A '''Heat detector''' is a fire-detection device that responds to thermal energy transferred from a fire to its sensing element. Fixed-temperature devices operate at a selected temperature, while rate-of-rise and rate-compensated devices respond to temperature change. Most heat detectors are located on or near the ceiling, where a ceiling jet delivers hot gases.<ref name="NUREG-1805-12-1">U.S. Nuclear Regulatory Commission (2005), pp. 12-1–12-2.</ref><ref name="IFEG-2.7-2">Australian Building Codes Board et al. (2005), p. 2.7-2.</ref>
A '''heat detector''' is a fire-detection device that operates when its sensing element reaches a specified temperature or responds to a sufficiently rapid temperature rise. It detects thermal conditions rather than smoke particles. Its response depends on heat reaching the device and then changing the temperature or physical behaviour of the sensing element.<ref name="SMC_4-5_4-7">Schifiliti, Meacham, and Custer (2002), pp. 4-5–4-7.</ref><ref name="N_12-1_12-4">Iqbal and Salley (2004), pp. 12-1–12-4.</ref>


Heat detectors are among the oldest automatic fire detectors and typically have a low false-alarm rate. They usually respond later than smoke detectors because they do not detect smoke. They are most suitable for confined spaces with rapidly growing high-heat fires, environments unsuitable for other detectors or applications where activation speed is secondary.<ref name="NUREG-1805-12-1" />
Hot gases moving beneath a ceiling commonly provide the exposure that heats the element. Gas temperature, gas velocity, detector position and thermal lag all affect when the device operates. The surrounding gas can therefore be hotter than the detector's nominal operating temperature before a fixed-temperature device responds.<ref name="IFEG_2.7-2">Australian Building Codes Board et al. (2005), p. 2.7-2.</ref><ref name="N_12-3">Iqbal and Salley (2004), p. 12-3.</ref>


The device measures a prescribed change in a physical or electrical property of its material or gas. That response depends on heat transfer, sensing-element properties and thermal inertia, so the air temperature at activation can differ from the element's rated temperature.<ref name="NUREG-1805-12-2">U.S. Nuclear Regulatory Commission (2005), p. 12-2.</ref><ref name="Schifiliti-4-7">Schifiliti, Meacham, and Custer (2002), p. 4-7.</ref>
Heat detectors include fixed-temperature, rate-of-rise, rate-compensated and combined arrangements. These mechanisms have different responses to fast and slow heating. Engineering assessment connects the selected mechanism to the expected fire, the normal environment and the time available for the intended protective action.<ref name="N_12-3_12-5">Iqbal and Salley (2004), pp. 12-3–12-5.</ref><ref name="SMC_4-19_4-20">Schifiliti, Meacham, and Custer (2002), pp. 4-19–4-20.</ref>


== Detector types ==
== What a heat detector senses ==


Fixed-temperature heat detectors operate when their sensing element reaches a specified point. Fusible elements melt at a predetermined temperature and close alarm contacts, while bimetallic and electronic elements use other property changes. Fused elements and line sections can require replacement rather than reset.<ref name="NUREG-1805-12-3">U.S. Nuclear Regulatory Commission (2005), p. 12-3.</ref><ref name="NUREG-1805-12-4">U.S. Nuclear Regulatory Commission (2005), p. 12-4.</ref>
A heat detector responds to thermal conditions at its sensing element. Fixed-temperature devices operate when the element reaches a specified temperature. Rate-of-rise devices respond to a sufficiently rapid temperature increase. Iqbal and Salley describe both principles in NUREG-1805, a 2004 handbook prepared for United States nuclear fire protection inspections.<ref name="N_12-1_12-4" />


Rate-of-rise heat detectors respond to the rate at which temperature increases. Rate-compensated designs account for that increase in a different way, using compensation to reduce inappropriate response. These approaches can support earlier detection in suitable scenarios, but they still depend on heat transfer and the selected set point.<ref name="NUREG-1805-12-4" /><ref name="Schifiliti-4-7" />
The detector forms an initiating input to a [[Fire alarm system]]; its operation does not itself mean that occupants have received a warning or that suppression has begun. The SFPE Handbook separates detection, processing and signalling when analysing the system. Those later functions can introduce additional time after the heat-sensitive element operates.<ref name="SMC_4-2_4-3">Schifiliti, Meacham, and Custer (2002), pp. 4-2–4-3.</ref>


Line-type detectors use a continuous sensitive element along a cable or tube. One arrangement melts insulation so that two conductors contact, while another uses a temperature-sensitive semiconductor to increase current. These provide spatial coverage different from a compact spot detector.<ref name="NUREG-1805-12-4" />
Heat detection requires sufficient energy to reach and heat the element, while a [[Smoke detector]] instead responds to combustion particles, which can provide an earlier indication in suitable fire conditions. A [[Flame detector]] senses emitted radiation and has different exposure requirements. The appropriate detection principle depends on the expected fire signature and the objective of the system.<ref name="N_12-1">Iqbal and Salley (2004), p. 12-1.</ref><ref name="SMC_4-3_4-4__4-30">Schifiliti, Meacham, and Custer (2002), pp. 4-3–4-4, 4-30.</ref>


Pneumatic detectors use expansion of heated air in a tube or chamber to move a diaphragm and actuate the alarm. They can be available as line or spot types. Their operating principle differs from fusible-metal devices but still relies on heat reaching and changing the sensing system.<ref name="NUREG-1805-12-4" />
Heat detection therefore cannot be described as universally interchangeable with smoke detection. NUREG-1805 associates it with situations such as confined spaces where rapidly developing fires are expected or environments unsuitable for other detection. The same source warns that thermal detection may be too slow for an early life-safety warning. These observations concern the relationship between the fire and the sensing mechanism.<ref name="N_12-1" />


[[Flame detector]] technologies detect radiant energy or flame characteristics rather than only convected heat. They address a different indication of fire and should not be used as interchangeable with heat detectors. The scenario determines which indication provides timely and reliable detection.<ref name="Schifiliti-4-30">Schifiliti, Meacham, and Custer (2002), pp. 4-30–4-31.</ref><ref name="IFEG-1.8-7">Australian Building Codes Board et al. (2005), p. 1.8-7.</ref>
== Fixed-temperature and rate-of-rise mechanisms ==


== Heat transfer and ceiling jet ==
A fusible fixed-temperature element uses a material that melts at its operating temperature. Melting releases a mechanism or closes contacts to initiate the signal; the fusible element is not restored simply by cooling. NUREG-1805 distinguishes this arrangement from bimetallic devices that can return to their original condition after heating stops.<ref name="N_12-3" />


A [[Ceiling jet]] forms when the plume reaches the ceiling and spreads horizontally. Hot gases transfer energy to the ceiling and to heat-responsive devices. The detector's response therefore depends on the plume and ceiling-jet temperatures, velocity and position relative to the device.<ref name="IFEG-2.7-2" /><ref name="NUREG-1805-12-2">U.S. Nuclear Regulatory Commission (2005), p. 12-2.</ref>
Bimetallic devices use metals with different thermal expansion behaviour: a strip can bend, or a shaped disc can reverse curvature when heated. This movement operates the electrical contacts. Electronic thermal detectors instead monitor a temperature-dependent electrical resistance and can apply a fixed-temperature or rate-of-rise criterion.<ref name="N_12-3__12-5">Iqbal and Salley (2004), pp. 12-3, 12-5.</ref>


Heat reaches the sensing element by convection, with conduction into the element and possible radiation affecting its boundary. The element then warms according to its mass and thermal properties. This creates thermal lag, where the surrounding air can be hotter than the element's rated temperature at activation.<ref name="NUREG-1805-12-2">U.S. Nuclear Regulatory Commission (2005), p. 12-2.</ref><ref name="Schifiliti-4-7" />
A pneumatic rate-of-rise detector uses expanding air in a chamber or tube: a small vent accommodates gradual changes, while sufficiently rapid heating produces pressure faster than it can escape. That pressure operates a diaphragm and contacts. NUREG-1805 describes example operating rates around 7–8 °C per minute; this is not a universal threshold for every product.<ref name="N_12-4">Iqbal and Salley (2004), p. 12-4.</ref>
[[File:fse-heat-detector-v1.svg|thumb|upright=1.5|alt=Plume and ceiling jet transfer heat to a detector element, which responds after a lag.|Heat-detector response depends on ceiling-jet exposure and thermal lag. Based on Australian Building Codes Board et al. (2005), p. 2.7-2 and Schifiliti, Meacham, and Custer (2002), p. 4-7.]]


Detector response is not determined by ambient room temperature alone. Fire heat release rate, plume geometry and airflow change the local exposure. A detector that is appropriately rated for one ceiling and fire can respond differently in another.<ref name="Schifiliti-4-7" /><ref name="Schifiliti-4-9">Schifiliti, Meacham, and Custer (2002), p. 4-9.</ref>
Heat detection can cover a compact point or extend along a line. NUREG-1805 describes a continuous cable in which heat-sensitive insulation separates two conductors until the operating condition is reached. Another arrangement uses temperature-dependent electrical conduction within the cable assembly. Pneumatic line detection instead responds to expansion within a length of tubing. The exposed length and the distribution of heating then affect the signal.<ref name="N_12-3__12-5" />


Smooth ceilings support more predictable distribution of hot gases, while obstructions and unusual ceiling forms change the flow. Spacing and location should therefore be based on actual construction and expected fire position rather than on a generic ceiling grid.<ref name="NUREG-1805-12-3" /><ref name="Schifiliti-4-5">Schifiliti, Meacham, and Custer (2002), p. 4-5.</ref>
Combination devices can include both fixed-temperature and rate-of-rise functions: the rapid-rise element can respond during fast heating, while the fixed-temperature function remains relevant during slower heating. Rate-compensated devices use differential expansion to reduce the effect of thermal lag. Their internal mechanisms differ from a simple element represented by one uniform temperature.<ref name="N_12-4_12-5">Iqbal and Salley (2004), pp. 12-4–12-5.</ref><ref name="SMC_4-7">Schifiliti, Meacham, and Custer (2002), p. 4-7.</ref>


== Response time index and thermal lag ==
[[File:fse-heat-detector-v3.svg|thumb|upright=1.5|alt=Fixed-temperature alarm at a threshold and rate-of-rise alarm during rapid increase.|Fixed-temperature and rate-of-rise detection principles. Based on Iqbal and Salley (2004), pp. 12-3–12-4 and Schifiliti, Meacham, and Custer (2002), p. 4-19.]]


[[Response time index (RTI)]] characterises the thermal responsiveness of a heat-sensing element. It relates the element's temperature change to its exposure and is used to estimate activation time under changing conditions. A lower-RTI device generally responds more quickly to a developing exposure, although the complete model still matters.<ref name="Schifiliti-4-7" /><ref name="IFEG-2.7-2" />
== Transport from the fire to the sensing element ==


Thermal inertia causes the element to lag behind the surrounding gas temperature. The rated temperature is reached only after enough energy has been absorbed, so the air temperature at activation can be higher than the element's nominal rating. This is one reason detector response cannot be predicted from rating alone.<ref name="NUREG-1805-12-2">U.S. Nuclear Regulatory Commission (2005), p. 12-2.</ref>
Hot gases rise in a plume and spread beneath a ceiling as a [[Ceiling jet]]. A detector in this flow receives heat from the moving gases. Both gas temperature and gas velocity affect the transfer of energy to the element. The International Fire Engineering Guidelines (IFEG, 2005) also identify the element's distance below the ceiling as relevant.<ref name="IFEG_2.7-2" />
[[File:fse-heat-detector-v2.svg|thumb|upright=1.5|alt=Gas temperature rises quickly while element temperature follows more slowly past the rating.|Element temperature lags behind gas temperature. Based on U.S. Nuclear Regulatory Commission (2005), p. 12-2 and Schifiliti, Meacham, and Custer (2002), p. 4-7.]]


The lumped thermal model links element temperature with gas temperature and a convective coefficient. That model assumes a suitable thermal mass and exposure description. Detector-specific RTI data and the fire's time-dependent heat flux must be consistent with it.<ref name="IFEG-2.7-2" /><ref name="Schifiliti-4-7" />
The temperature and velocity are not uniform throughout the flow, and their values change with location relative to the fire and with depth below the ceiling. A detector placed outside the relevant hot flow does not receive the exposure assumed for a detector within it. Geometry is therefore part of the response calculation rather than a separate installation detail.<ref name="IFEG_2.7-2" /><ref name="SMC_4-7" />


A heat detector can be approximated as having a low RTI for smoke-detector response in some nuclear methods. This provides a way to use heat-response analysis for smoke detectors, but it is an approximation rather than a complete smoke-response model. Smoke properties and entry processes add further uncertainty.<ref name="NUREG-1805-11-6">U.S. Nuclear Regulatory Commission (2005), p. 11-6.</ref><ref name="Schifiliti-4-23">Schifiliti, Meacham, and Custer (2002), p. 4-23.</ref>
Thermal lag is the delay caused by the sensing element taking time to heat. During rising gas temperature, the element can remain cooler than the surrounding gases. Consequently, the gas temperature at operation can exceed the detector's nominal operating temperature. The rating applies to the element's response, not to instantaneous equality between gas and element temperatures.<ref name="N_12-3" />


== Activation time ==
The [[Detector activation time]] contains the effects of exposure and thermal response. A steady-exposure calculation begins when the assumed hot gases reach the element, so it does not automatically include the earlier transport of those gases from the fire. Schifiliti and colleagues explicitly identify this transport omission in the simplest steady ceiling-jet model.<ref name="SMC_4-7_4-8">Schifiliti, Meacham, and Custer (2002), pp. 4-7–4-8.</ref>


[[Detector activation time]] includes heat production, transport to the detector and heating of the sensing element. Fire growth, location, spacing and thermal properties all influence it. A faster fire can produce a shorter activation time under otherwise similar conditions, but the relationship need not be simple.<ref name="Schifiliti-4-7" /><ref name="Schifiliti-4-9" />
[[File:fse-heat-detector-v1.svg|thumb|upright=1.5|alt=Plume and ceiling jet transfer heat to a detector element, which responds after a lag.|Heat-detector response depends on ceiling-jet exposure and thermal lag. Based on Australian Building Codes Board et al. (2005), p. 2.7-2 and Schifiliti, Meacham, and Custer (2002), p. 4-7.]]
 
Spacing determines how far hot gases must travel before reaching the device. Schifiliti and colleagues analyse how ceiling height and detector spacing affect response, with different outcomes for fixed-temperature and rate-of-rise devices. These models are scenario-specific and should not be converted into a universal maximum spacing.<ref name="Schifiliti-4-5" /><ref name="Schifiliti-4-19">Schifiliti, Meacham, and Custer (2002), p. 4-19.</ref>
 
Fixed-temperature and rate-of-rise devices can favour different numbers of detectors. In one analysis, more fixed-temperature devices were required for a given objective than rate-of-rise devices, but this conclusion was not universal. Device type and scenario determine the comparison.<ref name="Schifiliti-4-19" />
[[File:fse-heat-detector-v3.svg|thumb|upright=1.5|alt=Fixed-temperature alarm at a threshold and rate-of-rise alarm during rapid increase.|Fixed-temperature and rate-of-rise detection principles. Based on U.S. Nuclear Regulatory Commission (2005), pp. 12-3–12-4 and Schifiliti, Meacham, and Custer (2002), p. 4-19.]]


C/VM2 uses a critical-velocity method and a heat-release rate method for heat-detector response in its 2025 design scenarios. Those are specific analytical methods, not universal guarantees of activation time. The required fire and ceiling conditions must be represented in the calculation.<ref name="CVM2-26">Ministry of Business, Innovation and Employment (2025), p. 26.</ref><ref name="IFEG-2.7-2" />
== Thermal response and response time index ==


== Heat and smoke detection ==
A common model treats the sensing element as a single uniform thermal mass. This is called the lumped-mass approximation. It assumes that temperature differences within the element can be neglected. The temperature then increases according to the heat transferred from the gas and the element's thermal response.<ref name="SMC_4-5_4-6">Schifiliti, Meacham, and Custer (2002), pp. 4-5–4-6.</ref><ref name="N_12-6">Iqbal and Salley (2004), p. 12-6.</ref>


A [[Smoke detector]] usually activates before a heat detector because smoke is produced earlier and does not require the same heat output. Using both can provide complementary information about the fire's development. The combination should be selected for its actual response rather than assuming redundancy guarantees earlier detection.<ref name="NUREG-1805-12-1" /><ref name="Schifiliti-4-23" />
The [[Response time index]] (RTI) expresses thermal sensitivity in this model. For a given gas exposure, a smaller RTI gives faster heating of the element. The governing equation relates the rate of element heating to gas velocity and the temperature difference. As the element approaches the gas temperature, that driving temperature difference becomes smaller.<ref name="SMC_4-6">Schifiliti, Meacham, and Custer (2002), p. 4-6.</ref>


Heat detectors typically have a low false-alarm rate, while smoke detectors can be more susceptible to nuisance signatures. That does not make heat detection universally better, because slower activation can reduce available escape time. Selection must balance timeliness and reliability.<ref name="NUREG-1805-12-1" /><ref name="Proulx-3-351">Proulx (2002), p. 3-351.</ref>
<math display="block">\frac{dT_d}{dt}=\frac{\sqrt{u}}{\mathrm{RTI}}(T_g-T_d)</math>


Smoke-detector response can be approximated using heat-response models in some methods, but actual smoke entry and particle properties remain important. A low-RTI heat model alone does not describe every smoke-detector response. The two measurement problems should be distinguished.<ref name="NUREG-1805-11-6" /><ref name="Schifiliti-4-23" />
{| class="wikitable"
! Symbol !! Description !! Unit
|-
| <math>T_d</math> || Temperature of the detector's sensing element || °C
|-
| <math>T_g</math> || Gas temperature at the sensing element || °C
|-
| <math>t</math> || Time measured from the start of the assumed exposure || s
|-
| <math>u</math> || Gas velocity at the element || m/s
|-
| <math>\mathrm{RTI}</math> || Response time index || m<sup>1/2</sup>s<sup>1/2</sup>
|-
| <math>T_a</math> || Initial element temperature, equal to ambient in this model || °C
|-
| <math>T_r</math> || Element temperature required for operation || °C
|-
| <math>t_r</math> || Time to operation under the assumed constant exposure || s
|}


Heat and smoke detection can also initiate different responses. Heat detectors may be used to activate sprinklers or other thermal devices, while smoke detection can support earlier alarm and investigation. The complete alarm and suppression sequence should be assessed rather than only the sensor's threshold.<ref name="IFEG-2.7-2" /><ref name="NUREG-1805-11-6" />
For constant gas temperature and velocity, the equation can be integrated to obtain the time to reach the operating temperature. The expression below uses the natural logarithm, and it applies when the element starts at ambient temperature and the gas temperature exceeds the operating threshold. It represents fixed-temperature response under the stated thermal assumptions.<ref name="SMC_4-8">Schifiliti, Meacham, and Custer (2002), p. 4-8.</ref><ref name="N_12-6" />


== Ambient conditions and unwanted alarms ==
<math display="block">t_r=\frac{\mathrm{RTI}}{\sqrt{u}}\ln\left(\frac{T_g-T_a}{T_g-T_r}\right)</math>


Detector rating must suit the ambient ceiling temperature. NUREG-1805 lists ordinary detectors rated from 57 to 74 °C for ceilings not exceeding 37.7 °C, with higher ratings for hotter environments. Choosing an inappropriate rating can cause premature activation and reduce credibility.<ref name="NUREG-1805-12-3" />
The ratio inside the logarithm uses temperature differences, so consistent Celsius differences can be used. The response time becomes longer when the operating temperature approaches the imposed gas temperature. If the gas never becomes hot enough, this constant-exposure model does not predict threshold operation. A nominal temperature rating alone is therefore insufficient to calculate a response time.<ref name="SMC_4-6_4-8">Schifiliti, Meacham, and Custer (2002), pp. 4-6–4-8.</ref>


Hot rooms such as boiler rooms and dry kilns require special consideration. Detectors intended for those conditions need to withstand high ambient temperatures for long periods and should be selected to avoid nuisance activation. Normal temperature conditions should be at least 6.6 °C below the rating for low-degree devices in the cited guidance.<ref name="NUREG-1805-12-3" />
[[File:fse-heat-detector-v2.svg|thumb|upright=1.5|alt=Gas temperature rises quickly while element temperature follows more slowly past the rating.|Element temperature lags behind gas temperature. Based on Iqbal and Salley (2004), p. 12-3 and Schifiliti, Meacham, and Custer (2002), p. 4-7.]]


[[Unwanted fire alarms]] can still occur even though heat detectors have a low false-alarm rate. Abnormal heat from uninsulated pipes, unsuitable placement or an incorrect rating can produce a non-fire signal. Those conditions should be investigated and corrected rather than accepted as unavoidable.<ref name="NUREG-1805-12-3" /><ref name="Proulx-3-351" />
== Worked example under constant exposure ==


Unwanted activation is not the only concern. Excessive sensitivity to an unusual environment can delay detection if the rating is raised unnecessarily to avoid it. The detector must be chosen for both the environment and the required response time.<ref name="NUREG-1805-12-3" /><ref name="Schifiliti-4-7" />
The SFPE Handbook's second example uses the gas conditions calculated for a 4 m² kerosene pool beneath a flat ceiling. The ceiling is 6 m above the fire and the detector is 6 m horizontally from the plume centre. The ambient temperature is 20 °C. Its calculated exposure is a gas temperature of 153 °C and a velocity of 2.4 m/s.<ref name="SMC_4-8" />


== Fire alarm system integration ==
The example detector has an RTI of 55 m<sup>1/2</sup>s<sup>1/2</sup> and an operating temperature of 57 °C. Substituting those values gives an exposure response time of approximately 11.6 s. Rounded upwards to whole seconds, the required time is 12 s. This reproduces the response reported in the handbook example.<ref name="SMC_4-8" />


A [[Fire alarm system]] uses the detector's signal to initiate alarm and notification. Detector selection should therefore include control, communication and the intended response. An appropriate heat detector can still fail to protect if the rest of the chain does not work.<ref name="Schifiliti-4-1">Schifiliti, Meacham, and Custer (2002), pp. 4-1–4-2.</ref><ref name="IFEG-1.8-7">Australian Building Codes Board et al. (2005), p. 1.8-7.</ref>
<math display="block">t_r=\frac{55}{\sqrt{2.4}}\ln\left(\frac{153-20}{153-57}\right)\ \mathrm{s}\approx12\ \mathrm{s}</math>


Heat detectors can be used in combination with smoke detectors and with suppression systems. Each initiation path should be defined, including whether an alarm, suppression action or smoke-control response follows. Backup paths should be checked for common failures rather than assumed independent.<ref name="IFEG-1.2-24">Australian Building Codes Board et al. (2005), p. 1.2-24.</ref><ref name="IFEG-2.7-2" />
This is the time for the specified element to heat under the specified exposure. It is not a claim that a detector will alarm 12 s after every kerosene fire ignites. The example assumes the calculated gas conditions are already present and remain constant. Fire growth, transport to the detector and subsequent alarm-system delays require separate treatment.<ref name="SMC_4-2_4-3__4-8">Schifiliti, Meacham, and Custer (2002), pp. 4-2–4-3, 4-8.</ref>


The detector's response must be converted into an intelligible alarm. Occupants need to know what the signal means and what to do, and that message must be audible and credible. A low false-alarm rate alone does not create an effective evacuation.<ref name="Proulx-3-350">Proulx (2002), pp. 3-350–3-351.</ref>
For growing fires, Schifiliti and colleagues divide the changing exposure into short time intervals. The updated element temperature is carried from one interval into the next. Gas temperature and velocity can then change as the fire grows. This approach preserves the element's heating history instead of restarting the calculation at ambient temperature each time.<ref name="SMC_4-8_4-9">Schifiliti, Meacham, and Custer (2002), pp. 4-8–4-9.</ref>


Testing should cover the complete activation and notification chain. Fusible elements and line sections may need replacement, and control and sounders must be checked. System maintenance should preserve the intended rating, placement and operation.<ref name="NUREG-1805-12-3" /><ref name="CVM2-13">Ministry of Business, Innovation and Employment (2025), p. 13.</ref>
== What tests and prescribed inputs represent ==


== Reliability and limitations ==
A plunge test exposes the device to a gas flow with known, constant temperature and velocity. The measured operating time can be used to infer a thermal time constant and RTI. The SFPE Handbook explains that this is a simplified representation of heat transfer. Flow around the device and heat loss into its supporting body can limit the approximation.<ref name="SMC_4-6" />


Heat detectors are usually slower than smoke detectors and may not provide enough early warning in life-threatening scenarios. Their suitability depends on expected fire growth and the available response time. Using them where early detection is essential requires careful justification.<ref name="NUREG-1805-12-1" />
Listed spacing is derived through defined test arrangements, but it does not directly state the time to respond to every fire in an actual building. Ceiling height, beams, airflow and detector exposure can differ from the test. Schifiliti and colleagues distinguish compliance with spacing rules from quantitative assessment against a specified fire-size or response objective.<ref name="SMC_4-3_4-4">Schifiliti, Meacham, and Custer (2002), pp. 4-3–4-4.</ref>


Their low false-alarm rate does not mean no unwanted alarms. Incorrect rating, abnormal ambient heat and unsuitable placement can still produce false or premature signals. Those conditions should be controlled through correct selection and management.<ref name="NUREG-1805-12-3" /><ref name="Proulx-3-351" />
In New Zealand, C/VM2, second edition (2025), prescribes heat-detector modelling inputs regardless of the installed make or model. These include RTI 30 m<sup>1/2</sup>s<sup>1/2</sup>, an activation temperature of 57 °C and a radial distance of 4.2 m. The table also specifies a position at least 25 mm below the ceiling. These values belong to that verification method's analysis.<ref name="CVM_27">Ministry of Business, Innovation and Employment (2025), p. 27.</ref>


Rated temperature and activation temperature are not identical. Thermal lag can make the surrounding air hotter than the element's rating when it finally responds, and ceiling-jet temperature is not room-average temperature. Reporting should identify which temperature is meant.<ref name="NUREG-1805-12-2">U.S. Nuclear Regulatory Commission (2005), p. 12-2.</ref><ref name="Schifiliti-4-7" />
RTI describes the interaction between the sensing element and the moving gases; it is not a temperature rating or a direct statement of the time from ignition. The same RTI can give different response times when gas temperature or velocity changes. Likewise, two detectors with the same operating temperature can respond at different times because their thermal sensitivities differ. These distinctions explain why both temperature and sensitivity appear in the model.<ref name="SMC_4-6_4-8" />


Finally, a heat detector is only one part of the alarm system. It must produce a signal that is transmitted, understood and acted upon. Effective fire safety depends on that complete sequence rather than on the detector's nominal rating alone.<ref name="Schifiliti-4-1" /><ref name="Proulx-3-350" />
The prescribed values must not be mistaken for a universal specification of actual detectors. A product can have measured characteristics different from those analysis inputs. The source distinguishes the required simulation from the device selected for installation. An engineering report therefore identifies whether its inputs are measured, assumed or prescribed by the chosen method.<ref name="CVM_27" /><ref name="SMC_4-6" />


Response modelling should distinguish the surrounding gas, the ceiling jet and the sensing element. Their temperatures can differ, and the element responds only after absorbing enough energy. Reporting one ambient room temperature cannot represent that sequence or the thermal lag at activation.<ref name="NUREG-1805-12-2" /><ref name="Schifiliti-4-7" />
== Choosing between thermal response principles ==


RTI data should be tied to the actual element and exposure. A low-RTI element can respond quickly to a suitable ceiling jet, but changing its mass, mounting or boundary conditions can change the result. Detector-specific evidence is therefore necessary when activation time is critical.<ref name="Schifiliti-4-7" /><ref name="IFEG-2.7-2" />
A fixed-temperature device and a rate-of-rise device respond to different features of the same exposure. A rapid temperature increase can activate the rate-of-rise function before the fixed-temperature element reaches its threshold. During slower heating, the rate-of-rise condition may be less favourable. Combination devices use both mechanisms to address these different conditions.<ref name="N_12-4_12-5" />


For spacing, the fire's position and the ceiling's shape should be established before applying a grid. A detector placed far from the plume can receive a weaker or later exposure, and obstructions can redirect that flow. A maximum spacing from one scenario should not be used as a universal allowance.<ref name="Schifiliti-4-5" /><ref name="Schifiliti-4-19">Schifiliti, Meacham, and Custer (2002), p. 4-19.</ref>
The handbook examines this distinction using several fire growth rates, and its examples show that detector spacing and response depend on the growth history as well as sensitivity. A device that responds earlier in one scenario need not do so in another. The result supports comparing detectors against the intended fire scenarios rather than ranking the mechanisms universally.<ref name="SMC_4-19_4-20" />


For unwanted alarms, abnormal heat and rating should be reviewed before sensitivity is changed. An incorrect rating can create premature activation, while an unnecessarily high rating can delay genuine detection. Correct selection requires both the ambient condition and the required fire response.<ref name="NUREG-1805-12-3" /><ref name="Proulx-3-351">Proulx (2002), p. 3-351.</ref>
Rate-compensated and pneumatic rate-of-rise devices require particular care in modelling, and their internal heat transfer and mechanical response are more complex than one directly exposed element. The SFPE Handbook explains that a single lumped mass may not represent these mechanisms adequately. Applying the fixed-temperature equation unchanged would omit parts of the device's operating principle.<ref name="SMC_4-7" />


A final evaluation should link detector response with notification and acceptance criteria. If the alarm arrives after the required intervention time, a lower false-alarm rate does not make the system successful. The detector must provide timely and credible information for the intended response.<ref name="Schifiliti-4-1" /><ref name="Proulx-3-350">Proulx (2002), pp. 3-350–3-351.</ref>
== Environmental effects and calculation limits ==


The detector's evidence should distinguish rated temperature, ceiling-jet temperature and element temperature. They describe different stages of exposure and can differ at activation. Keeping them separate prevents a nominal rating from being mistaken for a direct measurement of the room's condition.<ref name="NUREG-1805-12-2" /><ref name="Schifiliti-4-7" />
Normal non-fire temperatures influence the selection of a thermal operating rating. NUREG-1805 discusses higher-temperature devices for locations where ordinary ambient conditions would otherwise cause premature operation. The relevant exposure is the temperature near the detector, including expected non-fire heat sources. A rating chosen without those conditions can produce unwanted alarms.<ref name="N_12-1_12-3">Iqbal and Salley (2004), pp. 12-1–12-3.</ref>


For acceptance, activation time should be compared with the required response, not just with another detector. A slower heat detector can be suitable for some scenarios, while an earlier but less reliable alternative can be preferable in others. The decision must consider both timeliness and the credibility of the resulting alarm.<ref name="NUREG-1805-12-1" /><ref name="Proulx-3-351" />
The report's simple ceiling-jet method assumes an unconfined flat ceiling and a fire away from walls and corners. It excludes a developed hot layer beneath the jet during the period of interest. Obstructions and irregular ceilings can undermine the assumed flow. The method also does not explicitly include direct radiant heating of the sensing element.<ref name="N_12-10_12-11">Iqbal and Salley (2004), pp. 12-10–12-11.</ref>


A complete report should identify the detector type, rating, RTI where relevant, placement and the scenario used for evaluation. It should also record whether abnormal ambient conditions were included. Those details allow another reviewer to assess whether the detector's performance applies to the intended installation.<ref name="NUREG-1805-12-3" /><ref name="Schifiliti-4-7" />
The assumption of a constant RTI is itself an approximation. Schifiliti and colleagues discuss the complex gas flow around irregular detector shapes and the possibility of heat conduction into supporting parts. A plunge test may involve conditions in which those heat losses are relatively small, but their importance can differ during the slower flows of an actual fire. A thermal parameter obtained from one test condition therefore needs an appropriate range of application.<ref name="SMC_4-6" />


For final acceptance, the complete exposure and response should be documented. The fire's location, ceiling-jet behaviour, element properties and thermal lag determine activation, while the rating alone does not predict it. Those inputs should be shown explicitly so that another reviewer can assess the result.<ref name="Schifiliti-4-7" /><ref name="IFEG-2.7-2" />
Modelled response after another protective device operates also requires care. The handbook notes that its basic calculations do not account for sprinkler cooling when predicting subsequent detector or sprinkler activation. The first operating device can change the environment experienced by other devices. Their later responses cannot automatically be inferred by continuing the original unsuppressed exposure unchanged.<ref name="SMC_4-7" />


The detector should then be judged by the response it enables. An appropriate activation is one that produces a credible alarm and enough time for the intended action, not simply one that proves the element changed state. This connects heat detection with evacuation and fire-safety performance.<ref name="Schifiliti-4-1" /><ref name="Proulx-3-350" />
The gas-flow calculation and the element-response calculation have separate limitations. Correctly integrating a thermal equation cannot compensate for an unsuitable gas temperature or velocity prediction. Conversely, suitable gas conditions do not establish the correct thermal model for every detector mechanism. The assessed geometry, fire development and device behaviour must all fit the chosen method.<ref name="SMC_4-7_4-9">Schifiliti, Meacham, and Custer (2002), pp. 4-7–4-9.</ref><ref name="N_12-10">Iqbal and Salley (2004), p. 12-10.</ref>


== See also ==
== See also ==


* [[Detector activation time]]
* [[Multi-sensor detector]]
* [[Response time index (RTI)]]
* [[Thermal inertia]]
* [[Smoke detector]]
* [[Fire plume]]


== Notes ==
== Notes ==
Line 122: Line 133:
== References ==
== References ==


* Australian Building Codes Board, National Research Council of Canada, International Code Council, & Department of Building and Housing New Zealand. (2005). ''International fire engineering guidelines'' (2005 ed.). Australian Building Codes Board.
* Australian Building Codes Board, National Research Council of Canada, International Code Council, & Department of Building and Housing New Zealand. (2005). ''International fire engineering guidelines''. Australian Building Codes Board.
* Ministry of Business, Innovation and Employment. (2025). ''C protection from fire: Verification method C/VM2'' (2nd ed.). New Zealand Government.
* Iqbal, N., & Salley, M. H. (2004). ''Fire dynamics tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission fire protection inspection program'' (NUREG-1805). U.S. Nuclear Regulatory Commission.
* Proulx, G. (2002). Movement of people: The evacuation timing. In P. J. DiNenno (Ed.), ''SFPE handbook of fire protection engineering'' (3rd ed.). National Fire Protection Association.
* Ministry of Business, Innovation and Employment. (2025). ''C protection from fire: Verification method C/VM2'' (2nd ed.).
* Schifiliti, R. P., Meacham, B. J., & Custer, R. L. P. (2002). Design of detection systems. In P. J. DiNenno (Ed.), ''SFPE handbook of fire protection engineering'' (3rd ed.). National Fire Protection Association.
* Schifiliti, R. P., Meacham, B. J., & Custer, R. L. P. (2002). Design of detection systems. In P. J. DiNenno (Ed.), ''SFPE handbook of fire protection engineering'' (3rd ed., pp. 4-1–4-43). National Fire Protection Association.
* U.S. Nuclear Regulatory Commission. (2005). ''Fire dynamics tools: Quantitative fire hazard analysis methods for the U.S. nuclear regulatory commission fire protection inspection program'' (NUREG-1805). Author.


[[Category:Detection & Alarm]]
[[Category:Detection & Alarm]]

Latest revision as of 19:42, 2 November 2026

A heat detector is a fire-detection device that operates when its sensing element reaches a specified temperature or responds to a sufficiently rapid temperature rise. It detects thermal conditions rather than smoke particles. Its response depends on heat reaching the device and then changing the temperature or physical behaviour of the sensing element.[1][2]

Hot gases moving beneath a ceiling commonly provide the exposure that heats the element. Gas temperature, gas velocity, detector position and thermal lag all affect when the device operates. The surrounding gas can therefore be hotter than the detector's nominal operating temperature before a fixed-temperature device responds.[3][4]

Heat detectors include fixed-temperature, rate-of-rise, rate-compensated and combined arrangements. These mechanisms have different responses to fast and slow heating. Engineering assessment connects the selected mechanism to the expected fire, the normal environment and the time available for the intended protective action.[5][6]

What a heat detector senses

A heat detector responds to thermal conditions at its sensing element. Fixed-temperature devices operate when the element reaches a specified temperature. Rate-of-rise devices respond to a sufficiently rapid temperature increase. Iqbal and Salley describe both principles in NUREG-1805, a 2004 handbook prepared for United States nuclear fire protection inspections.[2]

The detector forms an initiating input to a Fire alarm system; its operation does not itself mean that occupants have received a warning or that suppression has begun. The SFPE Handbook separates detection, processing and signalling when analysing the system. Those later functions can introduce additional time after the heat-sensitive element operates.[7]

Heat detection requires sufficient energy to reach and heat the element, while a Smoke detector instead responds to combustion particles, which can provide an earlier indication in suitable fire conditions. A Flame detector senses emitted radiation and has different exposure requirements. The appropriate detection principle depends on the expected fire signature and the objective of the system.[8][9]

Heat detection therefore cannot be described as universally interchangeable with smoke detection. NUREG-1805 associates it with situations such as confined spaces where rapidly developing fires are expected or environments unsuitable for other detection. The same source warns that thermal detection may be too slow for an early life-safety warning. These observations concern the relationship between the fire and the sensing mechanism.[8]

Fixed-temperature and rate-of-rise mechanisms

A fusible fixed-temperature element uses a material that melts at its operating temperature. Melting releases a mechanism or closes contacts to initiate the signal; the fusible element is not restored simply by cooling. NUREG-1805 distinguishes this arrangement from bimetallic devices that can return to their original condition after heating stops.[4]

Bimetallic devices use metals with different thermal expansion behaviour: a strip can bend, or a shaped disc can reverse curvature when heated. This movement operates the electrical contacts. Electronic thermal detectors instead monitor a temperature-dependent electrical resistance and can apply a fixed-temperature or rate-of-rise criterion.[10]

A pneumatic rate-of-rise detector uses expanding air in a chamber or tube: a small vent accommodates gradual changes, while sufficiently rapid heating produces pressure faster than it can escape. That pressure operates a diaphragm and contacts. NUREG-1805 describes example operating rates around 7–8 °C per minute; this is not a universal threshold for every product.[11]

Heat detection can cover a compact point or extend along a line. NUREG-1805 describes a continuous cable in which heat-sensitive insulation separates two conductors until the operating condition is reached. Another arrangement uses temperature-dependent electrical conduction within the cable assembly. Pneumatic line detection instead responds to expansion within a length of tubing. The exposed length and the distribution of heating then affect the signal.[10]

Combination devices can include both fixed-temperature and rate-of-rise functions: the rapid-rise element can respond during fast heating, while the fixed-temperature function remains relevant during slower heating. Rate-compensated devices use differential expansion to reduce the effect of thermal lag. Their internal mechanisms differ from a simple element represented by one uniform temperature.[12][13]

Fixed-temperature alarm at a threshold and rate-of-rise alarm during rapid increase.
Fixed-temperature and rate-of-rise detection principles. Based on Iqbal and Salley (2004), pp. 12-3–12-4 and Schifiliti, Meacham, and Custer (2002), p. 4-19.

Transport from the fire to the sensing element

Hot gases rise in a plume and spread beneath a ceiling as a Ceiling jet. A detector in this flow receives heat from the moving gases. Both gas temperature and gas velocity affect the transfer of energy to the element. The International Fire Engineering Guidelines (IFEG, 2005) also identify the element's distance below the ceiling as relevant.[3]

The temperature and velocity are not uniform throughout the flow, and their values change with location relative to the fire and with depth below the ceiling. A detector placed outside the relevant hot flow does not receive the exposure assumed for a detector within it. Geometry is therefore part of the response calculation rather than a separate installation detail.[3][13]

Thermal lag is the delay caused by the sensing element taking time to heat. During rising gas temperature, the element can remain cooler than the surrounding gases. Consequently, the gas temperature at operation can exceed the detector's nominal operating temperature. The rating applies to the element's response, not to instantaneous equality between gas and element temperatures.[4]

The Detector activation time contains the effects of exposure and thermal response. A steady-exposure calculation begins when the assumed hot gases reach the element, so it does not automatically include the earlier transport of those gases from the fire. Schifiliti and colleagues explicitly identify this transport omission in the simplest steady ceiling-jet model.[14]

Plume and ceiling jet transfer heat to a detector element, which responds after a lag.
Heat-detector response depends on ceiling-jet exposure and thermal lag. Based on Australian Building Codes Board et al. (2005), p. 2.7-2 and Schifiliti, Meacham, and Custer (2002), p. 4-7.

Thermal response and response time index

A common model treats the sensing element as a single uniform thermal mass. This is called the lumped-mass approximation. It assumes that temperature differences within the element can be neglected. The temperature then increases according to the heat transferred from the gas and the element's thermal response.[15][16]

The Response time index (RTI) expresses thermal sensitivity in this model. For a given gas exposure, a smaller RTI gives faster heating of the element. The governing equation relates the rate of element heating to gas velocity and the temperature difference. As the element approaches the gas temperature, that driving temperature difference becomes smaller.[17]

dTddt=uRTI(Tg−Td)

Symbol Description Unit
Td Temperature of the detector's sensing element °C
Tg Gas temperature at the sensing element °C
t Time measured from the start of the assumed exposure s
u Gas velocity at the element m/s
RTI Response time index m1/2s1/2
Ta Initial element temperature, equal to ambient in this model °C
Tr Element temperature required for operation °C
tr Time to operation under the assumed constant exposure s

For constant gas temperature and velocity, the equation can be integrated to obtain the time to reach the operating temperature. The expression below uses the natural logarithm, and it applies when the element starts at ambient temperature and the gas temperature exceeds the operating threshold. It represents fixed-temperature response under the stated thermal assumptions.[18][16]

tr=RTIuln⁡(Tg−TaTg−Tr)

The ratio inside the logarithm uses temperature differences, so consistent Celsius differences can be used. The response time becomes longer when the operating temperature approaches the imposed gas temperature. If the gas never becomes hot enough, this constant-exposure model does not predict threshold operation. A nominal temperature rating alone is therefore insufficient to calculate a response time.[19]

Gas temperature rises quickly while element temperature follows more slowly past the rating.
Element temperature lags behind gas temperature. Based on Iqbal and Salley (2004), p. 12-3 and Schifiliti, Meacham, and Custer (2002), p. 4-7.

Worked example under constant exposure

The SFPE Handbook's second example uses the gas conditions calculated for a 4 m² kerosene pool beneath a flat ceiling. The ceiling is 6 m above the fire and the detector is 6 m horizontally from the plume centre. The ambient temperature is 20 °C. Its calculated exposure is a gas temperature of 153 °C and a velocity of 2.4 m/s.[18]

The example detector has an RTI of 55 m1/2s1/2 and an operating temperature of 57 °C. Substituting those values gives an exposure response time of approximately 11.6 s. Rounded upwards to whole seconds, the required time is 12 s. This reproduces the response reported in the handbook example.[18]

tr=552.4ln⁡(153−20153−57) s≈12 s

This is the time for the specified element to heat under the specified exposure. It is not a claim that a detector will alarm 12 s after every kerosene fire ignites. The example assumes the calculated gas conditions are already present and remain constant. Fire growth, transport to the detector and subsequent alarm-system delays require separate treatment.[20]

For growing fires, Schifiliti and colleagues divide the changing exposure into short time intervals. The updated element temperature is carried from one interval into the next. Gas temperature and velocity can then change as the fire grows. This approach preserves the element's heating history instead of restarting the calculation at ambient temperature each time.[21]

What tests and prescribed inputs represent

A plunge test exposes the device to a gas flow with known, constant temperature and velocity. The measured operating time can be used to infer a thermal time constant and RTI. The SFPE Handbook explains that this is a simplified representation of heat transfer. Flow around the device and heat loss into its supporting body can limit the approximation.[17]

Listed spacing is derived through defined test arrangements, but it does not directly state the time to respond to every fire in an actual building. Ceiling height, beams, airflow and detector exposure can differ from the test. Schifiliti and colleagues distinguish compliance with spacing rules from quantitative assessment against a specified fire-size or response objective.[22]

In New Zealand, C/VM2, second edition (2025), prescribes heat-detector modelling inputs regardless of the installed make or model. These include RTI 30 m1/2s1/2, an activation temperature of 57 °C and a radial distance of 4.2 m. The table also specifies a position at least 25 mm below the ceiling. These values belong to that verification method's analysis.[23]

RTI describes the interaction between the sensing element and the moving gases; it is not a temperature rating or a direct statement of the time from ignition. The same RTI can give different response times when gas temperature or velocity changes. Likewise, two detectors with the same operating temperature can respond at different times because their thermal sensitivities differ. These distinctions explain why both temperature and sensitivity appear in the model.[19]

The prescribed values must not be mistaken for a universal specification of actual detectors. A product can have measured characteristics different from those analysis inputs. The source distinguishes the required simulation from the device selected for installation. An engineering report therefore identifies whether its inputs are measured, assumed or prescribed by the chosen method.[23][17]

Choosing between thermal response principles

A fixed-temperature device and a rate-of-rise device respond to different features of the same exposure. A rapid temperature increase can activate the rate-of-rise function before the fixed-temperature element reaches its threshold. During slower heating, the rate-of-rise condition may be less favourable. Combination devices use both mechanisms to address these different conditions.[12]

The handbook examines this distinction using several fire growth rates, and its examples show that detector spacing and response depend on the growth history as well as sensitivity. A device that responds earlier in one scenario need not do so in another. The result supports comparing detectors against the intended fire scenarios rather than ranking the mechanisms universally.[6]

Rate-compensated and pneumatic rate-of-rise devices require particular care in modelling, and their internal heat transfer and mechanical response are more complex than one directly exposed element. The SFPE Handbook explains that a single lumped mass may not represent these mechanisms adequately. Applying the fixed-temperature equation unchanged would omit parts of the device's operating principle.[13]

Environmental effects and calculation limits

Normal non-fire temperatures influence the selection of a thermal operating rating. NUREG-1805 discusses higher-temperature devices for locations where ordinary ambient conditions would otherwise cause premature operation. The relevant exposure is the temperature near the detector, including expected non-fire heat sources. A rating chosen without those conditions can produce unwanted alarms.[24]

The report's simple ceiling-jet method assumes an unconfined flat ceiling and a fire away from walls and corners. It excludes a developed hot layer beneath the jet during the period of interest. Obstructions and irregular ceilings can undermine the assumed flow. The method also does not explicitly include direct radiant heating of the sensing element.[25]

The assumption of a constant RTI is itself an approximation. Schifiliti and colleagues discuss the complex gas flow around irregular detector shapes and the possibility of heat conduction into supporting parts. A plunge test may involve conditions in which those heat losses are relatively small, but their importance can differ during the slower flows of an actual fire. A thermal parameter obtained from one test condition therefore needs an appropriate range of application.[17]

Modelled response after another protective device operates also requires care. The handbook notes that its basic calculations do not account for sprinkler cooling when predicting subsequent detector or sprinkler activation. The first operating device can change the environment experienced by other devices. Their later responses cannot automatically be inferred by continuing the original unsuppressed exposure unchanged.[13]

The gas-flow calculation and the element-response calculation have separate limitations. Correctly integrating a thermal equation cannot compensate for an unsuitable gas temperature or velocity prediction. Conversely, suitable gas conditions do not establish the correct thermal model for every detector mechanism. The assessed geometry, fire development and device behaviour must all fit the chosen method.[26][27]

See also

Notes

  1. ↑ Schifiliti, Meacham, and Custer (2002), pp. 4-5–4-7.
  2. ↑ 2.0 2.1 Iqbal and Salley (2004), pp. 12-1–12-4.
  3. ↑ 3.0 3.1 3.2 Australian Building Codes Board et al. (2005), p. 2.7-2.
  4. ↑ 4.0 4.1 4.2 Iqbal and Salley (2004), p. 12-3.
  5. ↑ Iqbal and Salley (2004), pp. 12-3–12-5.
  6. ↑ 6.0 6.1 Schifiliti, Meacham, and Custer (2002), pp. 4-19–4-20.
  7. ↑ Schifiliti, Meacham, and Custer (2002), pp. 4-2–4-3.
  8. ↑ 8.0 8.1 Iqbal and Salley (2004), p. 12-1.
  9. ↑ Schifiliti, Meacham, and Custer (2002), pp. 4-3–4-4, 4-30.
  10. ↑ 10.0 10.1 Iqbal and Salley (2004), pp. 12-3, 12-5.
  11. ↑ Iqbal and Salley (2004), p. 12-4.
  12. ↑ 12.0 12.1 Iqbal and Salley (2004), pp. 12-4–12-5.
  13. ↑ 13.0 13.1 13.2 13.3 Schifiliti, Meacham, and Custer (2002), p. 4-7.
  14. ↑ Schifiliti, Meacham, and Custer (2002), pp. 4-7–4-8.
  15. ↑ Schifiliti, Meacham, and Custer (2002), pp. 4-5–4-6.
  16. ↑ 16.0 16.1 Iqbal and Salley (2004), p. 12-6.
  17. ↑ 17.0 17.1 17.2 17.3 Schifiliti, Meacham, and Custer (2002), p. 4-6.
  18. ↑ 18.0 18.1 18.2 Schifiliti, Meacham, and Custer (2002), p. 4-8.
  19. ↑ 19.0 19.1 Schifiliti, Meacham, and Custer (2002), pp. 4-6–4-8.
  20. ↑ Schifiliti, Meacham, and Custer (2002), pp. 4-2–4-3, 4-8.
  21. ↑ Schifiliti, Meacham, and Custer (2002), pp. 4-8–4-9.
  22. ↑ Schifiliti, Meacham, and Custer (2002), pp. 4-3–4-4.
  23. ↑ 23.0 23.1 Ministry of Business, Innovation and Employment (2025), p. 27.
  24. ↑ Iqbal and Salley (2004), pp. 12-1–12-3.
  25. ↑ Iqbal and Salley (2004), pp. 12-10–12-11.
  26. ↑ Schifiliti, Meacham, and Custer (2002), pp. 4-7–4-9.
  27. ↑ Iqbal and Salley (2004), p. 12-10.

References

  • Australian Building Codes Board, National Research Council of Canada, International Code Council, & Department of Building and Housing New Zealand. (2005). International fire engineering guidelines. Australian Building Codes Board.
  • Iqbal, N., & Salley, M. H. (2004). Fire dynamics tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission fire protection inspection program (NUREG-1805). U.S. Nuclear Regulatory Commission.
  • Ministry of Business, Innovation and Employment. (2025). C protection from fire: Verification method C/VM2 (2nd ed.).
  • Schifiliti, R. P., Meacham, B. J., & Custer, R. L. P. (2002). Design of detection systems. In P. J. DiNenno (Ed.), SFPE handbook of fire protection engineering (3rd ed., pp. 4-1–4-43). National Fire Protection Association.