'''NFPA 30''', the ''Flammable and Combustible Liquids Code'', is the code of the [[NFPA|National Fire Protection Association]] (NFPA) used in the United States to regulate the safety of flammable and combustible liquids.<ref name="Ordile-7-16">Ordile (2008), p. 7-16.</ref><ref name="Snyder-12-184">Snyder (2008), p. 12-184.</ref> It contains requirements for tank storage, piping systems, containers and operations, and its container-storage sections set the criteria for fire suppression systems.<ref name="Scheffey02-4-113">Scheffey (2002), p. 4-113.</ref> The code sorts liquids into classes by their [[flash point]], and many of its limits depend on that class.<ref name="Slye-6-198">Slye (2008), p. 6-198.</ref><ref name="Ordile-7-18-30">Ordile (2008), pp. 7-18–7-30.</ref>
'''NFPA 30''', the ''Flammable and Combustible Liquids Code'', is the code of the [[NFPA|National Fire Protection Association]] (NFPA) used in the United States to regulate the safety of flammable and combustible liquids.<ref name="Ordile-7-16">Ordile (2008), p. 7-16.</ref><ref name="Snyder-12-184">Snyder (2008), p. 12-184.</ref> It contains requirements for tank storage, piping systems, containers and operations, and its container-storage sections set the criteria for fire suppression systems.<ref name="Scheffey02-4-113">Scheffey (2002), p. 4-113.</ref> The code sorts liquids into classes by their [[flash point]], and many of its limits depend on that class.<ref name="Slye-6-198">Slye (2008), p. 6-198.</ref><ref name="Ordile-7-18-30">Ordile (2008), pp. 7-18–7-30.</ref>


Like other NFPA standards, NFPA 30 is a voluntary consensus document that has the force of law only where a government adopts it. The US Occupational Safety and Health Administration (OSHA) rules on flammable and combustible liquids adopt it by reference.<ref name="HN-13-94">Hildebrand and Noll (2008), p. 13-94.</ref> It is also one of the NFPA standards that US states and local jurisdictions adopt most often.<ref name="Snyder-12-184" /> The sources used here describe the code second-hand. The ''Fire Protection Handbook'' (2008) reproduces tables of the 2003 edition, and a 2004 report of the US Nuclear Regulatory Commission quotes the 2000 edition.<ref name="Ordile-7-28">Ordile (2008), p. 7-28.</ref><ref name="IS-B-17">Iqbal and Salley (2004), pp. B-17–B-18.</ref> The values in this article therefore describe US practice of around 2000 to 2008, not current or universal requirements.
Like other NFPA standards, NFPA 30 is a voluntary consensus document that has the force of law only where a government adopts it. According to Hildebrand and Noll (2008), the rules of the US Occupational Safety and Health Administration (OSHA) on flammable and combustible liquids then in force adopted it by reference.<ref name="HN-13-94">Hildebrand and Noll (2008), p. 13-94.</ref> It is also one of the NFPA standards that US states and local jurisdictions adopt most often.<ref name="Snyder-12-184" /> The ''Fire Protection Handbook'' (2008) reproduces tables of the 2003 edition, and a 2004 report of the US Nuclear Regulatory Commission quotes the 2000 edition.<ref name="Ordile-7-28">Ordile (2008), p. 7-28.</ref><ref name="IS-B-17">Iqbal and Salley (2004), pp. B-17–B-18.</ref> The values in this article therefore describe US practice of around 2000 to 2008, not current or universal requirements.


== Scope and legal status ==
== Scope and legal status ==
Scheffey (2002) calls NFPA 30 the applicable NFPA protection document for stored flammable and combustible liquids. This covers retail outlets, general-purpose warehouses and dedicated liquid warehouses.<ref name="Scheffey02-4-113" /> In his handbook chapter on liquid storage, Ordile (2008) refers to NFPA 30 for aboveground, underground and indoor tanks, for vaults, for container storage and for bulk transfer at wharves.<ref name="Ordile-7-18-30" />
Scheffey (2002) calls NFPA 30 the applicable NFPA protection document for stored flammable and combustible liquids. This covers retail outlets, general-purpose warehouses and dedicated liquid warehouses.<ref name="Scheffey02-4-113" />


NFPA has more than 60 consensus standards related to hazardous materials, and none of them has the force of law unless a government agency adopts it.<ref name="HN-13-94" /> Hildebrand and Noll (2008) give NFPA 30 as the example: the OSHA regulations on flammable and combustible liquids adopt it by reference, so an NFPA document becomes law through adoption. They also note that many US state regulations based on NFPA 30 and NFPA 58 had adopted editions 5 to 10 years older than the current ones.<ref name="HN-13-94" /> Snyder (2008) names NFPA 30 and NFPA 58, the ''Liquefied Petroleum Gas Code'', as the NFPA standards that states and local jurisdictions adopt most commonly as a basis for regulation.<ref name="Snyder-12-184" />
NFPA has more than 60 consensus standards related to hazardous materials, and none of them has the force of law unless a government agency adopts it.<ref name="HN-13-94" /> Hildebrand and Noll (2008) give NFPA 30 as the example: the OSHA regulations on flammable and combustible liquids adopt it by reference, so an NFPA document becomes law through adoption. They also note that many US state regulations based on NFPA 30 and NFPA 58 had adopted editions 5 to 10 years older than the current ones.<ref name="HN-13-94" /> Snyder (2008) names NFPA 30 and NFPA 58, the ''Liquefied Petroleum Gas Code'', among the NFPA standards that states and local jurisdictions adopt most commonly as a basis for regulation.<ref name="Snyder-12-184" />


NFPA 30 also serves as the general document behind several narrower codes. NFPA 31, the standard for oil-burning equipment, covers underground tanks, tanks inside buildings and outside aboveground tanks of up to 2,500 L (660 gal). Larger outside aboveground tanks fall under Chapter 4 of NFPA 30, which is more general and covers liquids with a wider range of flash points in many kinds of occupancy.<ref name="GW-10-15">Gore Willse (2008a), p. 10-15.</ref> For bulk storage plants that hold at least one carload of gasoline or similar liquids, NFPA 30 and Article 515 of the US ''National Electrical Code'' define the [[Hazardous area classification|hazardous (classified) areas]] for electrical equipment.<ref name="Milatovich-8-172">Milatovich (2008), p. 8-172.</ref>
NFPA 30 also serves as the general document behind several narrower codes. As described by Gore Willse (2008a), NFPA 31, the standard for oil-burning equipment, covered underground tanks, tanks inside buildings and outside aboveground tanks of up to 2,500 L (660 gal). Larger outside aboveground tanks fell under Chapter 4 of NFPA 30, which is more general and covers liquids with a wider range of flash points in many kinds of occupancy.<ref name="GW-10-15">Gore Willse (2008a), p. 10-15.</ref> For bulk storage plants holding at least one carload of gasoline or similar liquids, NFPA 30 and Article 515 of the US ''National Electrical Code'' defined the [[Hazardous area classification|hazardous (classified) areas]] for electrical equipment.<ref name="Milatovich-8-172">Milatovich (2008), p. 8-172.</ref>


Before the first edition of NFPA 30B appeared in 1990, aerosol products fell under NFPA 30 and were treated as equivalent to Class IA flammable liquids.<ref name="Fredrickson-6-257">Fredrickson (2008), p. 6-257.</ref> Many users found this excessive, and fire tests in the 1980s showed that some aerosols were far more severe than a Class IA liquid and others far less.<ref name="Fredrickson-6-257" /> The Port Authority's Tenant Construction Review Manual for alterations at the World Trade Center, in use from 1971 to March 1997, also referenced NFPA 30 specifically, next to the New York City building code standards.<ref name="GJ-11-12">Grill and Johnson (2005c), pp. 11–12.</ref>
Before the first edition of NFPA 30B appeared in 1990, aerosol products fell under NFPA 30 and were treated as equivalent to Class IA flammable liquids.<ref name="Fredrickson-6-257">Fredrickson (2008), p. 6-257.</ref> Many users found the resulting protection excessive. Fire tests in the early to mid-1980s showed that some aerosol products presented severe fire hazards, whereas others presented a much lower fire challenge than a Class IA liquid.<ref name="Fredrickson-6-257" /> The Port Authority's Tenant Construction Review Manual, available from 1971 to March 1997 for its facilities including the World Trade Center, also referenced NFPA 30 specifically in its 1997 edition.<ref name="GJ-11-12">Grill and Johnson (2005c), pp. 11–12.</ref>


== Classification of liquids ==
== Classification of liquids ==
Line 33: Line 33:
| IIIB (combustible) || 93 °C (200 °F) and above || not used || mineral oil, olive oil, lubricating oil
| IIIB (combustible) || 93 °C (200 °F) and above || not used || mineral oil, olive oil, lubricating oil
|}
|}
The class limits in the table follow Slye (2008), and the examples follow the 2000 edition as quoted in NUREG-1805.<ref name="Slye-6-198" /><ref name="IS-B-17" /> The system is treated in detail in [[Flammable and combustible liquid classification]]. Some liquids have a flash point but cannot sustain burning. Their fire point is the lowest temperature at which the vapour sustains burning for at least 5 s after a test flame is applied. Codes such as NFPA 30 use it to exempt such liquids from storage limits.<ref name="Slye-6-200">Slye (2008), p. 6-200.</ref> Other classification systems use different break points, the open-cup tester, or the solubility of the liquid in water, so the NFPA 30 classes do not carry over directly to them.<ref name="Slye-6-198" />
The class limits in the table follow Slye (2008), and the examples follow the 2000 edition as quoted in NUREG-1805.<ref name="Slye-6-198" /><ref name="IS-B-17" /> The system is treated in detail in [[Flammable and combustible liquid classification]]. The fire point is the lowest temperature to which a liquid must be heated to give off enough vapour for burning to continue for at least 5 s after a test flame is applied. Codes such as NFPA 30 use it to exempt liquids that have a flash point but cannot sustain burning from storage limits.<ref name="Slye-6-200">Slye (2008), p. 6-200.</ref> Other classification systems use different break points, the open-cup tester, or the solubility of the liquid in water, so the NFPA 30 classes do not carry over directly to them.<ref name="Slye-6-198" />


== Tank storage ==
== Tank storage ==
Ordile (2008) groups tanks by design pressure. [[Atmospheric storage tank|Atmospheric tanks]] are designed for 0 to 6.9 kPa (0 to 1.0 psig), low-pressure tanks for 6.9 to 103 kPa (1.0 to 15 psig) and pressure vessels for more than 103 kPa (15 psig).<ref name="Ordile-7-16" /> The vapour space above the liquid governs the explosion hazard inside a tank. Above liquids with a vapour pressure over 28 kPa (4 psia), such as gasoline, the mixture is normally too rich to burn. Above liquids below about 14 kPa (2 psia), such as kerosene, it is normally too lean. Liquids in between, such as ethyl and methyl alcohol and JP-4 jet fuel, normally have a flammable vapour space.<ref name="Ordile-7-16" />
The tank rules in this section are those of NFPA 30 as described by Ordile (2008) in the 2008 handbook, which does not name the edition it follows.<ref name="Ordile-7-18-30" /> Ordile groups tanks by design pressure. [[Atmospheric storage tank|Atmospheric tanks]] are designed for 0 to 6.9 kPa (0 to 1.0 psig), low-pressure tanks for 6.9 to 103 kPa (1.0 to 15 psig) and pressure vessels for more than 103 kPa (15 psig).<ref name="Ordile-7-16" />


NFPA 30 specifies the distances from aboveground tanks to property lines that can be built on, to public ways and to important buildings, and the spacing between tanks.<ref name="Ordile-7-18">Ordile (2008), p. 7-18.</ref> The distances depend on whether the tank pressure, including the pressure reached during fire exposure, can exceed 17 kPa (2.5 psig). They also depend on whether the liquid is stable, unstable or prone to [[boilover]], on the size and design of the tank and on the protection provided.<ref name="Ordile-7-18" />  
NFPA 30 specifies the distances from aboveground tanks to property lines that can be built on, to public ways and to important buildings, and the spacing between tanks.<ref name="Ordile-7-18">Ordile (2008), p. 7-18.</ref> The distances depend on whether the tank pressure, including the pressure reached during fire exposure, can exceed 17 kPa (2.5 psig). They also depend on whether the liquid is stable, unstable or prone to [[boilover]], on the size and design of the tank and on the protection provided.<ref name="Ordile-7-18" />  


Every tank needs a normal vent for filling, emptying and thermal expansion. It can be sized by the American Petroleum Institute (API) Standard 2000. Otherwise it must be at least as large as the largest filling or withdrawal connection, and never smaller than 32 mm (1.25 in.) nominal inside diameter.<ref name="Ordile-7-18" /> Vapour that would be a hazard is piped to a safe outside point at least 3.7 m (12 ft) above grade. NFPA 30 requires vents that stay closed except under pressure or vacuum for Class IA liquids. Pressure-vacuum vent valves or [[flame arrester]]s are required for all Class I liquids.<ref name="Ordile-7-18" />
Every tank needs a normal vent for filling, emptying and thermal expansion. It can be sized by the American Petroleum Institute (API) Standard 2000. Otherwise it should be at least as large as the largest filling or withdrawal connection, and never smaller than 32 mm (1.25 in.) nominal inside diameter.<ref name="Ordile-7-18" /> Vapour that would be a hazard is piped to a safe outside point at least 3.7 m (12 ft) above grade. NFPA 30 requires vents that stay closed except under pressure or vacuum for Class IA liquids. Pressure-vacuum vent valves or [[flame arrester]]s are required for all Class I liquids.<ref name="Ordile-7-18" />


Spill control is the second main theme. Where a release would endanger important facilities, waterways or neighbouring property, the preferred layout uses sloping ground that drains to a remote impounding basin. There the liquid can burn without exposing other tanks.<ref name="Ordile-7-22">Ordile (2008), p. 7-22.</ref>
Spill control is the second main theme. Where a release would endanger important facilities, waterways or neighbouring property, the preferred layout uses sloping ground that drains to a remote impounding basin. There the liquid can burn without exposing other tanks.<ref name="Ordile-7-22">Ordile (2008), p. 7-22.</ref>
Line 53: Line 53:


== Emergency venting of tanks ==
== Emergency venting of tanks ==
A tank exposed to a fire under or around it needs emergency pressure relief in addition to its normal vent. Without it, high internal pressures can build up and sometimes cause an explosion.<ref name="Ordile-7-20">Ordile (2008), p. 7-20.</ref> The required relief rate depends on the wetted area. This is the part of the tank wall in contact with the liquid that a ground fire would heat.<ref name="Ordile-7-20" />
As in the previous section, the venting rules are those of NFPA 30 as described in the 2008 handbook.<ref name="Ordile-7-21" /> Most aboveground tanks need emergency relief of internal pressure, in addition to the normal vent, in case a fire occurs under or around them; a floating roof removes this need.<ref name="Ordile-7-20" /> Without such relief, high internal pressures can build up and sometimes cause an explosion.<ref name="Ordile-7-20">Ordile (2008), p. 7-20.</ref> The required relief rate depends on the wetted area. This is the part of the tank wall in contact with the liquid that a ground fire would heat.<ref name="Ordile-7-20" />


For a sphere or spheroid it is 55 % of the exposed area, and for a horizontal tank 75 %. For a vertical tank it is the exposed shell over the first 9 m (30 ft) above grade.<ref name="Ordile-7-20" /> Ordile tabulates the required venting as free air at 101 kPa and 15.5 °C for wetted areas up to 260 m² (2,800 ft²), with interpolation between rows.<ref name="Ordile-7-21">Ordile (2008), p. 7-21.</ref>
For a sphere or spheroid it is 55 % of the exposed area, and for a horizontal tank 75 %. For a vertical tank it is the exposed shell over the first 9 m (30 ft) above grade.<ref name="Ordile-7-20" /> Ordile tabulates the required venting as free air at 101 kPa and 15.5 °C for wetted areas up to 260 m² (2,800 ft²), with interpolation between rows.<ref name="Ordile-7-21">Ordile (2008), p. 7-21.</ref>
Line 83: Line 83:
|}
|}


The factor ''F'' is 0.5 for approved drainage on tanks with more than 18.6 m² (200 ft²) of wetted area. It is 0.3 for approved water spray with drainage, for approved automatic water spray or for approved insulation, and 0.15 for approved water spray combined with approved insulation.<ref name="Ordile-7-21" /> With some restrictions the factors may be halved for liquids whose heat of combustion and burning rate do not exceed those of ethanol, but never below 0.15.<ref name="Ordile-7-21" /> Each vent design below 200 mm (8 in.) should be flow tested, because the flow of manufactured vents varies widely.<ref name="Ordile-7-20" /> The power law agrees with the large-tank table: for 279 m² (3,000 ft²) it gives 22,256 m³/h against 22,257 m³/h in the table.<ref name="Ordile-7-21" />
The factor ''F'' is 0.5 for approved drainage on tanks with more than 18.6 m² (200 ft²) of wetted area. It is 0.3 for approved water spray with drainage, for approved automatic water spray or for approved insulation, and 0.15 for approved water spray combined with approved insulation.<ref name="Ordile-7-21" /> With some restrictions the factors may be halved for liquids whose heat of combustion and burning rate do not exceed those of ethanol, but never below 0.15.<ref name="Ordile-7-21" /> Each vent design below 200 mm (8 in.) should be flow tested, because the flow of manufactured vents varies widely.<ref name="Ordile-7-20" /> The power law reproduces the large-tank table within 0.4 % in every row but one. For 3,000 ft² (278.7 m²) it gives 22,256 m³/h against 22,257 m³/h. At 5,000 ft² (464 m²), however, the printed 35,396 m³/h is about 5 % above the formula value of 33,835 m³/h.<ref name="Ordile-7-21" />


'''Worked example.''' Ordile lists a horizontal tank of 37,854 L (10,000 gal), 2.44 m in diameter and 8.23 m long, as a typical size of underground tank.<ref name="Ordile-7-23">Ordile (2008), p. 7-23.</ref> If a tank of this size is installed aboveground, its shell has an area of 63.09 m² and its two ends 9.35 m², a total of 72.44 m². The wetted area is 75 % of this, or 54.33 m² (585 ft²).<ref name="Ordile-7-20" />
'''Worked example.''' Ordile lists a horizontal tank of 37,854 L (10,000 gal), 2.44 m in diameter and 8.23 m long, as a typical size of underground tank.<ref name="Ordile-7-23">Ordile (2008), p. 7-23.</ref> If a tank of this size is installed aboveground, its shell has an area of 63.09 m² and its two ends 9.35 m², a total of 72.44 m². The wetted area is 75 % of this, or 54.33 m² (585 ft²).<ref name="Ordile-7-20" />
Line 90: Line 90:


== Containers, cabinets and storage rooms ==
== Containers, cabinets and storage rooms ==
Flammable and combustible liquids are packed in bottles, drums and other containers of up to 225 L (60 gal). Intermediate bulk containers (IBCs) hold up to 3,000 L (793 gal) and portable tanks up to 20,818 L (5,500 gal).<ref name="Ordile-7-27">Ordile (2008), p. 7-27.</ref> The NFPA 30 chapter "Container and Portable Tank Storage" covers all of these, except portable tanks larger than 3,000 L, which fall under its chapter "Tank Storage".<ref name="Ordile-7-27" /> The largest permitted container depends on its type and on the class of liquid.<ref name="Ordile-7-28" />
The container rules below are those of NFPA 30 as described in the 2008 handbook. Flammable and combustible liquids are packed in bottles, drums and other containers of up to 225 L (60 gal). Intermediate bulk containers (IBCs) hold up to 3,000 L (793 gal) and portable tanks up to 20,818 L (5,500 gal).<ref name="Ordile-7-27">Ordile (2008), p. 7-27.</ref> The NFPA 30 chapter "Container and Portable Tank Storage" covers all of these, except portable tanks larger than 3,000 L, which fall under its chapter "Tank Storage".<ref name="Ordile-7-27" /> The largest permitted container depends on its type and on the class of liquid.<ref name="Ordile-7-28" />


{| class="wikitable"
{| class="wikitable"
Line 114: Line 114:
Since the 1996 edition, NFPA 30 has contained mandatory protection criteria for inside storage, based on large-scale fire tests. Storage areas that do not meet them count as unprotected, even where some sprinklers are installed.<ref name="Ordile-7-28" /> Inside rooms are limited in the quantity they may hold, whereas the total quantity in a liquid warehouse is not restricted.<ref name="Ordile-7-27" />
Since the 1996 edition, NFPA 30 has contained mandatory protection criteria for inside storage, based on large-scale fire tests. Storage areas that do not meet them count as unprotected, even where some sprinklers are installed.<ref name="Ordile-7-28" /> Inside rooms are limited in the quantity they may hold, whereas the total quantity in a liquid warehouse is not restricted.<ref name="Ordile-7-27" />


Containers such as bottles and drums can also be kept in [[flammable liquid storage cabinet]]s, in storage rooms and warehouses, in yard areas or in storage lockers.<ref name="Ordile-7-32">Ordile (2008), pp. 7-32–7-33.</ref> Cabinets hold no more than 454 L (120 gal) of Class I, II and IIIA liquids.<ref name="Ordile-7-28" /> NUREG-1805 adds that no more than 227 L (60 gal) of this total may be Class I and Class II liquids.<ref name="IS-B-21">Iqbal and Salley (2004), p. B-21.</ref> On construction sites, Davis (2008a) recommends approved cabinets for more than 95 L (25 gal) and refers to Section 4.3 of NFPA 30 for the cabinet limits.<ref name="Davis-11-54">Davis (2008a), p. 11-54.</ref> Prefabricated hazardous material storage lockers may serve as inside storage rooms if they meet the fire resistance ratings of NFPA 30. Their gross floor area is limited to 140 m² (1,500 ft²).<ref name="Ordile-7-28" />  
Containers such as bottles and drums can also be kept in [[flammable liquid storage cabinet]]s, in storage rooms and warehouses, in yard areas or in storage lockers.<ref name="Ordile-7-32">Ordile (2008), pp. 7-32–7-33.</ref> Cabinets hold no more than 454 L (120 gal) of Class I, II and IIIA liquids.<ref name="Ordile-7-28" /> NUREG-1805 adds that no more than 227 L (60 gal) of this total may be Class I and Class II liquids.<ref name="IS-B-21">Iqbal and Salley (2004), p. B-21.</ref> On construction sites, Davis (2008a) recommends approved cabinets for more than 95 L (25 gal) and refers to Section 4.3 of NFPA 30 for the cabinet limits.<ref name="Davis-11-54">Davis (2008a), p. 11-54.</ref> Prefabricated hazardous material storage lockers could serve as inside storage rooms if they met the fire resistance ratings of NFPA 30, and their gross floor area was limited to 140 m² (1,500 ft²).<ref name="Ordile-7-28" />  


For outdoor container storage, the 2003 edition allowed piles of Class IA liquid of up to 4,160 L (1,100 gal) and 3.0 m (10 ft) high. Such piles had to stand 15.3 m (50 ft) from a property line that can be built upon. For Class III liquids it allowed piles of up to 83,200 L (22,000 gal), 5.4 m (18 ft) high, at 3.1 m (10 ft).<ref name="Ordile-7-29">Ordile (2008), p. 7-29.</ref>
For outdoor container storage, the 2003 edition allowed piles of Class IA liquid of up to 4,160 L (1,100 gal) and 3.0 m (10 ft) high. Such piles had to stand 15.3 m (50 ft) from a property line that can be built upon. For Class III liquids it allowed piles of up to 83,200 L (22,000 gal), 5.4 m (18 ft) high, at 3.1 m (10 ft).<ref name="Ordile-7-29">Ordile (2008), p. 7-29.</ref>
Line 123: Line 123:
For fire suppression, the protection criteria in NFPA 30 depend on the liquid, the likely ignition, the packaging, the container material and the storage arrangement.<ref name="Scheffey02-4-113" /> The protection tables carry references to the fire tests behind them. Appendix E of the code gives a test protocol that distinguishes a small point ignition from a large spill or three-dimensional fire.<ref name="Scheffey02-4-113" />
For fire suppression, the protection criteria in NFPA 30 depend on the liquid, the likely ignition, the packaging, the container material and the storage arrangement.<ref name="Scheffey02-4-113" /> The protection tables carry references to the fire tests behind them. Appendix E of the code gives a test protocol that distinguishes a small point ignition from a large spill or three-dimensional fire.<ref name="Scheffey02-4-113" />


The NFPA 30 Technical Committee based its foam criteria for metal containers on foam-water sprinkler tests, earlier drum tests and engineering judgement. The resulting ceiling application rates are on the order of 12.3 to 16.4 L/min/m² (0.30 to 0.40 gpm/ft²).<ref name="Scheffey02-4-116">Scheffey (2002), p. 4-116.</ref> The code recognises both water and [[aqueous film-forming foam]] (AFFF) protection for indoor storage.<ref name="Scheffey08-17-63">Scheffey (2008), p. 17-63.</ref> Where AFFF is used, NFPA 30 requires closed sprinklers and the discharge of foam solution once four closed sprinklers have operated.<ref name="Scheffey08-17-64">Scheffey (2008), p. 17-64.</ref> Scheffey (2008) gives 12.3 L/min/m² (0.30 gpm/ft²) as the lowest design application rate that NFPA 30 then permitted for indoor storage.<ref name="Scheffey08-17-64" />
The NFPA 30 Technical Committee based its foam criteria for metal containers on foam-water sprinkler tests, earlier drum tests and engineering judgement. The resulting ceiling application rates are on the order of 12.3 to 16.4 L/min/m² (0.30 to 0.40 gpm/ft²).<ref name="Scheffey02-4-116">Scheffey (2002), p. 4-116.</ref> The code then recognised both water and [[aqueous film-forming foam]] (AFFF) protection for indoor storage.<ref name="Scheffey08-17-63">Scheffey (2008), p. 17-63.</ref> As described by Scheffey (2008), NFPA 30 then required closed sprinklers where AFFF is used, and the discharge of foam solution once four closed AFFF sprinklers had operated.<ref name="Scheffey08-17-64">Scheffey (2008), p. 17-64.</ref> Scheffey (2008) gives 12.3 L/min/m² (0.30 gpm/ft²) as the lowest design application rate that NFPA 30 then permitted for indoor storage.<ref name="Scheffey08-17-64" />


NFPA 30 does not require every storage vessel to be inerted. NUREG-1805 notes that the 1996 edition, like other codes for flammable liquid storage, did not require inerting of storage tanks or containers. These codes take ignition sources to be absent from passive containers, so the gas composition inside them need not be controlled.<ref name="IS-B-27">Iqbal and Salley (2004), p. B-27.</ref>
NUREG-1805 notes that the 1996 edition of NFPA 30, like other codes for flammable liquid storage, did not require inerting of storage tanks or containers. These codes take ignition sources to be absent from passive containers, so the gas composition inside them need not be controlled.<ref name="IS-B-27">Iqbal and Salley (2004), p. B-27.</ref>


== Limits of the code and of the sources ==
== Limits of the code and of the sources ==
NFPA 30 is a prescriptive US document, and its limits are tied to its own classes of liquid.<ref name="Slye-6-198" /> The source folder does not contain the code itself. All values here come from summaries: the handbook reproduces tables of the 2003 edition, and NUREG-1805 quotes the 2000 edition.<ref name="Ordile-7-28" /><ref name="IS-B-20" /> These summaries already differ between editions, for example in the size of safety cans, and adoption by US states lagged 5 to 10 years behind.<ref name="IS-B-20" /><ref name="HN-13-94" />
NFPA 30 is a US document, and its limits are tied to its own classes of liquid.<ref name="Slye-6-198" /> The source folder does not contain the code itself. All values here come from summaries: the handbook reproduces tables of the 2003 edition, and NUREG-1805 quotes the 2000 edition.<ref name="Ordile-7-28" /><ref name="IS-B-20" /> These summaries already differ between editions, for example in the size of safety cans, and many US state regulations had adopted editions 5 to 10 years behind the current ones.<ref name="IS-B-20" /><ref name="HN-13-94" />


The sources also differ in detail. Ordile (2008) gives the Class IA flash point limit as 73 °F with a conversion of 28 °C, whereas Slye (2008) gives 22.8 °C, which is the correct conversion of 73 °F.<ref name="Ordile-7-18" /><ref name="Slye-6-198" /> Several handbook passages, such as the pressure test of new piping, describe good practice without saying whether NFPA 30 requires it.<ref name="Ordile-7-30" />
The sources also differ in detail. Ordile (2008) gives the Class IA flash point limit as 73 °F with a conversion of 28 °C, whereas Slye (2008) gives 22.8 °C, which is the correct conversion of 73 °F.<ref name="Ordile-7-18" /><ref name="Slye-6-198" /> Several handbook passages, such as the pressure test of new piping, describe good practice without saying whether NFPA 30 requires it.<ref name="Ordile-7-30" />

Revision as of 22:34, 7 November 2026

NFPA 30, the Flammable and Combustible Liquids Code, is the code of the National Fire Protection Association (NFPA) used in the United States to regulate the safety of flammable and combustible liquids.[1][2] It contains requirements for tank storage, piping systems, containers and operations, and its container-storage sections set the criteria for fire suppression systems.[3] The code sorts liquids into classes by their flash point, and many of its limits depend on that class.[4][5]

Like other NFPA standards, NFPA 30 is a voluntary consensus document that has the force of law only where a government adopts it. According to Hildebrand and Noll (2008), the rules of the US Occupational Safety and Health Administration (OSHA) on flammable and combustible liquids then in force adopted it by reference.[6] It is also one of the NFPA standards that US states and local jurisdictions adopt most often.[2] The Fire Protection Handbook (2008) reproduces tables of the 2003 edition, and a 2004 report of the US Nuclear Regulatory Commission quotes the 2000 edition.[7][8] The values in this article therefore describe US practice of around 2000 to 2008, not current or universal requirements.

Scope and legal status

Scheffey (2002) calls NFPA 30 the applicable NFPA protection document for stored flammable and combustible liquids. This covers retail outlets, general-purpose warehouses and dedicated liquid warehouses.[3]

NFPA has more than 60 consensus standards related to hazardous materials, and none of them has the force of law unless a government agency adopts it.[6] Hildebrand and Noll (2008) give NFPA 30 as the example: the OSHA regulations on flammable and combustible liquids adopt it by reference, so an NFPA document becomes law through adoption. They also note that many US state regulations based on NFPA 30 and NFPA 58 had adopted editions 5 to 10 years older than the current ones.[6] Snyder (2008) names NFPA 30 and NFPA 58, the Liquefied Petroleum Gas Code, among the NFPA standards that states and local jurisdictions adopt most commonly as a basis for regulation.[2]

NFPA 30 also serves as the general document behind several narrower codes. As described by Gore Willse (2008a), NFPA 31, the standard for oil-burning equipment, covered underground tanks, tanks inside buildings and outside aboveground tanks of up to 2,500 L (660 gal). Larger outside aboveground tanks fell under Chapter 4 of NFPA 30, which is more general and covers liquids with a wider range of flash points in many kinds of occupancy.[9] For bulk storage plants holding at least one carload of gasoline or similar liquids, NFPA 30 and Article 515 of the US National Electrical Code defined the hazardous (classified) areas for electrical equipment.[10]

Before the first edition of NFPA 30B appeared in 1990, aerosol products fell under NFPA 30 and were treated as equivalent to Class IA flammable liquids.[11] Many users found the resulting protection excessive. Fire tests in the early to mid-1980s showed that some aerosol products presented severe fire hazards, whereas others presented a much lower fire challenge than a Class IA liquid.[11] The Port Authority's Tenant Construction Review Manual, available from 1971 to March 1997 for its facilities including the World Trade Center, also referenced NFPA 30 specifically in its 1997 edition.[12]

Classification of liquids

NFPA 30 first separates liquids from gases and solids. A liquid, in the sense of the code, is a fluid with a vapour pressure not exceeding 2,068 mm Hg (40 psia, about 276 kPa) at 37.8 °C (100 °F). It must also flow more easily than asphalt of penetration grade 300.[4] The classes are then set by the flash point. NFPA 30 defines the flash point as the minimum temperature at which a liquid gives off enough vapour to form an ignitable mixture with air, near its surface or within the vessel used.[13] The code uses the closed-cup value.[8] Hurley and Bukowski (2008) add that the flash point is not a physical property, because the measured value can change with the test method.[13]

The class boundaries follow a simple argument about room temperature. In most areas the indoor temperature can reach 37.8 °C (100 °F) at some time of the year, so every liquid with a lower flash point is a Class I, or flammable, liquid.[4] Liquids with flash points from 37.8 to 60 °C (100 to 140 °F) need only moderate heating to reach their flash point and form Class II. Liquids above 60 °C need considerable heating from a source other than the surroundings and form Class III.[4] NUREG-1805 illustrates the logic with a spill on ground heated by the sun to 35 °C (95 °F). A Class I spill is then extremely hazardous, a Class II spill is dangerous only if a heat source warms it, and a Class III spill stays safe from ignition unless something heats it substantially.[14]

Classes of liquids in NFPA 30, with examples from the 2000 edition
Class Flash point Boiling point Examples
IA (flammable) below 22.8 °C (73 °F) below 37.8 °C (100 °F) ethyl ether
IB (flammable) below 22.8 °C (73 °F) at or above 37.8 °C (100 °F) ethyl alcohol, gasoline, cyclohexane
IC (flammable) 22.8 °C to below 37.8 °C not used butyl ether
II (combustible) 37.8 °C to below 60 °C (140 °F) not used kerosene, diesel fuel, jet fuel A
IIIA (combustible) 60 °C to below 93 °C (200 °F) not used creosote oil, butyl carbitol
IIIB (combustible) 93 °C (200 °F) and above not used mineral oil, olive oil, lubricating oil

The class limits in the table follow Slye (2008), and the examples follow the 2000 edition as quoted in NUREG-1805.[4][8] The system is treated in detail in Flammable and combustible liquid classification. The fire point is the lowest temperature to which a liquid must be heated to give off enough vapour for burning to continue for at least 5 s after a test flame is applied. Codes such as NFPA 30 use it to exempt liquids that have a flash point but cannot sustain burning from storage limits.[15] Other classification systems use different break points, the open-cup tester, or the solubility of the liquid in water, so the NFPA 30 classes do not carry over directly to them.[4]

Tank storage

The tank rules in this section are those of NFPA 30 as described by Ordile (2008) in the 2008 handbook, which does not name the edition it follows.[5] Ordile groups tanks by design pressure. Atmospheric tanks are designed for 0 to 6.9 kPa (0 to 1.0 psig), low-pressure tanks for 6.9 to 103 kPa (1.0 to 15 psig) and pressure vessels for more than 103 kPa (15 psig).[1]

NFPA 30 specifies the distances from aboveground tanks to property lines that can be built on, to public ways and to important buildings, and the spacing between tanks.[16] The distances depend on whether the tank pressure, including the pressure reached during fire exposure, can exceed 17 kPa (2.5 psig). They also depend on whether the liquid is stable, unstable or prone to boilover, on the size and design of the tank and on the protection provided.[16]

Every tank needs a normal vent for filling, emptying and thermal expansion. It can be sized by the American Petroleum Institute (API) Standard 2000. Otherwise it should be at least as large as the largest filling or withdrawal connection, and never smaller than 32 mm (1.25 in.) nominal inside diameter.[16] Vapour that would be a hazard is piped to a safe outside point at least 3.7 m (12 ft) above grade. NFPA 30 requires vents that stay closed except under pressure or vacuum for Class IA liquids. Pressure-vacuum vent valves or flame arresters are required for all Class I liquids.[16]

Spill control is the second main theme. Where a release would endanger important facilities, waterways or neighbouring property, the preferred layout uses sloping ground that drains to a remote impounding basin. There the liquid can burn without exposing other tanks.[17]

Otherwise dikes surround the tanks. A diked enclosure must hold the full contents of the largest tank, and the volume that other tanks occupy below the top of the dike counts as unavailable.[17] Intermediate dikes at least 457 mm (18 in.) high keep small spills away from neighbouring tanks. Dikes higher than 1.8 m (6 ft) are undesirable without extra safety measures. For Class I liquids, dikes averaging more than 3.6 m (12 ft) in height, or standing closer to a tank than their own height, call for access to valves and roofs without entering the enclosure.[17] Aboveground secondary containment tanks that meet NFPA 30 need no dike or drainage, as long as they stay within the capacities the code allows.[17]

Liquid that ignites inside a dike burns as a pool fire whose diameter is set by the enclosure. Beyler (2002a) works through a toluene spill in a diked area of 12 m diameter. His correlation gives a radiant heat flux of about 3.6 kW/m² at ground level 30 m from the pool centre, with no wind.[18] Beyler states that heat fluxes below 5 kW/m² cannot ignite combustibles.[18] Exposed steel supports under tanks should have a fire resistance rating of at least 2 hours, because supports that fail drop the tanks to the ground.[17]

Tanks below and inside buildings have their own rules. NFPA 30 requires underground tanks and their piping to be protected by corrosion-resistant materials, such as special alloys and fibreglass, or by an engineered cathodic protection system.[19] Tanks for Class I, II and IIIA liquids are permitted inside buildings that meet the NFPA 30 rules for storage tank buildings.[19]

An individual tank in such a building is limited to 380,000 L (100,000 gal) unless the authority having jurisdiction permits more. The building should keep its structural integrity for 2 hours of fire exposure.[20] Where it stores Class I liquids, or Class II and IIIA liquids above their flash point, ventilation must keep the vapour concentration at or below 25 % of the lower flammable limit.[20] Tank vaults have walls and floors of reinforced concrete at least 150 mm (6 in.) thick and hold one tank each. They need no separation distance to property lines.[20]

Emergency venting of tanks

As in the previous section, the venting rules are those of NFPA 30 as described in the 2008 handbook.[21] Most aboveground tanks need emergency relief of internal pressure, in addition to the normal vent, in case a fire occurs under or around them; a floating roof removes this need.[22] Without such relief, high internal pressures can build up and sometimes cause an explosion.[22] The required relief rate depends on the wetted area. This is the part of the tank wall in contact with the liquid that a ground fire would heat.[22]

For a sphere or spheroid it is 55 % of the exposed area, and for a horizontal tank 75 %. For a vertical tank it is the exposed shell over the first 9 m (30 ft) above grade.[22] Ordile tabulates the required venting as free air at 101 kPa and 15.5 °C for wetted areas up to 260 m² (2,800 ft²), with interpolation between rows.[21]

For tanks designed for more than 6.9 kPa (1 psig) with a wetted area above 260 m², the rate can also be calculated. The rate grows with the wetted area raised to the power 0.82, because the relation rests on a heat absorption of 21,000 A0.82 Btu/h, with A in ft².[21] In SI units the relation reads: V˙=220A0.82 For a specific stable liquid, the free-air rate is converted with the latent heat of vaporisation and the molecular weight of that liquid: V˙liq=V˙3107LM NFPA 30 permits the required rate to be multiplied by one reduction factor when the tank has approved protection:[21] V˙red=FV˙

Symbols in the emergency venting relations
Symbol Description Unit
V˙ required venting rate as free air at 101 kPa and 15.5 °C m³/h
A exposed wetted area of the tank m²
V˙liq venting rate for a specific stable liquid m³/h
L latent heat of vaporisation of the liquid kJ/kg
M molecular weight of the liquid g/mol
F reduction factor for approved protection –
V˙red reduced venting rate m³/h

The factor F is 0.5 for approved drainage on tanks with more than 18.6 m² (200 ft²) of wetted area. It is 0.3 for approved water spray with drainage, for approved automatic water spray or for approved insulation, and 0.15 for approved water spray combined with approved insulation.[21] With some restrictions the factors may be halved for liquids whose heat of combustion and burning rate do not exceed those of ethanol, but never below 0.15.[21] Each vent design below 200 mm (8 in.) should be flow tested, because the flow of manufactured vents varies widely.[22] The power law reproduces the large-tank table within 0.4 % in every row but one. For 3,000 ft² (278.7 m²) it gives 22,256 m³/h against 22,257 m³/h. At 5,000 ft² (464 m²), however, the printed 35,396 m³/h is about 5 % above the formula value of 33,835 m³/h.[21]

Worked example. Ordile lists a horizontal tank of 37,854 L (10,000 gal), 2.44 m in diameter and 8.23 m long, as a typical size of underground tank.[23] If a tank of this size is installed aboveground, its shell has an area of 63.09 m² and its two ends 9.35 m², a total of 72.44 m². The wetted area is 75 % of this, or 54.33 m² (585 ft²).[22]

The table gives 10,024 m³/h at 46.45 m² and 11,100 m³/h at 55.74 m².[21] Linear interpolation gives 10,937 m³/h, which is rounded up to a required capacity of 11,000 m³/h of free air. With approved insulation (F = 0.3) the requirement falls to 3,281 m³/h, rounded up to 3,300 m³/h. With approved drainage (F = 0.5) it falls to 5,500 m³/h, since the wetted area exceeds 18.6 m².[21]

Containers, cabinets and storage rooms

The container rules below are those of NFPA 30 as described in the 2008 handbook. Flammable and combustible liquids are packed in bottles, drums and other containers of up to 225 L (60 gal). Intermediate bulk containers (IBCs) hold up to 3,000 L (793 gal) and portable tanks up to 20,818 L (5,500 gal).[24] The NFPA 30 chapter "Container and Portable Tank Storage" covers all of these, except portable tanks larger than 3,000 L, which fall under its chapter "Tank Storage".[24] The largest permitted container depends on its type and on the class of liquid.[7]

Maximum container sizes in NFPA 30 (2003 edition, Table 6.2.3), selected rows
Container type Class IA Class IB Class IC Class II Class IIIA
Glass 0.5 L 1 L 5 L 5 L 20 L
Metal (other than drums) or approved plastic 5 L 20 L 20 L 20 L 20 L
Safety cans 10 L 20 L 20 L 20 L 20 L
Metal drum 450 L 450 L 450 L 450 L 450 L
Approved metal portable tanks and IBCs 3,000 L 3,000 L 3,000 L 3,000 L 3,000 L
Rigid plastic and composite IBCs not permitted not permitted not permitted 3,000 L 3,000 L

The table follows Ordile (2008).[7] The 2000 edition, as quoted in NUREG-1805, gave the safety can limits as 2 gal for Class IA and 5 gal for the other classes, and the glass limit for Class IA as 1 pt.[25]

The main hazard of closed containers is overpressure failure in a fire. The released liquid feeds the fire and can rupture further containers.[24] Fire tests have shown that sprinklers of ordinary density, and even early suppression fast-response (ESFR) sprinklers, can fail to prevent such ruptures in high-piled storage. Drainage of spilled liquid is critical, especially with water-only systems.[24]

Since the 1996 edition, NFPA 30 has contained mandatory protection criteria for inside storage, based on large-scale fire tests. Storage areas that do not meet them count as unprotected, even where some sprinklers are installed.[7] Inside rooms are limited in the quantity they may hold, whereas the total quantity in a liquid warehouse is not restricted.[24]

Containers such as bottles and drums can also be kept in flammable liquid storage cabinets, in storage rooms and warehouses, in yard areas or in storage lockers.[26] Cabinets hold no more than 454 L (120 gal) of Class I, II and IIIA liquids.[7] NUREG-1805 adds that no more than 227 L (60 gal) of this total may be Class I and Class II liquids.[27] On construction sites, Davis (2008a) recommends approved cabinets for more than 95 L (25 gal) and refers to Section 4.3 of NFPA 30 for the cabinet limits.[28] Prefabricated hazardous material storage lockers could serve as inside storage rooms if they met the fire resistance ratings of NFPA 30, and their gross floor area was limited to 140 m² (1,500 ft²).[7]

For outdoor container storage, the 2003 edition allowed piles of Class IA liquid of up to 4,160 L (1,100 gal) and 3.0 m (10 ft) high. Such piles had to stand 15.3 m (50 ft) from a property line that can be built upon. For Class III liquids it allowed piles of up to 83,200 L (22,000 gal), 5.4 m (18 ft) high, at 3.1 m (10 ft).[29]

Handling and fire protection

Transfer operations cause more trouble than storage, because they involve active steps in which human error can lead to spills.[30] Ordile (2008) describes loading racks at least 7.6 m (25 ft) from tanks for Class I liquids and 4.6 m (15 ft) for Class II and III liquids.[17] Bonding against static sparks is provided at all stations where Class I liquids are loaded or unloaded. It is not needed for Class II and III liquids transferred at ambient temperature.[31] Only inert gas should be used to transfer Class I liquids by gas pressure. Air is acceptable for Class II and III liquids unless they are heated above their flash point.[31]

For fire suppression, the protection criteria in NFPA 30 depend on the liquid, the likely ignition, the packaging, the container material and the storage arrangement.[3] The protection tables carry references to the fire tests behind them. Appendix E of the code gives a test protocol that distinguishes a small point ignition from a large spill or three-dimensional fire.[3]

The NFPA 30 Technical Committee based its foam criteria for metal containers on foam-water sprinkler tests, earlier drum tests and engineering judgement. The resulting ceiling application rates are on the order of 12.3 to 16.4 L/min/m² (0.30 to 0.40 gpm/ft²).[32] The code then recognised both water and aqueous film-forming foam (AFFF) protection for indoor storage.[33] As described by Scheffey (2008), NFPA 30 then required closed sprinklers where AFFF is used, and the discharge of foam solution once four closed AFFF sprinklers had operated.[34] Scheffey (2008) gives 12.3 L/min/m² (0.30 gpm/ft²) as the lowest design application rate that NFPA 30 then permitted for indoor storage.[34]

NUREG-1805 notes that the 1996 edition of NFPA 30, like other codes for flammable liquid storage, did not require inerting of storage tanks or containers. These codes take ignition sources to be absent from passive containers, so the gas composition inside them need not be controlled.[35]

Limits of the code and of the sources

NFPA 30 is a US document, and its limits are tied to its own classes of liquid.[4] The source folder does not contain the code itself. All values here come from summaries: the handbook reproduces tables of the 2003 edition, and NUREG-1805 quotes the 2000 edition.[7][25] These summaries already differ between editions, for example in the size of safety cans, and many US state regulations had adopted editions 5 to 10 years behind the current ones.[25][6]

The sources also differ in detail. Ordile (2008) gives the Class IA flash point limit as 73 °F with a conversion of 28 °C, whereas Slye (2008) gives 22.8 °C, which is the correct conversion of 73 °F.[16][4] Several handbook passages, such as the pressure test of new piping, describe good practice without saying whether NFPA 30 requires it.[31]

See also

Notes

  1. ↑ 1.0 1.1 Ordile (2008), p. 7-16.
  2. ↑ 2.0 2.1 2.2 Snyder (2008), p. 12-184.
  3. ↑ 3.0 3.1 3.2 3.3 Scheffey (2002), p. 4-113.
  4. ↑ 4.0 4.1 4.2 4.3 4.4 4.5 4.6 4.7 Slye (2008), p. 6-198.
  5. ↑ 5.0 5.1 Ordile (2008), pp. 7-18–7-30.
  6. ↑ 6.0 6.1 6.2 6.3 Hildebrand and Noll (2008), p. 13-94.
  7. ↑ 7.0 7.1 7.2 7.3 7.4 7.5 7.6 Ordile (2008), p. 7-28.
  8. ↑ 8.0 8.1 8.2 Iqbal and Salley (2004), pp. B-17–B-18.
  9. ↑ Gore Willse (2008a), p. 10-15.
  10. ↑ Milatovich (2008), p. 8-172.
  11. ↑ 11.0 11.1 Fredrickson (2008), p. 6-257.
  12. ↑ Grill and Johnson (2005c), pp. 11–12.
  13. ↑ 13.0 13.1 Hurley and Bukowski (2008), p. 3-126.
  14. ↑ Iqbal and Salley (2004), p. B-18.
  15. ↑ Slye (2008), p. 6-200.
  16. ↑ 16.0 16.1 16.2 16.3 16.4 Ordile (2008), p. 7-18.
  17. ↑ 17.0 17.1 17.2 17.3 17.4 17.5 Ordile (2008), p. 7-22.
  18. ↑ 18.0 18.1 Beyler (2002a), p. 3-286.
  19. ↑ 19.0 19.1 Ordile (2008), p. 7-24.
  20. ↑ 20.0 20.1 20.2 Ordile (2008), p. 7-25.
  21. ↑ 21.0 21.1 21.2 21.3 21.4 21.5 21.6 21.7 21.8 Ordile (2008), p. 7-21.
  22. ↑ 22.0 22.1 22.2 22.3 22.4 22.5 Ordile (2008), p. 7-20.
  23. ↑ Ordile (2008), p. 7-23.
  24. ↑ 24.0 24.1 24.2 24.3 24.4 Ordile (2008), p. 7-27.
  25. ↑ 25.0 25.1 25.2 Iqbal and Salley (2004), p. B-20.
  26. ↑ Ordile (2008), pp. 7-32–7-33.
  27. ↑ Iqbal and Salley (2004), p. B-21.
  28. ↑ Davis (2008a), p. 11-54.
  29. ↑ Ordile (2008), p. 7-29.
  30. ↑ Ordile (2008), p. 7-15.
  31. ↑ 31.0 31.1 31.2 Ordile (2008), p. 7-30.
  32. ↑ Scheffey (2002), p. 4-116.
  33. ↑ Scheffey (2008), p. 17-63.
  34. ↑ 34.0 34.1 Scheffey (2008), p. 17-64.
  35. ↑ Iqbal and Salley (2004), p. B-27.

References

  • Beyler, C. L. (2002a). Fire hazard calculations for large, open hydrocarbon fires. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 3-268–3-314). National Fire Protection Association; Society of Fire Protection Engineers.
  • Davis, R. J. (2008a). Fire hazards of construction, alteration, and demolition of buildings. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 11-47–11-58). National Fire Protection Association.
  • Fredrickson, D. L. (2008). Manufacture and storage of aerosol products. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-257–6-267). National Fire Protection Association.
  • Gore Willse, P. J. (2008a). Heating systems and appliances. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 10-9–10-56). National Fire Protection Association.
  • Grill, R. A., & Johnson, D. A. (2005c). Post-construction modifications to fire protection and life safety systems of the World Trade Center towers (NIST NCSTAR 1-1H). National Institute of Standards and Technology.
  • Hildebrand, M. S., & Noll, G. G. (2008). Public fire protection and hazmat management. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 13-81–13-98). National Fire Protection Association.
  • Hurley, M. J., & Bukowski, R. W. (2008). Fire hazard analysis techniques. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 3-121–3-134). National Fire Protection Association.
  • Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.
  • Milatovich, R. M. (2008). Electrical systems and appliances. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 8-127–8-173). National Fire Protection Association.
  • Ordile, A. M. (2008). Storage of flammable and combustible liquids. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 7-15–7-33). National Fire Protection Association.
  • Scheffey, J. L. (2002). Foam agents and AFFF system design considerations. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 4-88–4-122). National Fire Protection Association; Society of Fire Protection Engineers.
  • Scheffey, J. L. (2008). Foam extinguishing agents and systems. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 17-45–17-70). National Fire Protection Association.
  • Slye, O. M., Jr. (2008). Flammable and combustible liquids. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-197–6-208). National Fire Protection Association.
  • Snyder, M. (2008). Industrial fire loss prevention. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 12-177–12-198). National Fire Protection Association.