergency disconnects serve these aims.[6]

Definition and scope

In the electrical code chapter of the NFPA Fire Protection Handbook (20th edition, 2008), motor fuel dispensing facilities form an occupancy group of their own. It covers locations where gasoline, other volatile flammable liquids or liquefied petroleum gases are transferred to the fuel tanks or auxiliary fuel tanks of self-propelled vehicles.[1] For the hazardous (classified) areas and other fire safety guidance at service stations, the chapter refers to NFPA 30, NFPA 30A and Article 514 of the National Electrical Code.[1] The handbook chapter on service station operations covers both automotive and marine stations, whose operations include refuelling and repairs.[2] Under NFPA 101, Life Safety Code, refuelling facilities and repair garages are special-purpose industrial occupancies.[7]

Facilities can be attended or unattended, and many offer both. An attended facility is in theory safer, because a person can see problems that would go unnoticed at an unattended one.[6] The 2008 handbook says unattended facilities need automatic-closing hose nozzles and a telephone or other device to call the fire department.[6] Facilities can also dispense compressed natural gas (CNG), liquefied petroleum gas (LP-gas) or hydrogen to an alternative fuel vehicle. One urban example in the handbook stores and dispenses gasoline, CNG and LP-gas on a single site.[8]

Fire experience

Fire data for public service stations show where the greatest risk lies. Over 1994–1998, 62 % of the fires at public service stations in the United States were classed as vehicle fires. This does not mean that only the vehicle burned: several of these fires spread beyond it into the facility.[2] Because a motor vehicle fire is so often involved, the handbook stresses the code requirements on vehicle activity. In 2000 the country had about 210,000 retail outlets selling motor fuel. Many were combined with convenience stores or food retail, which brings more traffic and parked vehicles into the fuelling area.[2][3]

Several incidents in the handbook show how releases reach ignition sources. In January 1974, five people died at a service station in Saint John, New Brunswick, Canada, built on the roof of a tyre warehouse.[4] A vehicle knocked over a dispenser and the emergency shutoff valve failed. The fuel flowed into the warehouse below, where it ignited and exploded.[5] In August 1976 near Gadsden, Alabama, an electric pump with a missing junction box cover ignited vapour lost while a tank truck filled aboveground tanks. The fire spread to the truck, which exploded and killed three responding fire fighters.[6]

Other cases involved vehicle impact and work on tanks. In South Carolina in 1991, a pickup truck left the road and struck the piping of two 15,100 L (4,000 gal) aboveground tanks at a convenience store. Gasoline escaped, quickly found an ignition source, and the driver was killed.[4] In Portland, Maine, in May 1986, vapour vacuumed out of abandoned tanks was discharged at street level on a day with too little natural ventilation to disperse it. A vehicle ignited it, killing one person and injuring three others.[6] Vehicle refuelling is far more frequent than tank filling and accounts for a large share of incidents, but several serious accidents occurred during tank filling and servicing.[6]

Fuels and their hazards

Flammable liquids differ in volatility, so they evaporate and spread to ignition sources at different rates.[3] The Flash point is the lowest temperature at which a liquid gives off enough vapour to form an ignitable mixture with air near its surface or within the vessel, as measured by a standard test.[3] NFPA 30 classifies liquids principally by flash point and, for some sub-classes, boiling point.[9]

Under the NFPA 30 classification in the handbook, Class I liquids have flash points below 37.8 °C and vapour pressures no greater than 40 psia at that temperature. Class IB also requires a flash point below 22.8 °C and a boiling point at or above 37.8 °C.[9] Combustible Class II liquids flash at or above 37.8 °C but below 60 °C; Class IIIB liquids flash at or above 93 °C.[9] Several service station rules depend on this classification, such as the vent height of underground tanks and the separation of heaters from areas where Class I liquids are dispensed.[10]

Gasoline has the lowest flash point in the handbook's table of service-station liquids: −40 °C to −46 °C (−40 °F to −50 °F). The table classifies it as Class IB and gives a minimum ignition temperature in air of about 441 °C.[11] That flash-point range is about 78 K to 84 K below the 38 °C value for diesel fuel No. 1; the handbook says only severe cold would prevent gasoline vapour forming an ignitable mixture.[3] Diesel fuels No. 1, 2 and 4, with flash points of 38 °C to 54 °C, and kerosene at 38 °C are Class II liquids.[11] Pure methanol, used in windscreen washer fluid mixtures, flashes at 12 °C and is Class IB, while antifreeze, brake fluid, greases and lubricants are Class IIIB.[11]

Vapour that escapes in a part of a building free of ignition sources can travel to places where ignition sources exist. Serious accidents have happened through pathways that nobody had considered beforehand.[10] Spill control must prevent fuel from flowing through the floor or into other parts of a building. Drainage connected to public sewers or waterways needs an oil trap or separator.[12]

Storage tanks and piping

Under the 2008 handbook's NFPA 30A account, all flammable liquids must be kept in approved closed containers or in tanks; at service stations a container may hold at most 227 L (60 gal).[10] Tanks may be underground, aboveground or in vaults. An Underground storage tank presents less fire hazard but a greater risk to the environment, and environmental rules for such tanks are stricter.[10] Ordile (2008) describes underground tanks as generally the safest form of storage, while noting the growing concern about groundwater contamination.[13] The handbook illustrates a system with double-walled, cathodically protected steel tanks on a concrete foundation, double-walled piping and monitoring wells.[3]

Vent pipes of underground tanks must be wide enough to prevent blowback of vapour or liquid at the fill opening during filling. For Class I liquids such as gasoline, the vent must discharge at least 3.7 m (12 ft) above ground, away from building openings and air intakes, and higher than the fill pipe.[10][4] The tanks need external corrosion protection and must be at least 0.3 m (1 ft) from basement or pit walls and 0.91 m (3 ft) from property lines that can be built on.[4] Poor workmanship is one of the largest causes of leaks. A properly installed steel tank with a fibreglass outer wall or cathodic protection can be expected to last 25 to 30 years.[14] Leaking contents can travel substantial distances underground, or penetrate 610 mm (24 in.) of waterproofed concrete before appearing in a building.[14]

Aboveground tanks need separation from property lines, buildings, dispensers, public ways and other tanks, according to their size and fire protection. They also need spill protection, an alarm at 90 % of capacity, and protection against vehicle impact and unauthorised access.[4] Gasoline tanks in vaults must have ventilation and vapour and liquid detection in the handbook's 2008 account. The vapour detector should alarm at or above 25 % of the lower flammable limit.[4] Ordile describes vault walls and floors of reinforced concrete at least 150 mm (6 in.) thick. The top of an above-grade vault should vent an internal explosion; an at-grade or below-grade vault top should relieve or contain its force.[15]

Piping is one of the most vulnerable parts of the system, because vehicle impact can rupture it, corrosion can make it leak and stress can crack it. It must be protected against damage, enclosed in fire-resistant material inside buildings, and colour-coded by product.[4] Daily inventory records allow a mass balance, comparing fuel received with fuel dispensed, which can reveal a small leak before it becomes a large one.[6]

Dispensing equipment and ignition control

The 2008 handbook gives two general rules for liquid-fuel dispensing systems: the whole vehicle must stand on the facility's property, and pumps must transfer fuel without pressurising the storage container.[4] A dispenser may not operate while its nozzle rests in the holder. It must be bolted to a concrete island that keeps other vehicles out of the refuelling area.[4] The fuel supply line needs an emergency shutoff valve that closes on severe impact or fire exposure, tested at least once a year.[4] Remote or submersible pumps need a leak detector and must be at least 1.5 m (5 ft) from building entrances and 3 m (10 ft) from property lines.[5]

Hoses must be listed and no longer than 5.5 m (18 ft). Gasoline hoses need a breakaway device that retains the fuel if a driver pulls away with the nozzle still in the fill pipe.[5] Gasoline nozzles must close automatically when released. Together with a breakaway device, this is intended to limit a drive-away release to a small amount of fuel.[5]

Remote emergency electrical disconnects must be 6.1 m to 30.5 m (20 ft to 100 ft) from the dispensers. They are interconnected, so that any one of them cuts power to all hazardous locations around the dispensers.[5][6] They can remove electrical ignition sources and stop the flow if other safety devices fail.[5]

The space around the dispensers is subject to hazardous area classification. Special electrical equipment is required up to 457 mm (18 in.) above grade within a radius of 6.1 m (20 ft) of refuelling areas.[6] Article 514 of the National Electrical Code governs electrical equipment and wiring at gasoline dispensing stations.[16] In Class I, Division 1 locations, ignitable concentrations can exist in normal operation, whereas in Division 2 locations the flammable liquids are normally kept within closed containers or systems.[17] The Gadsden explosion shows what an unsuitable electrical fitting in such a zone can do.[6]

Static electricity is a further ignition source. A person who gets back into the vehicle during refuelling can build up a charge sliding across the seat and then discharge it when removing the nozzle. The 2008 handbook therefore says customers at unattended facilities must stay outside the vehicle throughout refuelling.[6] It also requires portable containers to be approved, labelled, filled by hand and placed on the ground, not in or on a vehicle.[6] A can filled on the plastic bedliner of a pickup truck is insulated from the earth, so its charge can spark from the edge of the fill opening to the grounded fill pipe.[18]

Buildings, repair garages and fire protection

Most public service stations dispense fuel outdoors, but occasionally a parking garage includes fuel dispensing.[10] In the 2008 handbook's NFPA 30A account, indoor dispensing areas must be separated from the rest of the building by 2-hour fire-resistant construction, with fire doors and fire dampers in openings. They must be at street level, within 15.2 m (50 ft) of a building entrance or exit, and serve no more than four vehicles.[10] A dedicated mechanical exhaust system, interlocked with the dispensers, must move air across the whole floor to prevent ignitable vapour from building up.[10]

Repair garages add other hazards. Pits and below-grade work areas must be noncombustible and ventilated, and they can become oxygen-deficient when airflow is restricted.[10] The 2008 handbook says heat-producing appliances must be of approved types and separated from Class I liquid dispensing. It gives another room or a position at least 2.4 m (8 ft) above the floor as ways to achieve this separation.

Cleaning floors with gasoline is a common unsafe practice that can lead to fires and explosions.[10] Hot work must take place in specially designed areas, and spray painting is limited to small parts at least 6.1 m (20 ft) from ignition sources. The handbook recommends nonflammable parts-cleaning solvents whenever possible.[19]

The 2008 handbook often recommended fixed fire protection for refuelling areas and described it as required in larger repair garages.[20] Its thresholds were two or more storeys with any floor above 10,000 ft² (approximately 930 m²), one storey above 15,000 ft² (approximately 1,400 m²), or a garage in a basement.[10] The handbook calls for listed fire extinguishers with a rating of at least 40-B:C within 30 m (100 ft) of every pump, fill-pipe opening and lubrication or service room.[20]

Estimating the size of a spill fire

Spill control matters because a liquid released on a flat surface spreads into a thin layer. In the SFPE Handbook, Gottuk and White (2002) relate the depth of a spill to its volume and area, so that the area follows from the volume once a depth is assumed.[21] In limited unconfined-spill tests, ignition expanded the fuel area; Gottuk and White suggest about 155 % of the initial area when estimating maximum fire size.[21] The area can then be expressed as the diameter of a circle of the same size.[22]

As=Vδ

A=1.55As

D=4Aπ

Symbol Description Unit
V Volume of liquid released m³
δ Depth of the unconfined spill m
As Initial spill area m²
A Area of the spill fire m²
D Diameter of a circle with the same area m

For releases of 95 L (25 gal) or more, the spill area per litre approaches about 0.3 m²/L, which corresponds to depths of 2.8 mm to 4 mm.[21] As an illustrative calculation, suppose 95 L escapes from a liquid-fuel dispenser line. Applying the SFPE large-spill value, drawn mostly from jet-fuel tests, gives 95 × 0.3 = 28.5 m². The suggested factor of 1.55 gives a possible fire area of about 44 m², with an equivalent-circle diameter of 7.5 m.[21]

For comparison only, the electrical classification extends 6.1 m from refuelling areas at a specified height.[6] As a bounding calculation, a depth of 0.7 mm gives about 136 m² of spill and 210 m² of possible fire area. That minimum came from smaller JP-8 spills and foam-solution tests, not a measured 95 L gasoline spill.[23]

The data behind these estimates come mostly from jet fuels, water and foam solution on smooth concrete. The only gasoline data, for 0.25 L to 1 L on wood parquet and vinyl tile, gave depths of 0.5 mm to 0.7 mm and areas of 0.4 m² to 1.8 m².[23] Spill depths can range from 0.7 mm to 4 mm, depending mainly on the quantity released.[23] A spill fire also burns differently from a deep pool: for diameters above about 1 m, unconfined spills of jet fuel on concrete burned at about one-fifth of the maximum burning rate of confined pools.[24] The estimate therefore indicates the area at risk, not the heat release rate.

Gaseous fuels and marine facilities

The 2008 handbook describes separate rules for gaseous fuels. In its NFPA 30A account, LP-gas dispensers should be at least 6.1 m (20 ft) from gasoline or diesel dispensers, and LP-gas hoses need a listed emergency breakaway device.[25] CNG dispensers need protection from vehicle impact and a nonconductive hose of at most 7.6 m (25 ft) with a breakaway device.[26][27] CNG is normally dispensed outdoors; indoors it requires a dedicated structure or a room behind walls of at least 2-hour fire resistance, explosion venting and gas detection. The handbook notes that local approvals vary but public parking garages are commonly unacceptable for fuelling with conventional or alternative fuels.[28] For hydrogen dispensers, the 2008 FCV chapter envisages leak detection, emergency shutoff, breakaway protection and station relief valves set at 1.38 times the vehicle's nominal working pressure.[29]

At marine facilities, fuel often runs from a tank on land to a dispenser on a pier, increasing the risk of a release. The extra requirements therefore focus on the supply line, with shutoff valves at the approach to the pier and at the shore end.[20] The 2008 handbook says an attendant should always be present, and the nozzle must stay in contact with the vessel's fill pipe to keep them bonded.[20] Piers extending more than 152 m (500 ft) from shore should have a Class III standpipe system.[30]

All the requirements above are those of United States codes as summarised in a 2008 handbook, not current editions or the rules of other countries. Fire data were available only for public stations, not for private ones.[2] For LP-gas installations the handbook stresses that setback distances are minimum requirements that reduce risk, not safe distances that remove it.[8]

See also

Notes

  1. ↑ 1.0 1.1 1.2 Milatovich (2008), p. 8-172.
  2. ↑ 2.0 2.1 2.2 2.3 2.4 2.5 2.6 Rivkin (2008a), p. 21-29.
  3. ↑ 3.0 3.1 3.2 3.3 3.4 3.5 Rivkin (2008a), p. 21-30.
  4. ↑ 4.00 4.01 4.02 4.03 4.04 4.05 4.06 4.07 4.08 4.09 4.10 Rivkin (2008a), p. 21-34.
  5. ↑ 5.0 5.1 5.2 5.3 5.4 5.5 5.6 Rivkin (2008a), p. 21-35.
  6. ↑ 6.00 6.01 6.02 6.03 6.04 6.05 6.06 6.07 6.08 6.09 6.10 6.11 6.12 Rivkin (2008a), p. 21-36.
  7. ↑ Rivkin (2008a), p. 21-31.
  8. ↑ 8.0 8.1 Rivkin (2008b), p. 21-67.
  9. ↑ 9.0 9.1 9.2 Slye (2008), p. 6-198.
  10. ↑ 10.00 10.01 10.02 10.03 10.04 10.05 10.06 10.07 10.08 10.09 10.10 Rivkin (2008a), p. 21-33.
  11. ↑ 11.0 11.1 11.2 Rivkin (2008a), p. 21-32 (Table 21.3.1).
  12. ↑ Rivkin (2008a), p. 21-32.
  13. ↑ Ordile (2008), p. 7-23.
  14. ↑ 14.0 14.1 Ordile (2008), p. 7-24.
  15. ↑ Ordile (2008), p. 7-25.
  16. ↑ Milatovich (2008), p. 8-162.
  17. ↑ Milatovich (2008), p. 8-169.
  18. ↑ Scarbrough (2008a), p. 11-64.
  19. ↑ Rivkin (2008a), p. 21-37.
  20. ↑ 20.0 20.1 20.2 20.3 Rivkin (2008a), p. 21-38.
  21. ↑ 21.0 21.1 21.2 21.3 Gottuk and White (2002), p. 2-298.
  22. ↑ Heskestad (2002), p. 2-4.
  23. ↑ 23.0 23.1 23.2 Gottuk and White (2002), p. 2-299.
  24. ↑ Gottuk and White (2002), p. 2-311.
  25. ↑ Rivkin (2008b), p. 21-68.
  26. ↑ Rivkin (2008b), p. 21-63.
  27. ↑ Rivkin (2008b), p. 21-64.
  28. ↑ Rivkin (2008b), p. 21-62.
  29. ↑ Scheffler and Collins (2008), p. 21-88.
  30. ↑ Rivkin (2008a), p. 21-39.

References

  • Gottuk, D. T., & White, D. A. (2002). Liquid fuel fires. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-297–2-316). National Fire Protection Association; Society of Fire Protection Engineers.
  • Heskestad, G. (2002). Fire plumes, flame height, and air entrainment. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-1–2-17). National Fire Protection Association; Society of Fire Protection Engineers.
  • Milatovich, R. M. (2008). Electrical systems and appliances. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 8-127–8-173). National Fire Protection Association.
  • Ordile, A. M. (2008). Storage of flammable and combustible liquids. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 7-15–7-33). National Fire Protection Association.
  • Rivkin, C. H. (2008a). Automotive and marine service station operations. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 21-29–21-40). National Fire Protection Association.
  • Rivkin, C. H. (2008b). Vehicle fueling using gaseous fuels. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 21-41–21-76). National Fire Protection Association.
  • Scarbrough, D. R. (2008a). Control of electrostatic ignition sources. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 11-59–11-68). National Fire Protection Association.
  • Scheffler, G. W., & Collins, W. P. (2008). Fuel cell vehicles. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 21-77–21-89). National Fire Protection Association.
  • Slye, O. M., Jr. (2008). Flammable and combustible liquids. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-197–6-208). National Fire Protection Association.