== Why facilities organise a brigade == | == Why facilities organise a brigade == | ||
Fire and explosion losses can involve property damage, business interruption, harm to people and the environment, damage to the corporate image and lower future profits. Snyder notes that these consequences led many commercial and industrial organisations to develop loss prevention programmes and emergency response organisations.<ref name="Snyder-12-177">Snyder (2008), p. 12-177.</ref> In his framework of [[Fire safety management|fire risk management]], establishing emergency organisations to control fires that do occur is one of three main priorities, next to identifying hazards and managing the identified risks.<ref name="Snyder-12-177" /> A fire sequence event tree in the same chapter shows the brigade as the last line of defence. | Fire and explosion losses can involve property damage, business interruption, harm to people and the environment, damage to the corporate image and lower future profits. Snyder notes that these consequences led many commercial and industrial organisations to develop loss prevention programmes and emergency response organisations.<ref name="Snyder-12-177">Snyder (2008), p. 12-177.</ref> In his framework of [[Fire safety management|fire risk management]], establishing emergency organisations to control fires that do occur is one of three main priorities, next to identifying hazards and managing the identified risks.<ref name="Snyder-12-177" /> A fire sequence event tree in the same chapter shows the brigade as the last line of defence. If detection and emergency controls succeed but automatic suppression fails, the tree branches to the plant brigade: success leads to a moderate controlled fire and failure to a large uncontrolled fire. Failure of detection and emergency controls leads directly to the large-fire branch.<ref name="Snyder-12-179">Snyder (2008), p. 12-179.</ref> | ||
The decision depends strongly on the local public fire service. For storage yards, the availability and ability of the public fire department normally govern the level of organisation, training and equipment of a private brigade. The larger and more valuable the yard, the greater the need for immediate on-site response.<ref name="JMoore-20-176">J. Moore (2008), p. 20-176.</ref> Some electric generating plants are located far from professional or volunteer fire departments, and for these plants a brigade may be necessary.<ref name="Sheridan-9-180" /> | The decision depends strongly on the local public fire service. For storage yards, the availability and ability of the public fire department normally govern the level of organisation, training and equipment of a private brigade. The larger and more valuable the yard, the greater the need for immediate on-site response.<ref name="JMoore-20-176">J. Moore (2008), p. 20-176.</ref> Some electric generating plants are located far from professional or volunteer fire departments, and for these plants a brigade may be necessary.<ref name="Sheridan-9-180" /> | ||
| Line 20: | Line 20: | ||
== Regulation and standards in the United States == | == Regulation and standards in the United States == | ||
OSHA, the [[Occupational Safety and Health Administration]], first addressed fire service occupational safety and health in 1980, when it issued 29 CFR 1910.156, the fire brigades regulations.<ref name="Teele-12-144">Teele (2008), p. 12-144.</ref> Loflin (2008) summarises the standard as containing requirements for personal protective equipment, training, respiratory protection and the use of fire-fighting equipment. He calls it the fire service's introduction to safety and health requirements.<ref name="Loflin-12-109">Loflin (2008), p. 12-109.</ref> For respiratory protection, the standard requires positive-pressure self-contained breathing apparatus certified by the National Institute for Occupational Safety and Health, with a rated service life of at least 30 minutes.<ref name="Teele-12-151">Teele (2008), p. 12-151.</ref> NFPA 1500, the fire department safety and health standard, was written to support this OSHA standard | OSHA, the [[Occupational Safety and Health Administration]], first addressed fire service occupational safety and health in 1980, when it issued 29 CFR 1910.156, the fire brigades regulations.<ref name="Teele-12-144">Teele (2008), p. 12-144.</ref> Loflin (2008) summarises the standard as containing requirements for personal protective equipment, training, respiratory protection and the use of fire-fighting equipment. He calls it the fire service's introduction to safety and health requirements.<ref name="Loflin-12-109">Loflin (2008), p. 12-109.</ref> For respiratory protection, the standard requires positive-pressure self-contained breathing apparatus certified by the National Institute for Occupational Safety and Health, with a rated service life of at least 30 minutes.<ref name="Teele-12-151">Teele (2008), p. 12-151.</ref> NFPA 1500, the fire department safety and health standard, was written to support this OSHA standard.<ref name="Denlinger-12-60">Denlinger (2008), p. 12-60.</ref> Teele (2008) notes that federal OSHA regulations did not apply to state and local government employees, while federally approved state OSHA plans had to cover them.<ref name="Teele-12-144" /> | ||
The NFPA documents set out the content of a brigade programme. NFPA 600 and OSHA Subpart L give management a choice of fire-fighting capability levels. NFPA 1081 defines the roles, skill competencies and core job performance requirements of industrial fire brigade members.<ref name="Snyder-12-192" /><ref name="Snyder-12-193" /><ref name="Snyder-12-194">Snyder (2008), p. 12-194.</ref> A brigade | The NFPA documents set out the content of a brigade programme. NFPA 600 and OSHA Subpart L give management a choice of fire-fighting capability levels. NFPA 1081 defines the roles, skill competencies and core job performance requirements of industrial fire brigade members.<ref name="Snyder-12-192" /><ref name="Snyder-12-193" /><ref name="Snyder-12-194">Snyder (2008), p. 12-194.</ref> A brigade assigned to emergency response for hazardous-substance releases falls under the hazardous waste operations and emergency response rule, 29 CFR 1910.120. This rule covers industrial emergency response team members as well as public responders and requires, among other things, a response plan, an incident management system, specific training and medical surveillance.<ref name="HildNoll-13-88">Hildebrand and Noll (2008), p. 13-88.</ref> | ||
== Levels of fire-fighting capability == | == Levels of fire-fighting capability == | ||
| Line 49: | Line 49: | ||
Staffing follows from the duties set in the organisational statement and from the rule that all fire fighting is done in teams. Two fire fighters are needed to operate a mobile 1½ in. (38 mm) hose stream of 75 to 100 gpm (300 to 400 L/min). One such line therefore needs at least five members in full protective equipment: two to fight the fire, two on standby for their rescue, and one incident commander.<ref name="Snyder-12-194" /> Because of vacations, absences and shift schedules, a roster of two to three times the minimum number of responders is usually required.<ref name="Snyder-12-194" /> As an illustration, a facility that wants one hose line available on every shift would thus need a roster of 10 to 15 brigade members. | Staffing follows from the duties set in the organisational statement and from the rule that all fire fighting is done in teams. Two fire fighters are needed to operate a mobile 1½ in. (38 mm) hose stream of 75 to 100 gpm (300 to 400 L/min). One such line therefore needs at least five members in full protective equipment: two to fight the fire, two on standby for their rescue, and one incident commander.<ref name="Snyder-12-194" /> Because of vacations, absences and shift schedules, a roster of two to three times the minimum number of responders is usually required.<ref name="Snyder-12-194" /> As an illustration, a facility that wants one hose line available on every shift would thus need a roster of 10 to 15 brigade members. | ||
Snyder states that no single item is more important to a brigade than a well-organised and well-documented training programme. No member should be expected to perform a duty for which he or she has not been fully trained.<ref name="Snyder-12-194" /> NFPA 600 requires periodic training matched to the type of fire fighting expected, and the right frequency depends on factors such as the fixed systems, outside help and the experience of the members.<ref name="Snyder-12-194" /> Training should simulate the fires actually expected, not only outside oil-pit or scrap-wood fires, and unannounced drills should test the brigade response and the plant's prefire plans.<ref name="Snyder-12-194" /> | Snyder states that no single item is more important to a brigade than a well-organised and well-documented training programme. No member should be expected to perform a duty for which he or she has not been fully trained.<ref name="Snyder-12-194" /> NFPA 600 requires periodic training matched to the type of fire fighting expected, and the right frequency depends on factors such as the fixed systems, outside help and the experience of the members.<ref name="Snyder-12-194" /> Training should simulate the fires actually expected, not only outside oil-pit or scrap-wood fires, and unannounced drills should test the brigade response and the plant's prefire plans.<ref name="Snyder-12-194" /> Snyder advises conducting live fire training in compliance with NFPA 1403 and giving leaders specific training in leadership, fire tactics and the incident management system.<ref name="Snyder-12-194" /><ref name="Snyder-12-195">Snyder (2008), p. 12-195.</ref> Schmidt adds that fire brigades, like hazardous materials and technical rescue teams, need more frequent training than other members of an emergency organisation.<ref name="Schmidt-1-152">Schmidt (2008), p. 1-152.</ref> | ||
== Equipment, pre-incident planning and the public fire department == | == Equipment, pre-incident planning and the public fire department == | ||
Equipment should match the duties of the brigade and the hazards it will face. A fire truck is often not needed, because many industrial sites already have large quantities of water at fairly high pressure. What is needed is a reasonable distribution of yard hydrants and hose houses, interior standpipes and a way of carrying additional hose. Members who fight fires beyond the incipient stage also need protective "turnout" gear with hoods.<ref name="Snyder-12-195" /> Breathing apparatus, spare air cylinders, two-way radios and salvage equipment complete the list, and members should inspect all equipment as part of their routine training.<ref name="Snyder-12-195" /><ref name="Snyder-12-196">Snyder (2008), p. 12-196.</ref> | Equipment should match the duties of the brigade and the hazards it will face. A fire truck is often not needed, because many industrial sites already have large quantities of water at fairly high pressure. What is needed is a reasonable distribution of yard hydrants and hose houses, interior standpipes and a way of carrying additional hose. Members who fight fires beyond the incipient stage also need protective "turnout" gear with hoods.<ref name="Snyder-12-195" /> Breathing apparatus, spare air cylinders, two-way radios and salvage equipment complete the list, and members should inspect all equipment as part of their routine training.<ref name="Snyder-12-195" /><ref name="Snyder-12-196">Snyder (2008), p. 12-196.</ref> | ||
Some building systems are designed with brigades in mind. Class II standpipes, with 1½ in. (40 mm) hose for first-aid fire fighting, are generally intended for trained fire brigades before the fire department arrives. The 2007 edition of NFPA 14 refers to "Trained Industrial Fire Brigades" rather than to building occupants.<ref name="Hague-16-192">Hague (2008b), p. 16-192.</ref> | |||
[[Pre-incident planning|Pre-incident plans]] should be developed for each building in a format that is useful to both the facility brigade and the municipal fire service.<ref name="Snyder-12-195" /> Among other items, they cover the layout and access routes, construction features, operations and hazards, and water supplies and fixed protection. They also describe the drainage of firewater, communications with the public fire department and the tactics the brigade should use.<ref name="Snyder-12-195" /> Serapiglia (2008) calls the pre-incident plan one of the most valuable tools for helping both the fire department and an on-site brigade to control an emergency.<ref name="Serapiglia-12-289">Serapiglia (2008), p. 12-289.</ref> | [[Pre-incident planning|Pre-incident plans]] should be developed for each building in a format that is useful to both the facility brigade and the municipal fire service.<ref name="Snyder-12-195" /> Among other items, they cover the layout and access routes, construction features, operations and hazards, and water supplies and fixed protection. They also describe the drainage of firewater, communications with the public fire department and the tactics the brigade should use.<ref name="Snyder-12-195" /> Serapiglia (2008) calls the pre-incident plan one of the most valuable tools for helping both the fire department and an on-site brigade to control an emergency.<ref name="Serapiglia-12-289">Serapiglia (2008), p. 12-289.</ref> | ||
| Line 76: | Line 76: | ||
| <math>\lambda</math> || Mean suppression rate for the type of fire, from fire event data || 1/min | | <math>\lambda</math> || Mean suppression rate for the type of fire, from fire event data || 1/min | ||
|- | |- | ||
| <math>C_s</math> || Scenario-specific adjustment factor; 1 | | <math>C_s</math> || Scenario-specific adjustment factor; 1 when the scenario response equals the plant's typical response || – | ||
|- | |- | ||
| <math>T_{fb,s}</math> || Mean fire brigade response time for the scenario analysed || min | | <math>T_{fb,s}</math> || Mean fire brigade response time for the scenario analysed || min | ||
| Line 83: | Line 83: | ||
|} | |} | ||
The rates come from a reanalysis that began with 250 manually suppressed fires in US nuclear plants; four events were removed from the revised curves.<ref name="Hyslop-14-5-6">Hyslop et al. (2010), pp. 14-5–14-6.</ref> They range from 0.33 per minute for control room fires to 0.025 per minute for turbine-generator fires, with 0.102 per minute for electrical fires.<ref name="Hyslop-14-11">Hyslop et al. (2010), p. 14-11.</ref> The adjustment factor | The rates come from a reanalysis that began with 250 manually suppressed fires in US nuclear plants; four events were removed from the revised curves.<ref name="Hyslop-14-5-6">Hyslop et al. (2010), pp. 14-5–14-6.</ref> They range from 0.33 per minute for control room fires to 0.025 per minute for turbine-generator fires, with 0.102 per minute for electrical fires.<ref name="Hyslop-14-11">Hyslop et al. (2010), p. 14-11.</ref> The adjustment factor may be used when the scenario's brigade response differs by more than 5 minutes from the plant's typical response, and it was derived empirically, not from first principles.<ref name="Hyslop-14-4" /><ref name="Hyslop-14-7">Hyslop et al. (2010), p. 14-7.</ref> | ||
As an illustration, for an electrical fire with 15 minutes available, <math>P_{ns} = \exp(-0.102 \times 15) \approx 0.22</math>, close to the tabulated 0.218.<ref name="Hyslop-14-10">Hyslop et al. (2010), p. 14-10.</ref> As an illustration, if the brigade needs 20 minutes to reach a hard-to-access location instead of a typical 10 minutes, <math>C_s = 1 - 10/30 \approx 0.67</math>. The non-suppression probability then rises to about 0.36. The reanalysis also showed that many fires were put out before the brigade arrived in full, and nearly half were detected by plant personnel.<ref name="Hyslop-14-8">Hyslop et al. (2010), p. 14-8.</ref> | |||
The Eurocode method of structural fire design can credit a brigade in a different way. Lane (2008) describes the time-equivalent method of Eurocode 1, Part 1-2. In it, the design fire load density is the characteristic fire load density multiplied by a combustion factor and by factors for compartment size, occupancy and active fire-fighting measures:<ref name="Lane-19-82">Lane (2008), p. 19-82.</ref> | |||
<math display="block">q_{f,d} = q_{f,k}\, m\, \delta_{q1}\, \delta_{q2}\, \delta_n</math> | <math display="block">q_{f,d} = q_{f,k}\, m\, \delta_{q1}\, \delta_{q2}\, \delta_n</math> | ||
| Line 100: | Line 100: | ||
Industrial fire fighting carries its own hazards. In a fire in a sprinklered paper mill warehouse in Idaho, bales of scrap paper that had absorbed water collapsed on the crews. Three members of the industrial fire department and two other employees died, and seven other brigade members were injured.<ref name="JMoore-20-173" /> | Industrial fire fighting carries its own hazards. In a fire in a sprinklered paper mill warehouse in Idaho, bales of scrap paper that had absorbed water collapsed on the crews. Three members of the industrial fire department and two other employees died, and seven other brigade members were injured.<ref name="JMoore-20-173" /> | ||
The NFPA national estimates cover fires reported to municipal fire departments and therefore exclude fires reported only to industrial fire brigades.<ref name="HallCote-3-14">Hall and Cote (2008), p. 3-14.</ref> As Hall and Ahrens (2002) note, high-hazard occupancies are more likely to have their own brigades, so this gap is not random.<ref name="HallAhrens-5-70">Hall and Ahrens (2002), p. 5-70.</ref> All requirements quoted in this article are US rules and NFPA documents as described between 2004 and 2010, apart from the Eurocode, Dutch and international examples named as such. | |||
== See also == | == See also == | ||
Revision as of 00:01, 8 November 2026
An industrial fire brigade is a private fire-fighting organisation made up of the employees of a plant or other facility. The owner creates, equips and trains it to deal with fires and related emergencies on its own site. In the NFPA Fire Protection Handbook (2008), Snyder describes such private fire brigades as one of the most important parts of a facility's emergency organisation.[1] A brigade backs up automatic fire protection, fights fires manually, helps with evacuation and salvage, and plans with the public fire department that will respond to the site.[2]
In the United States, fire fighting by employees is not required by OSHA standards or the model fire prevention codes. A facility that chooses to organise a brigade must, however, comply with the OSHA fire brigade standard, 29 CFR 1910.156, and should follow NFPA 600, Standard on Industrial Fire Brigades.[3] Brigades range from teams that attack only small, beginning fires with extinguishers to brigades equipped for interior structural fire fighting with breathing apparatus.[4] This article describes mainly US practice as reported in 2004 to 2010, with European and other examples where the sources give them.
Definition and terminology
Snyder (2008) uses "private fire brigades" and "industrial fire brigades" for the same thing: an organised group of facility employees for fire fighting.[1] Other chapters of the handbook speak of a "plant fire brigade", an "in-plant fire protection force" for nuclear facilities, an "industrial fire department" or a dedicated "emergency response team".[5][6][7][8] The word "brigade" on its own can mislead. In British usage, as reflected in the handbook's description of UK fire data, the public fire departments themselves are called fire brigades.[9]
The brigade is one part of a wider emergency organisation. Schmidt (2008) explains that a facility far from public emergency services, or one where response time is excessive or the public responders' capabilities are limited, needs trained personnel of its own. Their tasks can range from first aid and spill containment to fire fighting, rescue and hazardous materials response.[3] Fire prevention codes require industrial facilities and several other occupancies to have fire emergency plans and trained personnel, and many jurisdictions have adopted stricter rules for fire safety teams and emergency action plans.[3] The leader of the emergency response team also serves as incident commander and must have the authority to order evacuation without delay.[10]
Similar in-house teams exist outside industry. In New York City, the building code provisions for the fire safety plan of office buildings, as summarised by Grill and Johnson (2005b), required a fire safety director with a certificate of fitness. This person organises, trains and supervises a fire brigade selected from qualified building service employees, under fire department control during emergencies.[11] At the World Trade Center towers before 2001, members of the Port Authority Police with firefighting training staffed the complex's fire brigade.[12] In the Netherlands, a guidance report on car parks notes that quick action after an alarm depends on proper follow-up by an in-house emergency responder or a residents' organisation.[13] Introduction to Fire Safety Engineering adds that the way management treats the in-company emergency response organisation, seriously or as a necessary evil, influences how people behave before they evacuate.[14]
Why facilities organise a brigade
Fire and explosion losses can involve property damage, business interruption, harm to people and the environment, damage to the corporate image and lower future profits. Snyder notes that these consequences led many commercial and industrial organisations to develop loss prevention programmes and emergency response organisations.[15] In his framework of fire risk management, establishing emergency organisations to control fires that do occur is one of three main priorities, next to identifying hazards and managing the identified risks.[15] A fire sequence event tree in the same chapter shows the brigade as the last line of defence. If detection and emergency controls succeed but automatic suppression fails, the tree branches to the plant brigade: success leads to a moderate controlled fire and failure to a large uncontrolled fire. Failure of detection and emergency controls leads directly to the large-fire branch.[16]
The decision depends strongly on the local public fire service. For storage yards, the availability and ability of the public fire department normally govern the level of organisation, training and equipment of a private brigade. The larger and more valuable the yard, the greater the need for immediate on-site response.[17] Some electric generating plants are located far from professional or volunteer fire departments, and for these plants a brigade may be necessary.[5]
For facilities with nuclear reactors or radioactive materials, Holmes (2008a) recommends an in-plant fire protection force with 24-hour routines, because decisions on such fires cannot be solved by simply calling the public fire department.[6] Mineral processing sites are usually remote. Larger sites there have dedicated emergency response teams with structural fire apparatus such as pumpers, while smaller sites may have only basic brigades.[8]
Snyder lists the questions management typically asks before starting a programme. They concern what the brigade will cost, how much training time employees need, who will train them and how all shifts will be covered. They also ask whether trained members will make fires less likely, fight them more safely and reduce property loss through prompt action.[1] He adds that a brigade makes a contribution that is often overlooked: assurance that detection and suppression systems are functional and ready for use. Developing the brigade also raises employees' awareness of fire safety.[18]
Regulation and standards in the United States
OSHA, the Occupational Safety and Health Administration, first addressed fire service occupational safety and health in 1980, when it issued 29 CFR 1910.156, the fire brigades regulations.[19] Loflin (2008) summarises the standard as containing requirements for personal protective equipment, training, respiratory protection and the use of fire-fighting equipment. He calls it the fire service's introduction to safety and health requirements.[20] For respiratory protection, the standard requires positive-pressure self-contained breathing apparatus certified by the National Institute for Occupational Safety and Health, with a rated service life of at least 30 minutes.[21] NFPA 1500, the fire department safety and health standard, was written to support this OSHA standard.[22] Teele (2008) notes that federal OSHA regulations did not apply to state and local government employees, while federally approved state OSHA plans had to cover them.[19]
The NFPA documents set out the content of a brigade programme. NFPA 600 and OSHA Subpart L give management a choice of fire-fighting capability levels. NFPA 1081 defines the roles, skill competencies and core job performance requirements of industrial fire brigade members.[1][4][23] A brigade assigned to emergency response for hazardous-substance releases falls under the hazardous waste operations and emergency response rule, 29 CFR 1910.120. This rule covers industrial emergency response team members as well as public responders and requires, among other things, a response plan, an incident management system, specific training and medical surveillance.[24]
Levels of fire-fighting capability
Snyder (2008) describes five options for the fire-fighting capability of a facility, based on OSHA Subpart L and NFPA 600. Options 2 to 4 deal with incipient fires: fires in their initial stage that can be controlled or extinguished safely with portable extinguishers, small standpipe hose or similar equipment, without protective clothing or breathing apparatus.[4]
| Option | Who fights fire | Main requirements |
|---|---|---|
| 1 | No employee; everyone evacuates | Assets protected by fixed fire protection systems and/or the local fire department |
| 2 | All employees, incipient fires only | Training at least annually in the use of fire extinguishers |
| 3 | Designated employees, incipient fires only | Same training as option 2, given to selected employees |
| 4 | Organised industrial fire brigade, incipient fires | Written organisational statement with leadership, procedures, training and equipment; leaders trained beyond members; hands-on training every year |
| 5 | Organised industrial fire brigade, fires beyond the incipient stage | Physical fitness assessment, protective clothing, positive-pressure breathing apparatus, quarterly training with yearly hands-on training; NFPA 600 requirements for advanced exterior and/or interior structural fire fighting |
Management should choose an option from a needs assessment that considers the hazards, the existing prevention and automatic protection, and the availability and adequacy of the public fire department.[4] According to Snyder, a facility that would benefit from a brigade often does not need option 5 and would probably find it financially difficult to support one. A well-trained incipient brigade is relatively easy to develop and maintain, and its closeness to potential fires and its vested interest in the property make it an excellent loss control resource. Many large facilities, however, need a brigade that can fight fires beyond the incipient stage.[4] Some tasks demand that higher level. Sheridan (2008) warns that applying special agents to burning coal in power plant silos is inherently dangerous and should be left to the owner's structural brigade and the local fire department, not to incipient brigades.[25]
Organisation, staffing and training
A brigade starts with a written organisational statement that establishes its existence, structure, training and functions and the expected number of members.[26] In a typical brigade, the fire brigade chief has overall responsibility for training, equipment, procedures and maintenance. Assistant chiefs are the senior officers on each shift and usually act as incident commanders, while captains direct crews in rescue, suppression, salvage and overhaul. Command is exercised through an incident management system in line with NFPA 1561.[4] Members need suitable physical, mental and emotional qualifications and must be available to respond, which their normal job assignment affects. Support members such as electricians, pipe fitters and pump operators isolate power, operate valves and keep fire pumps running.[4][23]
Staffing follows from the duties set in the organisational statement and from the rule that all fire fighting is done in teams. Two fire fighters are needed to operate a mobile 1½ in. (38 mm) hose stream of 75 to 100 gpm (300 to 400 L/min). One such line therefore needs at least five members in full protective equipment: two to fight the fire, two on standby for their rescue, and one incident commander.[23] Because of vacations, absences and shift schedules, a roster of two to three times the minimum number of responders is usually required.[23] As an illustration, a facility that wants one hose line available on every shift would thus need a roster of 10 to 15 brigade members.
Snyder states that no single item is more important to a brigade than a well-organised and well-documented training programme. No member should be expected to perform a duty for which he or she has not been fully trained.[23] NFPA 600 requires periodic training matched to the type of fire fighting expected, and the right frequency depends on factors such as the fixed systems, outside help and the experience of the members.[23] Training should simulate the fires actually expected, not only outside oil-pit or scrap-wood fires, and unannounced drills should test the brigade response and the plant's prefire plans.[23] Snyder advises conducting live fire training in compliance with NFPA 1403 and giving leaders specific training in leadership, fire tactics and the incident management system.[23][27] Schmidt adds that fire brigades, like hazardous materials and technical rescue teams, need more frequent training than other members of an emergency organisation.[28]
Equipment, pre-incident planning and the public fire department
Equipment should match the duties of the brigade and the hazards it will face. A fire truck is often not needed, because many industrial sites already have large quantities of water at fairly high pressure. What is needed is a reasonable distribution of yard hydrants and hose houses, interior standpipes and a way of carrying additional hose. Members who fight fires beyond the incipient stage also need protective "turnout" gear with hoods.[27] Breathing apparatus, spare air cylinders, two-way radios and salvage equipment complete the list, and members should inspect all equipment as part of their routine training.[27][29]
Some building systems are designed with brigades in mind. Class II standpipes, with 1½ in. (40 mm) hose for first-aid fire fighting, are generally intended for trained fire brigades before the fire department arrives. The 2007 edition of NFPA 14 refers to "Trained Industrial Fire Brigades" rather than to building occupants.[30]
Pre-incident plans should be developed for each building in a format that is useful to both the facility brigade and the municipal fire service.[27] Among other items, they cover the layout and access routes, construction features, operations and hazards, and water supplies and fixed protection. They also describe the drainage of firewater, communications with the public fire department and the tactics the brigade should use.[27] Serapiglia (2008) calls the pre-incident plan one of the most valuable tools for helping both the fire department and an on-site brigade to control an emergency.[31]
However capable the brigade, Snyder considers it good practice to include the public fire department in pre-incident planning. The facility should realistically evaluate the assistance available, including response times that may vary with the time of day in volunteer departments. It should also check the compatibility of radio frequencies, breathing apparatus cylinders and hose threads.[29]
Management should not assume that local fire fighters have experience in industrial fire fighting; the plant may even need to supplement their training. Legal relationships and mutual assistance agreements must be settled where the plant lies outside a fire department's jurisdiction, and the plan must define who commands the combined effort.[29][18] For hazardous materials response, a brigade may have no role, act only as a first responder that recognises the hazard and secures the area, or serve as a full hazmat team. Because of training time and equipment cost, a facility may be financially unable to keep a brigade at that last level.[18]
Brigades in risk analysis and fire engineering
Fire risk analyses treat the brigade as one of several protection layers. For US nuclear power plants, NUREG-1805 counts fire brigades among the second element of defence in depth, next to detection and fixed suppression systems.[32] It also notes that human response, including the discovery of a fire and the travel time of the brigade, usually takes much longer than automatic sprinklers need to control an early fire.[33] The fire probabilistic risk assessment method NUREG/CR-6850 assesses the brigade from scenario-specific response times and historical suppression times.[34] Its 2010 supplement expresses manual suppression, by the brigade and by other plant personnel together, as a probability that the fire is not yet suppressed at time :[35][36]
| Symbol | Description | Unit |
|---|---|---|
| Probability that the fire has not been suppressed by time | – | |
| Time available for suppression: estimated time to target damage minus time to detection | min | |
| Mean suppression rate for the type of fire, from fire event data | 1/min | |
| Scenario-specific adjustment factor; 1 when the scenario response equals the plant's typical response | – | |
| Mean fire brigade response time for the scenario analysed | min | |
| Mean typical fire brigade response time at the plant | min |
The rates come from a reanalysis that began with 250 manually suppressed fires in US nuclear plants; four events were removed from the revised curves.[37] They range from 0.33 per minute for control room fires to 0.025 per minute for turbine-generator fires, with 0.102 per minute for electrical fires.[38] The adjustment factor may be used when the scenario's brigade response differs by more than 5 minutes from the plant's typical response, and it was derived empirically, not from first principles.[36][39]
As an illustration, for an electrical fire with 15 minutes available, , close to the tabulated 0.218.[40] As an illustration, if the brigade needs 20 minutes to reach a hard-to-access location instead of a typical 10 minutes, . The non-suppression probability then rises to about 0.36. The reanalysis also showed that many fires were put out before the brigade arrived in full, and nearly half were detected by plant personnel.[41]
The Eurocode method of structural fire design can credit a brigade in a different way. Lane (2008) describes the time-equivalent method of Eurocode 1, Part 1-2. In it, the design fire load density is the characteristic fire load density multiplied by a combustion factor and by factors for compartment size, occupancy and active fire-fighting measures:[42]
Here is the product of factors for measures such as sprinklers, detection and fire brigades. Table 19.5.4 of the handbook gives 0.61 for a work (on-site) fire brigade or 0.78 for an off-site fire brigade.[43][44] As an illustration with values from the same tables, consider an office compartment of 250 m² with MJ/m² (80 % fractile), , and .[45] Without brigade credit, is about 613 MJ/m². With an off-site brigade it falls to about 478 MJ/m², and with a works brigade to about 374 MJ/m².
In the International Fire Engineering Guidelines (2005), private industrial fire crews can likewise be included in the sub-systems for fire suppression and fire service intervention. In many fire engineering evaluations, the guidelines note, the effect of fire service intervention is not taken into account at all. They add that the evacuation analysis should not rely on fire service intervention.[46][47]
Limitations and safety lessons
A brigade depends on people being present and available. Sheridan notes a trend in electric generating plants to reduce operating staff, which shrinks the pool of qualified brigade members; some smaller plants operate unmanned or with as few as three people per shift.[5] In mining, quickly marshalling enough brigade members for a large fire could be a problem.[48] The analysts of NUREG/CR-6850 regard fire brigade practices, such as reliance on a brigade instead of a dedicated fire department, as issues that may affect fire risk but that cannot be quantified with current knowledge.[49]
Industrial fire fighting carries its own hazards. In a fire in a sprinklered paper mill warehouse in Idaho, bales of scrap paper that had absorbed water collapsed on the crews. Three members of the industrial fire department and two other employees died, and seven other brigade members were injured.[7]
The NFPA national estimates cover fires reported to municipal fire departments and therefore exclude fires reported only to industrial fire brigades.[50] As Hall and Ahrens (2002) note, high-hazard occupancies are more likely to have their own brigades, so this gap is not random.[51] All requirements quoted in this article are US rules and NFPA documents as described between 2004 and 2010, apart from the Eurocode, Dutch and international examples named as such.
See also
- Fire department organisation
- Mutual aid
- Incident command system
- Fire service training
- Self-contained breathing apparatus
Notes
- ↑ 1.0 1.1 1.2 1.3 Snyder (2008), p. 12-192.
- ↑ Snyder (2008), p. 12-180.
- ↑ 3.0 3.1 3.2 Schmidt (2008), p. 1-145.
- ↑ 4.0 4.1 4.2 4.3 4.4 4.5 4.6 Snyder (2008), p. 12-193.
- ↑ 5.0 5.1 5.2 Sheridan (2008), p. 9-180.
- ↑ 6.0 6.1 Holmes (2008a), p. 9-199.
- ↑ 7.0 7.1 J. Moore (2008), pp. 20-173–20-174.
- ↑ 8.0 8.1 L. J. Moore (2008), p. 9-221.
- ↑ Ahrens and Stewart (2008), p. 3-58.
- ↑ Schmidt (2008), p. 1-144.
- ↑ Grill and Johnson (2005b), p. 125.
- ↑ Evans et al. (2005), p. 62.
- ↑ Van der Graaf et al. (2021/2023), p. 37.
- ↑ Van Rossum (2027), §7.3.
- ↑ 15.0 15.1 Snyder (2008), p. 12-177.
- ↑ Snyder (2008), p. 12-179.
- ↑ J. Moore (2008), p. 20-176.
- ↑ 18.0 18.1 18.2 Snyder (2008), p. 12-197.
- ↑ 19.0 19.1 Teele (2008), p. 12-144.
- ↑ Loflin (2008), p. 12-109.
- ↑ Teele (2008), p. 12-151.
- ↑ Denlinger (2008), p. 12-60.
- ↑ 23.0 23.1 23.2 23.3 23.4 23.5 23.6 23.7 Snyder (2008), p. 12-194.
- ↑ Hildebrand and Noll (2008), p. 13-88.
- ↑ Sheridan (2008), p. 9-183.
- ↑ Schmidt (2008), p. 1-146.
- ↑ 27.0 27.1 27.2 27.3 27.4 Snyder (2008), p. 12-195.
- ↑ Schmidt (2008), p. 1-152.
- ↑ 29.0 29.1 29.2 Snyder (2008), p. 12-196.
- ↑ Hague (2008b), p. 16-192.
- ↑ Serapiglia (2008), p. 12-289.
- ↑ Iqbal and Salley (2004), p. 1-2.
- ↑ Iqbal and Salley (2004), p. 10-1.
- ↑ Nowlen et al. (2005a), p. 3-5.
- ↑ Hyslop et al. (2010), pp. 14-1–14-2.
- ↑ 36.0 36.1 Hyslop et al. (2010), p. 14-4.
- ↑ Hyslop et al. (2010), pp. 14-5–14-6.
- ↑ Hyslop et al. (2010), p. 14-11.
- ↑ Hyslop et al. (2010), p. 14-7.
- ↑ Hyslop et al. (2010), p. 14-10.
- ↑ Hyslop et al. (2010), p. 14-8.
- ↑ Lane (2008), p. 19-82.
- ↑ Lane (2008), p. 19-84.
- ↑ Cadorin et al. (2003), p. 446.
- ↑ Lane (2008), p. 19-83.
- ↑ National Research Council of Canada et al. (2005), p. 1.4-6.
- ↑ National Research Council of Canada et al. (2005), p. 1.9-1.
- ↑ L. J. Moore (2008), p. 9-213.
- ↑ Nowlen et al. (2005a), p. 3-10.
- ↑ Hall and Cote (2008), p. 3-14.
- ↑ Hall and Ahrens (2002), p. 5-70.
References
- Ahrens, M., & Stewart, S. (2008). Fire data collection and databases. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 3-43–3-59). National Fire Protection Association.
- Cadorin, J.-F., Pintea, D., Dotreppe, J.-C., & Franssen, J.-M. (2003). A tool to design steel elements submitted to compartment fires–OZone V2. Part 2: Methodology and application. Fire Safety Journal, 38, 429–451. https://doi.org/10.1016/S0379-7112(03)00015-8
- Denlinger, R. F. (2008). Managing fire-rescue departments. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 12-51–12-78). National Fire Protection Association.
- Evans, D. D., Peacock, R. D., Kuligowski, E. D., Dols, W. S., & Grosshandler, W. L. (2005). Active fire protection systems (NIST NCSTAR 1-4). National Institute of Standards and Technology.
- Grill, R. A., & Johnson, D. A. (2005b). Fire protection and life safety provisions applied to the design and construction of WTC 1, 2, and 7 and post-construction provisions applied after occupancy (NIST NCSTAR 1-1D). National Institute of Standards and Technology.
- Hague, D. R. (2008b). Standpipe and hose systems. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 16-191–16-204). National Fire Protection Association.
- Hall, J. R., Jr., & Ahrens, M. J. (2002). Data for engineering analysis. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 5-65–5-78). National Fire Protection Association; Society of Fire Protection Engineers.
- Hall, J. R., Jr., & Cote, A. E. (2008). An overview of the fire problem and fire protection. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 3-3–3-30). National Fire Protection Association.
- Hildebrand, M. S., & Noll, G. G. (2008). Public fire protection and hazmat management. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 13-81–13-98). National Fire Protection Association.
- Holmes, W. D. (2008a). Nuclear facilities. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-191–9-201). National Fire Protection Association.
- Hyslop, J. S., Kratchman, J., Siu, N., Afshar, C., Najafi, B., Joglar, F., Li, Y., Henneke, D., & Warner, M. (2010). Fire probabilistic risk assessment methods enhancements: Supplement 1 to NUREG/CR-6850 and EPRI 1011989 (NUREG/CR-6850, Supplement 1; EPRI 1019259). Electric Power Research Institute; U.S. Nuclear Regulatory Commission, Office of Nuclear Regulatory Research.
- Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.
- Lane, B. (2008). Approaches to calculating structural fire resistance. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 19-77–19-126). National Fire Protection Association.
- Loflin, M. E. (2008). Safety, medical, and health issues and programs. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 12-107–12-125). National Fire Protection Association.
- Moore, J. (2008). Storage occupancies. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 20-157–20-178). National Fire Protection Association.
- Moore, L. J. (2008). Mining and mineral processing. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-203–9-223). National Fire Protection Association.
- National Research Council of Canada, International Code Council, Department of Building and Housing, & Australian Building Codes Board. (2005). International fire engineering guidelines (2005 ed.). Australian Building Codes Board.
- Nowlen, S. P., Najafi, B., Wyant, F. J., Forester, J., Kazarians, M., Kolaczkowski, A., Joglar, F., Funk, D., Hannaman, G., & Anoba, R. (2005a). EPRI/NRC-RES fire PRA methodology for nuclear power facilities: Vol. 1. Summary and overview (NUREG/CR-6850; EPRI 1011989). Electric Power Research Institute; U.S. Nuclear Regulatory Commission, Office of Nuclear Regulatory Research.
- Schmidt, D. L. (2008). Emergency management and business continuity. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 1-137–1-156). National Fire Protection Association.
- Serapiglia, M. J. (2008). Pre-Incident planning for industrial and municipal emergency response. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 12-289–12-298). National Fire Protection Association.
- Sheridan, D. J. (2008). Electric generating plants. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-179–9-189). National Fire Protection Association.
- Snyder, M. (2008). Industrial fire loss prevention. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 12-177–12-198). National Fire Protection Association.
- Teele, B. W. (2008). Fire and emergency services protective clothing and protective equipment. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 12-143–12-160). National Fire Protection Association.
- Van der Graaf, J., Hessels, T., & Rosmuller, N. (2023). Fire safety of indoor car parks accommodating electrically powered vehicles. Nederlands Instituut Publieke Veiligheid. (Original work published 2021)
- Van Rossum, E. (2027). Introduction to Fire Safety Engineering. Fire Safety Academy.