'''Ammonia refrigeration''' is mechanical or absorption refrigeration that uses anhydrous ammonia (NH<sub>3</sub>, refrigerant number R-717) as the working fluid. It takes heat from a cold space or product and rejects it elsewhere by evaporating and condensing the ammonia.<ref name="Febo-8-119">Febo (2008), p. 8-119.</ref><ref name="Febo-8-121">Febo (2008), p. 8-121.</ref> Ammonia systems are an alternative to halogenated refrigerants, and large industrial systems are common in food processing, cold storage and process cooling.<ref name="Febo-8-118">Febo (2008), p. 8-118.</ref><ref name="Lemoff-6-179">Lemoff (2008), p. 6-179.</ref> Under the refrigerant safety classification of ANSI/ASHRAE 34 (2004 edition), ammonia is class B2: higher toxicity and lower flammability.<ref name="Febo-8-121" />
'''Ammonia refrigeration''' is mechanical or absorption refrigeration that uses anhydrous ammonia (NH<sub>3</sub>, refrigerant number R-717) as the working fluid. It takes heat from a cold space or product and rejects it elsewhere by evaporating and condensing the ammonia.<ref name="Febo-8-119">Febo (2008), p. 8-119.</ref><ref name="Febo-8-121">Febo (2008), p. 8-121.</ref> Ammonia systems head the handbook's list of alternatives to halogenated refrigerants. Systems holding more than 10,000 lb (4540 kg) of ammonia are quite common in industry, for example in large refrigerated warehouses and in low-temperature process cooling.<ref name="Febo-8-118">Febo (2008), p. 8-118.</ref><ref name="Lemoff-6-179">Lemoff (2008), p. 6-179.</ref><ref name="Febo-8-123">Febo (2008), p. 8-123.</ref> Under the refrigerant safety classification of ANSI/ASHRAE 34 (2004 edition), ammonia is class B2: higher toxicity and lower flammability.<ref name="Febo-8-119" /><ref name="Febo-8-121" />


The hazards are toxicity, fire, explosion and contamination of stored goods.<ref name="Febo-8-125">Febo (2008), p. 8-125.</ref> Ammonia burns only between about 15 and 28 percent by volume in air and needs a large ignition energy, so fires are infrequent.<ref name="RS-9-230">Rosales and Stoltzfus (2008), p. 9-230.</ref><ref name="Lemoff-6-179" /> In tight rooms such as refrigerated storage areas, however, a large release can form a flammable mixture whose ignition causes major structural damage.<ref name="Lemoff-6-179" /> Its toxicity acts at concentrations far below the flammable range.<ref name="Purser-2-92" /> The NFPA ''Fire Protection Handbook'' (2008) describes the US safeguards of the time: a separate machinery room, ventilation and gas detection, explosion venting, water spray and a high level of maintenance.<ref name="Febo-8-124">Febo (2008), p. 8-124.</ref><ref name="Febo-8-125" />
The hazards are toxicity, fire, explosion and contamination of stored goods.<ref name="Febo-8-125">Febo (2008), p. 8-125.</ref> Ammonia burns only between about 15 and 28 percent by volume in air and has a low heat of combustion, so fires are infrequent.<ref name="RS-9-230">Rosales and Stoltzfus (2008), p. 9-230.</ref><ref name="Lemoff-6-179" /> It also needs a large ignition energy, more than 1000 mJ in air.<ref name="RS-9-230" /> In tight rooms such as refrigerated storage areas, however, a large release can form a flammable mixture whose ignition causes major structural damage.<ref name="Lemoff-6-179" /> Its toxicity acts at concentrations far below the flammable range.<ref name="Purser-2-92" /><ref name="RS-9-230" /> The NFPA ''Fire Protection Handbook'' (2008) describes the US safeguards of the time: a separate machinery room, ventilation and gas detection, explosion venting, water spray and a high level of maintenance.<ref name="Febo-8-124">Febo (2008), p. 8-124.</ref><ref name="Febo-8-125" />


== Refrigerant and refrigeration cycle ==
== Refrigerant and refrigeration cycle ==
Line 8: Line 8:
In the United States, refrigeration capacity is expressed in tons. One ton is the heat needed to melt 1 ton (2000 lb, 907 kg) of ice at 0 °C in 24 hours. With a heat of fusion of about 144 Btu/lb (3.4 × 10<sup>5</sup> J/kg), this equals 12,000 Btu/h, or 3.5 kW.<ref name="Febo-8-119" />
In the United States, refrigeration capacity is expressed in tons. One ton is the heat needed to melt 1 ton (2000 lb, 907 kg) of ice at 0 °C in 24 hours. With a heat of fusion of about 144 Btu/lb (3.4 × 10<sup>5</sup> J/kg), this equals 12,000 Btu/h, or 3.5 kW.<ref name="Febo-8-119" />


Ammonia is also used in absorption refrigeration, where a heat-driven generator replaces the compressor.<ref name="Febo-8-122">Febo (2008), p. 8-122.</ref> Ammonia-water units serve large-tonnage industrial applications that need low process temperatures. Their solutions reach vapour pressures of up to 295 psi (2030 kPa) at cycle conditions, so the vessels must be much stronger than those of water-lithium bromide machines, which run under vacuum.<ref name="Febo-8-123">Febo (2008), p. 8-123.</ref> Febo (2008) notes that ammonia absorption systems share the inherent hazards of ammonia and need the same safeguards.<ref name="Febo-8-123" /> In indirect systems the refrigerant cools an intermediate liquid, called brine, which is then circulated to the space or product.<ref name="Febo-8-123" /> Indirect systems can sometimes allow a toxic refrigerant where the machine room can be placed safely away from normally occupied areas.<ref name="Febo-8-124" />
Ammonia is also used in absorption refrigeration, where a heat-driven generator replaces the compressor.<ref name="Febo-8-122">Febo (2008), p. 8-122.</ref> Ammonia-water units serve large-tonnage industrial applications that need low process temperatures. Their solutions reach vapour pressures of up to 295 psi (2030 kPa) at cycle conditions, so the vessels must be much stronger than those of water-lithium bromide machines, which run under vacuum.<ref name="Febo-8-123" /> Febo (2008) notes that ammonia absorption systems share the inherent hazards of ammonia and need the same safeguards.<ref name="Febo-8-123" /> In indirect systems the refrigerant cools an intermediate liquid, called brine, which is then circulated to the space or product.<ref name="Febo-8-123" /> Indirect systems can sometimes allow a toxic refrigerant where the machine room can be placed safely away from normally occupied areas.<ref name="Febo-8-124" />


== Properties of anhydrous ammonia ==
== Properties of anhydrous ammonia ==
Anhydrous ammonia is a nitrogen atom bonded to three hydrogen atoms. The word ''ammonia'' is, strictly, a solution of anhydrous (meaning "without water") ammonia in water.<ref name="Lemoff-6-178">Lemoff (2008), p. 6-178.</ref> Lemoff (2008) classifies it as a flammable, liquefied, industrial gas. Its NFPA 704 hazard ratings are 3 for health, 1 for flammability and 0 for instability, and its UN number is 1005.<ref name="Lemoff-6-178" /> Moist ammonia attacks copper, zinc and many brass and bronze alloys vigorously. LP-gas equipment of these metals must therefore be changed to steel before it is converted to ammonia service.<ref name="Lemoff-6-178" /><ref name="Lemoff-6-179" />
Anhydrous ammonia is a nitrogen atom bonded to three hydrogen atoms. The word ''ammonia'' is, strictly, a solution of anhydrous (meaning "without water") ammonia in water.<ref name="Lemoff-6-178">Lemoff (2008), p. 6-178.</ref> Lemoff (2008) classifies it as a flammable, liquefied, industrial gas. Its NFPA 704 hazard ratings are 3 for health, 1 for flammability and 0 for instability, and its UN number is 1005.<ref name="Lemoff-6-178" /> Moist ammonia attacks copper, zinc and many brass and bronze alloys vigorously. LP-gas equipment of these metals must therefore be changed to steel before it is converted to ammonia service.<ref name="Lemoff-6-178" /><ref name="Lemoff-6-179" />


At its normal boiling point of −33 °C (−28 °F), liquid ammonia has a density of 682.4 kg/m³ and a latent heat of evaporation of 1371 kJ/kg.<ref name="Lemoff-6-179" /> At normal temperature and pressure (NTP) the gas has a density of about 0.72 kg/m³. One cubic foot of liquid produces about 885 ft³ of gas.<ref name="Lemoff-6-179" /> At normal temperatures the gas weighs about 0.6 times as much as air, and released liquid floats and boils on water.<ref name="Lemoff-6-179" /> Table 8.12.1 of the handbook, taken from ANSI/ASHRAE 34-2004, gives a specific gravity of 0.59 relative to air and an autoignition temperature of 651 °C (1204 °F).<ref name="Febo-8-121" />
At its normal boiling point of −33 °C (−28 °F), liquid ammonia has a density of 682.4 kg/m³ and a latent heat of evaporation of 1371 kJ/kg.<ref name="Lemoff-6-179" /> At normal temperature and pressure (NTP) the gas has a density of about 0.72 kg/m³. One cubic foot of liquid produces about 885 ft³ of gas.<ref name="Lemoff-6-179" /> The two densities given on the same page imply a ratio of about 950 (682.4/0.72); the worked example below uses the density. At normal temperatures the gas weighs about 0.6 times as much as air, and released liquid floats and boils on water.<ref name="Lemoff-6-179" /> Table 8.12.1 of the handbook, taken from ANSI/ASHRAE 34-2004, gives a specific gravity of 0.59 relative to air and an autoignition temperature of 651 °C (1204 °F).<ref name="Febo-8-121" />


{| class="wikitable"
{| class="wikitable"
Line 42: Line 42:
The pungent odour and irritant properties of ammonia act as warnings, but their value depends on the rate of release.<ref name="Lemoff-6-179" /> A large liquid leak can rapidly produce a large gas cloud, so that people are trapped and killed before they can leave the area.<ref name="Lemoff-6-179" /> The human sense of smell also becomes accustomed to the odour over time. Lemoff (2008) stresses that this matters in plants that use large quantities, such as many large refrigerated warehouses.<ref name="Lemoff-6-179" />
The pungent odour and irritant properties of ammonia act as warnings, but their value depends on the rate of release.<ref name="Lemoff-6-179" /> A large liquid leak can rapidly produce a large gas cloud, so that people are trapped and killed before they can leave the area.<ref name="Lemoff-6-179" /> The human sense of smell also becomes accustomed to the odour over time. Lemoff (2008) stresses that this matters in plants that use large quantities, such as many large refrigerated warehouses.<ref name="Lemoff-6-179" />


The SFPE handbook gives toxicity data for ammonia as an irritant gas. In Table 2-6.1 of Purser (2002), severe sensory irritation in humans occurs at 700 to 1700 ppm.<ref name="Purser-2-92">Purser (2002), p. 2-92.</ref> The 30-minute lethal concentration for half of exposed mammals (LC<sub>50</sub>) lies between 1,400 and 8,000 ppm, and the RD<sub>50</sub> for mice, the concentration that halves the breathing rate, is 303 ppm.<ref name="Purser-2-92" /> Ammonia is also one of the irritants that Purser lists among combustion products, which links it to [[Fire toxicity|fire toxicity]] in general.<ref name="Purser-2-92" />
The SFPE handbook gives toxicity data for ammonia as an irritant gas. In Table 2-6.1 of Purser (2002), severe sensory irritation in humans occurs at 700 to 1700 ppm.<ref name="Purser-2-92">Purser (2002), p. 2-92.</ref> The 30-minute lethal concentration for half of exposed mammals (LC<sub>50</sub>) lies between 1,400 and 8,000 ppm, and the RD<sub>50</sub> for mice, the concentration that halves the breathing rate, is 303 ppm.<ref name="Purser-2-91">Purser (2002), p. 2-91.</ref><ref name="Purser-2-92" /> Ammonia is also one of the irritants that Purser lists among combustion products, which links it to [[Fire toxicity|fire toxicity]] in general.<ref name="Purser-2-92" />


One percent by volume is 10,000 ppm. A lower flammable limit of 15 percent therefore equals 150,000 ppm, about 100 times the lower end of the LC<sub>50</sub> range.<ref name="RS-9-230" /><ref name="Purser-2-92" /> A release that is far too dilute to burn can still be lethal.
One percent by volume is 10,000 ppm. A lower flammable limit of 15 percent therefore equals 150,000 ppm, about 100 times the lower end of the LC<sub>50</sub> range.<ref name="RS-9-230" /><ref name="Purser-2-92" /> A release that is far too dilute to burn can still be lethal.
Line 92: Line 92:
A release without fire is handled by directing, diluting and dispersing the gas away from people and goods while the flow is stopped.<ref name="Febo-8-125" /> Because ammonia dissolves readily in water, water spray controls the spread of escaping gas well.<ref name="Lemoff-6-179" /> Fire fighters using hose streams need breathing apparatus because of the toxic and inerting properties of the gas, and full protective clothing where contact with the liquid is likely.<ref name="Lemoff-6-179" /> Water should not be put on pools of cryogenic liquid unless the vapours can be controlled, because it increases the rate of evaporation.<ref name="Lemoff-6-179" /> Emergency plans should cover control of the release, protection of personnel, and decontamination or preservation of the stored goods.<ref name="Febo-8-125" />
A release without fire is handled by directing, diluting and dispersing the gas away from people and goods while the flow is stopped.<ref name="Febo-8-125" /> Because ammonia dissolves readily in water, water spray controls the spread of escaping gas well.<ref name="Lemoff-6-179" /> Fire fighters using hose streams need breathing apparatus because of the toxic and inerting properties of the gas, and full protective clothing where contact with the liquid is likely.<ref name="Lemoff-6-179" /> Water should not be put on pools of cryogenic liquid unless the vapours can be controlled, because it increases the rate of evaporation.<ref name="Lemoff-6-179" /> Emergency plans should cover control of the release, protection of personnel, and decontamination or preservation of the stored goods.<ref name="Febo-8-125" />


Ammonia is shipped and stored in a [[Compressed gas cylinder|compressed gas cylinder]], in cargo tank trucks, rail tank cars and barges, and in pressure tanks or insulated cryogenic tanks.<ref name="Lemoff-6-179" /> Containers holding less than 165 lb (75 kg) need not have overpressure protection devices, as described in the 2008 handbook. Lemoff (2008) explains this as a trade-off between the risk of container rupture and the risk of a toxic release indoors.<ref name="Lemoff-6-179" />
Ammonia is shipped and stored in a [[Compressed gas cylinder|compressed gas cylinder]], in cargo tank trucks, rail tank cars and barges, and in pressure tanks or insulated cryogenic tanks.<ref name="Lemoff-6-179" /> Containers holding less than 165 lb (75 kg; the handbook prints 79 kg, a conversion error) need not have overpressure protection devices, as described in the 2008 handbook. Lemoff (2008) explains this as a trade-off between the risk of container rupture and the risk of a toxic release indoors.<ref name="Lemoff-6-179" />


== Regulation in the United States ==
== Regulation in the United States ==
The handbook describes the US regulatory position around 2008. OSHA and Environmental Protection Agency (EPA) rules on ammonia refrigeration apply above quantity limits of typically 500 to 1000 lb (227 to 454 kg).<ref name="Febo-8-118" /> The OSHA Process Safety Management standard, 29 CFR 1910.119, applies to systems with more than 10,000 lb (4540 kg) of ammonia, which Febo (2008) describes as quite common in industrial systems.<ref name="Febo-8-118" /> Large systems of this kind are found in refrigerated warehouses and in industrial plants, where they form part of the hazards of an [[Industrial occupancy|industrial occupancy]].<ref name="Lemoff-6-179" /><ref name="Febo-8-118" /> The handbook lists ANSI/IIAR 2 (1999 edition) on ammonia mechanical refrigeration, ANSI/ASHRAE 15 (2004) and ANSI/ASME B31.5 (2001) on refrigeration piping as further references.<ref name="Febo-8-125" />
The handbook describes the US regulatory position around 2008. OSHA and Environmental Protection Agency (EPA) rules on ammonia refrigeration apply above quantity limits of typically 500 to 1000 lb (227 to 454 kg).<ref name="Febo-8-118" /> The OSHA Process Safety Management standard, 29 CFR 1910.119, applies to systems with more than 10,000 lb (4540 kg) of ammonia, which Febo (2008) describes as quite common in industrial systems.<ref name="Febo-8-118" /> Large systems of this kind are found in refrigerated warehouses and in industrial plants, where they form part of the hazards of an [[Industrial occupancy|industrial occupancy]].<ref name="Lemoff-6-179" /><ref name="Febo-8-118" /> The handbook lists ANSI/IIAR 2 (1999 edition) on ammonia mechanical refrigeration systems, ANSI/ASHRAE 15 (2004), the safety code for mechanical refrigeration, and ANSI/ASME B31.5 (2001) on refrigeration piping as further references.<ref name="Febo-8-125" />


The wider regulatory context favoured ammonia. The Montreal Protocol of 1987 and the US Clean Air Act of 1990 phased out chlorofluorocarbon (CFC) production, by 1 January 1996 in the United States. The Beijing amendment of 1999 set dates for ending production of hydrochlorofluorocarbons (HCFCs).<ref name="Febo-8-117">Febo (2008), p. 8-117.</ref><ref name="Febo-8-118" /> Ammonia systems head the handbook's list of alternatives to halogenated refrigerant systems.<ref name="Febo-8-118" /> These rules and editions describe the situation in 2007–2008; later editions and other countries may differ.
The wider regulatory context favoured ammonia. The Montreal Protocol of 1987 and the US Clean Air Act of 1990 phased out chlorofluorocarbon (CFC) production, by 1 January 1996 in the United States. The Beijing amendment of 1999 set dates for ending production of hydrochlorofluorocarbons (HCFCs).<ref name="Febo-8-117">Febo (2008), p. 8-117.</ref><ref name="Febo-8-118" /> Ammonia systems head the handbook's list of alternatives to halogenated refrigerant systems.<ref name="Febo-8-118" /> These rules and editions describe the situation in 2007–2008; later editions and other countries may differ.

Revision as of 22:33, 7 November 2026

Ammonia refrigeration is mechanical or absorption refrigeration that uses anhydrous ammonia (NH3, refrigerant number R-717) as the working fluid. It takes heat from a cold space or product and rejects it elsewhere by evaporating and condensing the ammonia.[1][2] Ammonia systems head the handbook's list of alternatives to halogenated refrigerants. Systems holding more than 10,000 lb (4540 kg) of ammonia are quite common in industry, for example in large refrigerated warehouses and in low-temperature process cooling.[3][4][5] Under the refrigerant safety classification of ANSI/ASHRAE 34 (2004 edition), ammonia is class B2: higher toxicity and lower flammability.[1][2]

The hazards are toxicity, fire, explosion and contamination of stored goods.[6] Ammonia burns only between about 15 and 28 percent by volume in air and has a low heat of combustion, so fires are infrequent.[7][4] It also needs a large ignition energy, more than 1000 mJ in air.[7] In tight rooms such as refrigerated storage areas, however, a large release can form a flammable mixture whose ignition causes major structural damage.[4] Its toxicity acts at concentrations far below the flammable range.[8][7] The NFPA Fire Protection Handbook (2008) describes the US safeguards of the time: a separate machinery room, ventilation and gas detection, explosion venting, water spray and a high level of maintenance.[9][6]

Refrigerant and refrigeration cycle

All refrigeration systems take heat from one space or medium and transfer it to another. A refrigerant absorbs heat when it changes from liquid to gas, and releases heat when it condenses back to a liquid.[1] A mechanical system has a receiver, an expansion valve, an evaporator, a compressor and a condenser. High-pressure liquid from the receiver expands through the valve, which lowers its pressure and temperature, and then evaporates in the coils of the evaporator.[1] The compressor raises the pressure of the low-pressure gas, and the hot gas gives up its heat in the condenser and returns to the receiver as a liquid.[1] Compressors may be reciprocating, centrifugal or rotary screw machines.[2]

In the United States, refrigeration capacity is expressed in tons. One ton is the heat needed to melt 1 ton (2000 lb, 907 kg) of ice at 0 °C in 24 hours. With a heat of fusion of about 144 Btu/lb (3.4 × 105 J/kg), this equals 12,000 Btu/h, or 3.5 kW.[1]

Ammonia is also used in absorption refrigeration, where a heat-driven generator replaces the compressor.[10] Ammonia-water units serve large-tonnage industrial applications that need low process temperatures. Their solutions reach vapour pressures of up to 295 psi (2030 kPa) at cycle conditions, so the vessels must be much stronger than those of water-lithium bromide machines, which run under vacuum.[5] Febo (2008) notes that ammonia absorption systems share the inherent hazards of ammonia and need the same safeguards.[5] In indirect systems the refrigerant cools an intermediate liquid, called brine, which is then circulated to the space or product.[5] Indirect systems can sometimes allow a toxic refrigerant where the machine room can be placed safely away from normally occupied areas.[9]

Properties of anhydrous ammonia

Anhydrous ammonia is a nitrogen atom bonded to three hydrogen atoms. The word ammonia is, strictly, a solution of anhydrous (meaning "without water") ammonia in water.[11] Lemoff (2008) classifies it as a flammable, liquefied, industrial gas. Its NFPA 704 hazard ratings are 3 for health, 1 for flammability and 0 for instability, and its UN number is 1005.[11] Moist ammonia attacks copper, zinc and many brass and bronze alloys vigorously. LP-gas equipment of these metals must therefore be changed to steel before it is converted to ammonia service.[11][4]

At its normal boiling point of −33 °C (−28 °F), liquid ammonia has a density of 682.4 kg/m³ and a latent heat of evaporation of 1371 kJ/kg.[4] At normal temperature and pressure (NTP) the gas has a density of about 0.72 kg/m³. One cubic foot of liquid produces about 885 ft³ of gas.[4] The two densities given on the same page imply a ratio of about 950 (682.4/0.72); the worked example below uses the density. At normal temperatures the gas weighs about 0.6 times as much as air, and released liquid floats and boils on water.[4] Table 8.12.1 of the handbook, taken from ANSI/ASHRAE 34-2004, gives a specific gravity of 0.59 relative to air and an autoignition temperature of 651 °C (1204 °F).[2]

Property Value Source
Boiling point −33 °C (−28 °F) Febo (2008); Lemoff (2008)
Specific gravity of gas (air = 1) 0.59 Febo (2008)
Autoignition temperature 651 °C (1204 °F) Febo (2008)
Flammable limits in air 16.0–25.0 % (ASHRAE 34-2004); 15.0–28.0 % (NFPA 53, 2004) Febo (2008); Rosales and Stoltzfus (2008)
Minimum ignition energy in air more than 1000 mJ Rosales and Stoltzfus (2008)
Maximum closed-vessel explosion pressure 5.4 bar gauge Zalosh (2002)
Severe sensory irritation in humans 700–1700 ppm Purser (2002)
30-minute LC50 in mammals 1,400–8,000 ppm Purser (2002)

The flammability limits differ slightly between sources. Table 8.12.1 gives 16.0 to 25.0 percent by volume in air.[2] Table 9.17.3, based on NFPA 53 (2004 edition), gives 15.0 to 28.0 percent in air and 15.0 to 79.0 percent in oxygen.[7] The same table lists a minimum ignition energy of more than 1000 mJ in air. This is several thousand times the energy needed to ignite methane, which is 0.300 mJ.[7][12]

The nitrogen in the molecule takes no part in combustion, which explains the high lower limit and the low heat of combustion.[11] For this reason the US Department of Transportation classifies anhydrous ammonia as a nonflammable gas for interstate transport, although it can be made to burn in air.[13] In the technical sense it remains a flammable gas. Every flammable gas has a lower and an upper flammable limit, and its mixtures with air ignite within this range when the minimum ignition energy is supplied.[13]

Toxicity and warning properties

The pungent odour and irritant properties of ammonia act as warnings, but their value depends on the rate of release.[4] A large liquid leak can rapidly produce a large gas cloud, so that people are trapped and killed before they can leave the area.[4] The human sense of smell also becomes accustomed to the odour over time. Lemoff (2008) stresses that this matters in plants that use large quantities, such as many large refrigerated warehouses.[4]

The SFPE handbook gives toxicity data for ammonia as an irritant gas. In Table 2-6.1 of Purser (2002), severe sensory irritation in humans occurs at 700 to 1700 ppm.[8] The 30-minute lethal concentration for half of exposed mammals (LC50) lies between 1,400 and 8,000 ppm, and the RD50 for mice, the concentration that halves the breathing rate, is 303 ppm.[14][8] Ammonia is also one of the irritants that Purser lists among combustion products, which links it to fire toxicity in general.[8]

One percent by volume is 10,000 ppm. A lower flammable limit of 15 percent therefore equals 150,000 ppm, about 100 times the lower end of the LC50 range.[7][8] A release that is far too dilute to burn can still be lethal.

Fire service and safety practice in the United States uses the concept of an atmosphere immediately dangerous to life or health. The Occupational Safety and Health Administration (OSHA) defines it as an atmosphere that poses an immediate hazard to life or produces immediate, irreversible, debilitating effects on health.[15] Refrigerants with a B toxicity rating, such as ammonia, present personnel hazards that must be addressed in design and emergency planning.[2]

Fire and explosion behaviour

Released outdoors, anhydrous ammonia rarely reaches its lower flammable limit except in small zones near the leak.[4] Even after large liquid releases, ignitable concentrations tend to form discontinuous pockets, and with the low heat of combustion this reduces the chance of sustained burning.[4] Experience shows the same in conventional, reasonably well-ventilated buildings. In unusually tight rooms, such as refrigerated process or storage areas, a release of liquid or of large quantities of gas can build up a flammable mixture and cause a combustion explosion.[4] The pressure is lower than with most flammable gases but enough to do major structural damage. Ammonia fires are therefore infrequent, and where ignition does occur an explosion is the likely result.[4]

Zalosh (2002) reports maximum closed-vessel explosion pressures of 6.8 to 8.1 bar gauge for most flammable gases. Ammonia is one of two exceptions, at 5.4 bar gauge.[16] This is still more than 50 times the damage threshold of 0.1 bar gauge that Zalosh uses to separate low-strength from high-strength enclosures.[17]

Worked example: concentration after a release. A release of 100 kg of liquid ammonia evaporates to about 100/0.72 = 139 m³ of gas at NTP, using the gas density given by Lemoff (2008).[4] If this gas spread evenly through a closed cold store of 1000 m³, the average concentration could not exceed 139/1000 = 14 percent. That is just below the lower limit of 15 to 16 percent, but local pockets near the leak can be richer.[4][2] The same 139 m³ of gas would be enough to bring about 139,000 m³ of air to 1000 ppm, a concentration within the severe irritation range of Purser's table.[8] The calculation ignores absorption, leakage and ventilation, so it is an upper estimate of the average concentration.

Machinery room and building safeguards

In the practice described in the 2008 handbook, refrigeration machinery is best placed in a separate room, cut off from adjoining occupancies and limited to the refrigeration machinery and controls.[9] Electrical switchgear, boilers and fuel-fired equipment belong in other rooms. Even the noncombustible refrigerants of classes A1 and B1 can be decomposed by arcs, flames and hot surfaces into corrosive chlorides and fluorides.[9] The room should be of noncombustible construction. Cutoffs should have a 1-hour fire rating for flammability class 1 and 2 refrigerants, and 2 hours where class 3 refrigerants are used.[9]

Where class 2 and 3 refrigerants are used, the possibility of a room explosion must be considered. Outdoor locations or rooms of damage-limiting construction, designed with NFPA 68 on deflagration venting, limit the damage.[9] Febo (2008) warns that ammonia, although class 2, is often treated as exempt from these criteria because of an exemption for electrical equipment. This exemption has proved ill-considered in a number of explosion incidents involving ammonia refrigeration systems.[9]

For class 2 and 3 refrigerants the machine room should conform to NFPA 70, the US National Electrical Code.[9] For ammonia, some US codes and authorities having jurisdiction accept ordinary electrical equipment under one of two conditions. Either the room is continuously ventilated with an alarm on ventilation failure, or a vapour detector starts the ventilation and sounds an alarm at 1000 ppm or less.[9] Such a detector is a gas detection system in its own right. All refrigerants other than class A1 need mechanical ventilation. Where flammability is an issue, continuous mechanical ventilation of 1 ft³/min per ft² (0.3 m³/min per m²) of floor area limits the chance of an explosive concentration during normal or minor leakage.[9]

Worked example: ventilation. A machine room of 10 m × 8 m with a height of 5 m has a floor area of 80 m² and a volume of 400 m³. The ventilation rate is 0.3048 × 80 = 24.4 m³/min, or 0.41 m³/s, which is about 3.7 air changes per hour.[9]

Explosion venting calculation

For low-strength enclosures, which fail at pressures below about 1.5 psig (0.1 bar gauge), Zalosh (2002) gives the Swift-Epstein venting equation.[17] The required vent area grows with the inside surface area of the room and with a fuel constant. It falls with the square root of the overpressure that the room can withstand.[18]

Av=CAsPred

Symbol Description Unit
Av vent area m² (or ft²)
C fuel characteristic constant; 0.05 psig1/2 (0.013 bar1/2) for anhydrous ammonia, 0.14 psig1/2 (0.037 bar1/2) for methane psig1/2 or bar1/2
As internal surface area of the enclosure m² (or ft²)
Pred overpressure damage threshold of the enclosure psig or bar

The equation is meant for damage thresholds between 0.35 and 1.5 psig and for enclosures with a length-to-diameter ratio below 3. The damage threshold must also exceed the vent opening pressure by more than 0.35 psi.[18] The C values are the highest inferred from tests in enclosures of 0.18 to 82.3 m³, and most test data correspond to lower values.[18] For compact high-strength enclosures, Zalosh gives a separate vent area equation from NFPA 68.[18]

Worked example: vent area. The 10 m × 8 m × 5 m machine room has an internal surface area of 2 × (80 + 50 + 40) = 340 m². Its walls can withstand 1.0 psig (6.9 kPa), within the validity range. With C = 0.05 psig1/2 for ammonia, the vent area is 0.05 × 340 / √1.0 = 17 m².[18]

The metric constant gives the same answer: 0.013 × 340 / √0.0689 = 16.8 m², rounded up to 17 m². For methane the same room would need 0.14 × 340 = 47.6 m², almost three times as much.[18] The low fuel constant of ammonia thus reduces the vent area, but 17 m² is still about a tenth of the 2 × (50 + 40) = 180 m² of wall area of this room.

Fire protection and emergency response

Fire emergencies are generally controlled by reducing the heat of the fire with water and, if possible, shutting off the gas supply. Water is applied as a spray from hoses or fixed nozzles.[9] Where the construction is combustible or flammable refrigerants are used, automatic sprinklers provide the most reliable fire protection, and all machine rooms should have portable extinguishers for at least Class B and C fires.[6] A high level of maintenance limits releases from equipment and piping. ANSI/ASHRAE 15, the safety code for mechanical refrigeration, sets out requirements for piping and pressure relief, and piping should be protected from mechanical damage.[6]

A release without fire is handled by directing, diluting and dispersing the gas away from people and goods while the flow is stopped.[6] Because ammonia dissolves readily in water, water spray controls the spread of escaping gas well.[4] Fire fighters using hose streams need breathing apparatus because of the toxic and inerting properties of the gas, and full protective clothing where contact with the liquid is likely.[4] Water should not be put on pools of cryogenic liquid unless the vapours can be controlled, because it increases the rate of evaporation.[4] Emergency plans should cover control of the release, protection of personnel, and decontamination or preservation of the stored goods.[6]

Ammonia is shipped and stored in a compressed gas cylinder, in cargo tank trucks, rail tank cars and barges, and in pressure tanks or insulated cryogenic tanks.[4] Containers holding less than 165 lb (75 kg; the handbook prints 79 kg, a conversion error) need not have overpressure protection devices, as described in the 2008 handbook. Lemoff (2008) explains this as a trade-off between the risk of container rupture and the risk of a toxic release indoors.[4]

Regulation in the United States

The handbook describes the US regulatory position around 2008. OSHA and Environmental Protection Agency (EPA) rules on ammonia refrigeration apply above quantity limits of typically 500 to 1000 lb (227 to 454 kg).[3] The OSHA Process Safety Management standard, 29 CFR 1910.119, applies to systems with more than 10,000 lb (4540 kg) of ammonia, which Febo (2008) describes as quite common in industrial systems.[3] Large systems of this kind are found in refrigerated warehouses and in industrial plants, where they form part of the hazards of an industrial occupancy.[4][3] The handbook lists ANSI/IIAR 2 (1999 edition) on ammonia mechanical refrigeration systems, ANSI/ASHRAE 15 (2004), the safety code for mechanical refrigeration, and ANSI/ASME B31.5 (2001) on refrigeration piping as further references.[6]

The wider regulatory context favoured ammonia. The Montreal Protocol of 1987 and the US Clean Air Act of 1990 phased out chlorofluorocarbon (CFC) production, by 1 January 1996 in the United States. The Beijing amendment of 1999 set dates for ending production of hydrochlorofluorocarbons (HCFCs).[19][3] Ammonia systems head the handbook's list of alternatives to halogenated refrigerant systems.[3] These rules and editions describe the situation in 2007–2008; later editions and other countries may differ.

See also

Notes

  1. ↑ 1.0 1.1 1.2 1.3 1.4 1.5 Febo (2008), p. 8-119.
  2. ↑ 2.0 2.1 2.2 2.3 2.4 2.5 2.6 Febo (2008), p. 8-121.
  3. ↑ 3.0 3.1 3.2 3.3 3.4 3.5 Febo (2008), p. 8-118.
  4. ↑ 4.00 4.01 4.02 4.03 4.04 4.05 4.06 4.07 4.08 4.09 4.10 4.11 4.12 4.13 4.14 4.15 4.16 4.17 4.18 4.19 4.20 4.21 Lemoff (2008), p. 6-179.
  5. ↑ 5.0 5.1 5.2 5.3 Febo (2008), p. 8-123.
  6. ↑ 6.0 6.1 6.2 6.3 6.4 6.5 6.6 Febo (2008), p. 8-125.
  7. ↑ 7.0 7.1 7.2 7.3 7.4 7.5 Rosales and Stoltzfus (2008), p. 9-230.
  8. ↑ 8.0 8.1 8.2 8.3 8.4 8.5 Purser (2002), p. 2-92.
  9. ↑ 9.00 9.01 9.02 9.03 9.04 9.05 9.06 9.07 9.08 9.09 9.10 9.11 Febo (2008), p. 8-124.
  10. ↑ Febo (2008), p. 8-122.
  11. ↑ 11.0 11.1 11.2 11.3 Lemoff (2008), p. 6-178.
  12. ↑ Rosales and Stoltzfus (2008), p. 9-229.
  13. ↑ 13.0 13.1 Lemoff (2008), p. 6-166.
  14. ↑ Purser (2002), p. 2-91.
  15. ↑ Loflin (2008), p. 12-110.
  16. ↑ Zalosh (2002), p. 3-407.
  17. ↑ 17.0 17.1 Zalosh (2002), p. 3-415.
  18. ↑ 18.0 18.1 18.2 18.3 18.4 18.5 Zalosh (2002), p. 3-416.
  19. ↑ Febo (2008), p. 8-117.

References

  • Febo, H. L., Jr. (2008). Refrigeration systems. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 8-117–8-125). National Fire Protection Association.
  • Lemoff, T. C. (2008). Gases. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-165–6-186). National Fire Protection Association.
  • Loflin, M. E. (2008). Safety, medical, and health issues and programs. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 12-107–12-125). National Fire Protection Association.
  • Purser, D. A. (2002). Toxicity assessment of combustion products. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-83–2-171). National Fire Protection Association; Society of Fire Protection Engineers.
  • Rosales, K., & Stoltzfus, J. M. (2008). Oxygen-Enriched atmospheres. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-225–9-243). National Fire Protection Association.
  • Zalosh, R. (2002). Explosion protection. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 3-402–3-421). National Fire Protection Association; Society of Fire Protection Engineers.