== Flammability and explosion properties == | == Flammability and explosion properties == | ||
The [[flammability limits]] of ethylene oxide are reported in two ways. Davenport gives a flammable range in air of 3 to 80 percent. He adds that the upper limit is frequently reported as 100 percent, but that explosions of mixtures with more than 80 percent ethylene oxide result from chemical decomposition.<ref name="DA-7-49" /> In the SFPE Handbook, Beyler lists a lower limit of 3.6 percent and an upper limit of 100 percent in air at atmospheric pressure.<ref name="BE-2-175">Beyler (2002b), p. 2-175.</ref> The NFPA 53 data in the handbook also give 3.6 and 100.0 percent in air, and in oxygen a lower limit of 3.6 percent or less with the same upper limit.<ref name="RS-9-230" /> For comparison, methane has limits of 5.0 and 15.0 percent in the same table, a range of only 10 percentage points.<ref name="RS-9-229">Rosales and Stoltzfus (2008), p. 9-229.</ref> | The [[flammability limits]] of ethylene oxide are reported in two ways. Davenport gives a flammable range in air of 3 to 80 percent. He adds that the upper limit is frequently reported as 100 percent, but that explosions of mixtures with more than 80 percent ethylene oxide result from chemical decomposition.<ref name="DA-7-49" /> In the SFPE Handbook, Beyler lists a lower limit of 3.6 percent and an upper limit of 100 percent in air at atmospheric pressure.<ref name="BE-2-175">Beyler (2002b), p. 2-175.</ref> The NFPA 53 data in the handbook also give 3.6 and 100.0 percent in air, and in oxygen a lower limit of 3.6 percent or less with the same upper limit.<ref name="RS-9-230" /> For comparison, methane has limits of 5.0 and 15.0 percent in the same table, a range of only 10 percentage points.<ref name="RS-9-229">Rosales and Stoltzfus (2008), p. 9-229.</ref> | ||
[[File:fse-ethylene-oxide-v1.svg|thumb|upright=1.5|alt=Range bars: ethylene oxide flammable from about 3 to 100 percent, hatched above 80 percent; methane only 5 to 15 percent.|Flammable ranges in air of ethylene oxide and three other gases. For ethylene oxide, mixtures above 80 percent explode by chemical decomposition | [[File:fse-ethylene-oxide-v1.svg|thumb|upright=1.5|alt=Range bars: ethylene oxide flammable from about 3 to 100 percent, hatched above 80 percent; methane only 5 to 15 percent.|Flammable ranges in air of ethylene oxide and three other gases. For ethylene oxide, mixtures above 80 percent explode by chemical decomposition.]] | ||
Ethylene oxide is also easy to ignite. Its [[minimum ignition energy]] in air is 0.062 mJ, against 0.300 mJ for methane and 0.017 mJ for acetylene.<ref name="RS-9-229" /><ref name="RS-9-230" /> The SFPE value of 1.48 × 10<sup>−5</sup> cal equals the same 0.062 mJ.<ref name="SFPE-A-35" /> Its fundamental burning velocity is 108 cm/s, about 2.7 times that of methane (40 cm/s) and a third of that of hydrogen (312 cm/s).<ref name="SC-18-82">Schwab (2008b), p. 18-82.</ref> | Ethylene oxide is also easy to ignite. Its [[minimum ignition energy]] in air is 0.062 mJ, against 0.300 mJ for methane and 0.017 mJ for acetylene.<ref name="RS-9-229" /><ref name="RS-9-230" /> The SFPE value of 1.48 × 10<sup>−5</sup> cal equals the same 0.062 mJ.<ref name="SFPE-A-35" /> Its fundamental burning velocity is 108 cm/s, about 2.7 times that of methane (40 cm/s) and a third of that of hydrogen (312 cm/s).<ref name="SC-18-82">Schwab (2008b), p. 18-82.</ref> | ||
[[File:fse-ethylene-oxide-v2.svg|thumb|upright=1.5|alt=Bar charts: ethylene oxide needs 0.062 mJ to ignite against 0.300 mJ for methane, and burns at 108 cm/s against 40 cm/s.|Minimum ignition energy in air (left, logarithmic axis) and fundamental burning velocity (right) of ethylene oxide and other gases | [[File:fse-ethylene-oxide-v2.svg|thumb|upright=1.5|alt=Bar charts: ethylene oxide needs 0.062 mJ to ignite against 0.300 mJ for methane, and burns at 108 cm/s against 40 cm/s.|Minimum ignition energy in air (left, logarithmic axis) and fundamental burning velocity (right) of ethylene oxide and other gases.]] | ||
In the United States electrical classification table reproduced by Milatovich (2008), ethylene oxide is a Group B material, classified by test. The table permits Group C equipment if all conduit of 1/2 in. trade size or larger is sealed in accordance with the NEC.<ref name="MI-8-165" /><ref name="MI-8-166">Milatovich (2008), p. 8-166.</ref> Hydrogen is also a Group B material, whereas most flammable gases are in Groups C or D.<ref name="LR-7-41">Lemoff and Rivkin (2008), p. 7-41.</ref> | In the United States electrical classification table reproduced by Milatovich (2008), ethylene oxide is a Group B material, classified by test. The table permits Group C equipment if all conduit of 1/2 in. trade size or larger is sealed in accordance with the NEC.<ref name="MI-8-165" /><ref name="MI-8-166">Milatovich (2008), p. 8-166.</ref> Hydrogen is also a Group B material, whereas most flammable gases are in Groups C or D.<ref name="LR-7-41">Lemoff and Rivkin (2008), p. 7-41.</ref> | ||
| Line 23: | Line 23: | ||
Ethylene oxide can polymerise violently when catalysed by anhydrous chlorides of iron, tin or aluminium, by oxides of iron (rust) and aluminium, and by alkali metal hydroxides. Heat or shock can also start violent polymerisation.<ref name="DA-7-49" /> It reacts with alcohols, organic and inorganic acids, ammonia and many other compounds. The heat released by these reactions can then cause the remaining ethylene oxide to polymerise.<ref name="DA-7-49" /> In a fire, its vapours in an exposed tank can be heated rapidly to their ignition temperature unless the tank is kept wet with water spray.<ref name="DA-7-49" /> | Ethylene oxide can polymerise violently when catalysed by anhydrous chlorides of iron, tin or aluminium, by oxides of iron (rust) and aluminium, and by alkali metal hydroxides. Heat or shock can also start violent polymerisation.<ref name="DA-7-49" /> It reacts with alcohols, organic and inorganic acids, ammonia and many other compounds. The heat released by these reactions can then cause the remaining ethylene oxide to polymerise.<ref name="DA-7-49" /> In a fire, its vapours in an exposed tank can be heated rapidly to their ignition temperature unless the tank is kept wet with water spray.<ref name="DA-7-49" /> | ||
[[File:fse-ethylene-oxide-v5.svg|thumb|upright=1.5|alt=Flow chart: catalysts, contaminants, heat, shock and fire exposure lead to polymerisation, ignition or detonation of ethylene oxide; safeguards shown alongside.|Routes to a violent reaction of ethylene oxide and the safeguards named in the handbook | [[File:fse-ethylene-oxide-v5.svg|thumb|upright=1.5|alt=Flow chart: catalysts, contaminants, heat, shock and fire exposure lead to polymerisation, ignition or detonation of ethylene oxide; safeguards shown alongside.|Routes to a violent reaction of ethylene oxide and the safeguards named in the handbook.]] | ||
In the NFPA 55 classification reproduced by Lemoff (2008), such gases are [[unstable reactive material]]s in three classes. A Class 2 gas undergoes violent chemical change at elevated temperatures and pressures. A Class 3 gas can detonate or decompose explosively but needs a strong initiating source or heating under confinement. A Class 4 gas can do so readily at normal temperatures and pressures.<ref name="LE-6-166">Lemoff (2008), p. 6-166.</ref> The handbook does not state which class applies to ethylene oxide. | In the NFPA 55 classification reproduced by Lemoff (2008), such gases are [[unstable reactive material]]s in three classes. A Class 2 gas undergoes violent chemical change at elevated temperatures and pressures. A Class 3 gas can detonate or decompose explosively but needs a strong initiating source or heating under confinement. A Class 4 gas can do so readily at normal temperatures and pressures.<ref name="LE-6-166">Lemoff (2008), p. 6-166.</ref> The handbook does not state which class applies to ethylene oxide. | ||
| Line 33: | Line 33: | ||
Ethylene oxide sterilisers bring a flammable and toxic gas into a [[health care occupancy]]. In Allen's (2008) account of United States facilities, venting the steriliser outside the building is mandatory.<ref name="AL-6-193" /> Ethylene oxide is not a medical gas in the sense that oxygen and nitrous oxide are, and it has no role in patient treatment. It is therefore not covered by the rules for the design and installation of a [[medical gas system]].<ref name="AL-6-193" /> Its safe storage, handling and use are covered by NFPA 560, which the NUREG-1805 list of NFPA documents gives in its 2002 edition.<ref name="AL-6-193" /><ref name="IS-E-8">Iqbal and Salley (2004), p. E-8.</ref> | Ethylene oxide sterilisers bring a flammable and toxic gas into a [[health care occupancy]]. In Allen's (2008) account of United States facilities, venting the steriliser outside the building is mandatory.<ref name="AL-6-193" /> Ethylene oxide is not a medical gas in the sense that oxygen and nitrous oxide are, and it has no role in patient treatment. It is therefore not covered by the rules for the design and installation of a [[medical gas system]].<ref name="AL-6-193" /> Its safe storage, handling and use are covered by NFPA 560, which the NUREG-1805 list of NFPA documents gives in its 2002 edition.<ref name="AL-6-193" /><ref name="IS-E-8">Iqbal and Salley (2004), p. E-8.</ref> | ||
[[File:fse-ethylene-oxide-v3.svg|thumb|upright=1.5|alt=Schematic: cylinder supplies a sterilizer chamber that is evacuated, filled with ethylene oxide and vented to the outside of the building.|Ethylene oxide gas sterilisation: the chamber is evacuated, filled with ethylene oxide and vented to the outside. The gas is not part of the medical gas system | [[File:fse-ethylene-oxide-v3.svg|thumb|upright=1.5|alt=Schematic: cylinder supplies a sterilizer chamber that is evacuated, filled with ethylene oxide and vented to the outside of the building.|Ethylene oxide gas sterilisation: the chamber is evacuated, filled with ethylene oxide and vented to the outside. The gas is not part of the medical gas system.]] | ||
Other gaseous sterilants, such as chlorine, ozone, sulfur dioxide and formaldehyde gas, were used in the past. They are no longer used for medical sterilisation because of handling problems, their corrosive nature and the greater efficacy and safety of heat and ethylene oxide sterilisation.<ref name="AL-6-193" /><ref name="AL-6-194">Allen (2008), p. 6-194.</ref> Ethylene oxide is also used to treat medical waste and, during freeze or vacuum drying of water-damaged collections, to stop mould growth.<ref name="SE-7-64" /><ref name="MC-20-194">McDaniel (2008), p. 20-194.</ref> | Other gaseous sterilants, such as chlorine, ozone, sulfur dioxide and formaldehyde gas, were used in the past. They are no longer used for medical sterilisation because of handling problems, their corrosive nature and the greater efficacy and safety of heat and ethylene oxide sterilisation.<ref name="AL-6-193" /><ref name="AL-6-194">Allen (2008), p. 6-194.</ref> Ethylene oxide is also used to treat medical waste and, during freeze or vacuum drying of water-damaged collections, to stop mould growth.<ref name="SE-7-64" /><ref name="MC-20-194">McDaniel (2008), p. 20-194.</ref> | ||
| Line 69: | Line 69: | ||
=== Worked example: carbon dioxide for an ethylene oxide hazard === | === Worked example: carbon dioxide for an ethylene oxide hazard === | ||
The theoretical minimum carbon dioxide concentration for ethylene oxide is 44 percent. The design concentration is 1.2 × 44 = 52.8 percent, which is above the floor of 34 percent and is given in the table as 53 percent.<ref name="WY-17-5" /><ref name="WY-17-6" /> For an enclosure at 21 °C, the specific volumes <math>S</math> and <math>V_\mathrm{s}</math> are equal and cancel. The agent volume per cubic metre of enclosure is then 2.303 × log<sub>10</sub>(100/47) = 0.755 m³.<ref name="DT-17-113" /> For methane, with a design concentration of 34 percent, the same calculation gives 0.416 m³, so ethylene oxide needs about 1.8 times as much carbon dioxide. | The theoretical minimum carbon dioxide concentration for ethylene oxide is 44 percent. The design concentration is 1.2 × 44 = 52.8 percent, which is above the floor of 34 percent and is given in the table as 53 percent.<ref name="WY-17-5" /><ref name="WY-17-6" /> For an enclosure at 21 °C, the specific volumes <math>S</math> and <math>V_\mathrm{s}</math> are equal and cancel. The agent volume per cubic metre of enclosure is then 2.303 × log<sub>10</sub>(100/47) = 0.755 m³.<ref name="DT-17-113" /> For methane, with a design concentration of 34 percent, the same calculation gives 0.416 m³, so ethylene oxide needs about 1.8 times as much carbon dioxide. | ||
[[File:fse-ethylene-oxide-v4.svg|thumb|upright=1.5|alt=Bar chart: carbon dioxide theoretical and design concentrations; ethylene oxide 44 and 53 percent, methane 25 and 34 percent, hydrogen 62 and 75 percent.|Theoretical minimum and minimum design carbon dioxide concentrations for inerting ethylene oxide and other fuels; the design value is 20 percent above the theoretical value but at least 34 percent | [[File:fse-ethylene-oxide-v4.svg|thumb|upright=1.5|alt=Bar chart: carbon dioxide theoretical and design concentrations; ethylene oxide 44 and 53 percent, methane 25 and 34 percent, hydrogen 62 and 75 percent.|Theoretical minimum and minimum design carbon dioxide concentrations for inerting ethylene oxide and other fuels; the design value is 20 percent above the theoretical value but at least 34 percent.]] | ||
After discharge, 47 percent of the enclosure atmosphere is still air. With air containing 21.0 percent oxygen by volume, the oxygen concentration falls to about 9.9 percent.<ref name="CH-14-100">Cholin (2008a), p. 14-100.</ref> Carbon dioxide concentrations above 9 percent make most people lose consciousness within a short time, so every carbon dioxide system needs safety precautions for occupants.<ref name="WY-17-5" /> | After discharge, 47 percent of the enclosure atmosphere is still air. With air containing 21.0 percent oxygen by volume, the oxygen concentration falls to about 9.9 percent.<ref name="CH-14-100">Cholin (2008a), p. 14-100.</ref> Carbon dioxide concentrations above 9 percent make most people lose consciousness within a short time, so every carbon dioxide system needs safety precautions for occupants.<ref name="WY-17-5" /> | ||
Latest revision as of 08:27, 8 November 2026
Ethylene oxide (C2H4O) is a highly flammable, chemically reactive and toxic compound. It is an extremely volatile liquid that vaporises readily at room temperature.[1][2] Its main use described in the handbook is as a gas sterilant for reusable medical equipment, because it kills bacteria and viruses. It is delivered to users in cylinders, sometimes mixed with other gases to reduce its flammability.[1] Ethylene oxide burns in air over an exceptionally wide range of concentrations, from about 3 percent upwards. Above 80 percent its explosions are the result of chemical decomposition rather than combustion with air.[3]
Ethylene oxide also counts among the unstable chemicals: it can polymerise violently when contaminated or heated, and its vapours can detonate.[3] Protection therefore combines the measures for flammable gases with those for reactive chemicals. In the United States, the 2008 NFPA Fire Protection Handbook refers to NFPA 560 for the storage, handling and use of ethylene oxide for sterilisation and fumigation.[1] It also lists high concentrations of inert agents needed to make its mixtures with air nonflammable, such as a carbon dioxide design concentration of 53 percent.[4]
Properties
Ethylene oxide has the molecular formula C2H4O and a molecular weight of 44.05.[2] The SFPE Handbook gives a boiling point of 10.6 °C and a heat of vaporisation of 581.1 kJ/kg.[5] Because the boiling point is close to room temperature, the liquid evaporates readily, and the handbook describes it as extremely volatile.[1] At the same temperature and pressure, the density of an ideal gas is proportional to its molecular weight.[6] With a molecular weight of 28.9 for air, ethylene oxide vapour is therefore about 1.52 times as dense as air.[6][2]
The data compiled from NFPA 53 give ethylene oxide a flash point below −17.8 °C (below 0 °F) and a minimum ignition temperature in air of 804 °F (429 °C).[7] The SFPE Handbook lists a spontaneous ignition temperature of 428.9 °C, and the electrical classification table in the handbook gives the same autoignition temperature.[5][8] Ethylene oxide is toxic to humans.[1] In the context of medical waste treatment, the handbook describes it, like formaldehyde, as highly flammable and hazardous to human health.[9] The sources consulted give no numerical toxicity or exposure limits.
Flammability and explosion properties
The flammability limits of ethylene oxide are reported in two ways. Davenport gives a flammable range in air of 3 to 80 percent. He adds that the upper limit is frequently reported as 100 percent, but that explosions of mixtures with more than 80 percent ethylene oxide result from chemical decomposition.[3] In the SFPE Handbook, Beyler lists a lower limit of 3.6 percent and an upper limit of 100 percent in air at atmospheric pressure.[10] The NFPA 53 data in the handbook also give 3.6 and 100.0 percent in air, and in oxygen a lower limit of 3.6 percent or less with the same upper limit.[7] For comparison, methane has limits of 5.0 and 15.0 percent in the same table, a range of only 10 percentage points.[11]
Ethylene oxide is also easy to ignite. Its minimum ignition energy in air is 0.062 mJ, against 0.300 mJ for methane and 0.017 mJ for acetylene.[11][7] The SFPE value of 1.48 × 10−5 cal equals the same 0.062 mJ.[5] Its fundamental burning velocity is 108 cm/s, about 2.7 times that of methane (40 cm/s) and a third of that of hydrogen (312 cm/s).[12]
In the United States electrical classification table reproduced by Milatovich (2008), ethylene oxide is a Group B material, classified by test. The table permits Group C equipment if all conduit of 1/2 in. trade size or larger is sealed in accordance with the NEC.[8][13] Hydrogen is also a Group B material, whereas most flammable gases are in Groups C or D.[14]
The handbook warns that ethylene oxide vapours can detonate if an initiating heat source is present.[3] A detonation is an explosion in which the flame travels at supersonic speed through the unburned mixture. Its pressure rise is so sudden and uneven that explosion venting and suppression cannot protect against it.[15] Calculated Chapman–Jouguet detonation pressures in the handbook show ethylene oxide among the highest of seven common gases. Its curve reaches about 20 bar near 15 percent fuel and stays high up to 35 percent.[16] Most accidental explosions are deflagrations, but detonations become possible in very flammable mixtures with a strong ignition source, a long or obstructed geometry or high turbulence.[16]
Reactivity and polymerisation
The handbook treats ethylene oxide as one of the unstable chemicals, which are subject to spontaneous decomposition or other dangerous reactions. Davenport (2008) recommends that storage planning consider the catalytic effect of containers, other materials in the same area, inhibitors, and sunlight and temperature changes.[17] Pressure-relief vents for containers, explosion venting for the storage area, sprinklers or water spray and the removal of combustibles are recommended. Where possible, unstable chemicals should be stored in a detached outside location.[17]
Ethylene oxide can polymerise violently when catalysed by anhydrous chlorides of iron, tin or aluminium, by oxides of iron (rust) and aluminium, and by alkali metal hydroxides. Heat or shock can also start violent polymerisation.[3] It reacts with alcohols, organic and inorganic acids, ammonia and many other compounds. The heat released by these reactions can then cause the remaining ethylene oxide to polymerise.[3] In a fire, its vapours in an exposed tank can be heated rapidly to their ignition temperature unless the tank is kept wet with water spray.[3]
In the NFPA 55 classification reproduced by Lemoff (2008), such gases are unstable reactive materials in three classes. A Class 2 gas undergoes violent chemical change at elevated temperatures and pressures. A Class 3 gas can detonate or decompose explosively but needs a strong initiating source or heating under confinement. A Class 4 gas can do so readily at normal temperatures and pressures.[18] The handbook does not state which class applies to ethylene oxide.
A further hazard arises when liquids leak into hot thermal insulation. Gray notes that leaked liquids can ignite spontaneously in high-surface-area lagging such as mineral wool or fibreglass.[19] Britton reported practical cases and experimental tests of this effect with particular reference to ethylene oxide fires.[20]
Use as a sterilant in health care
Sterilisation by dry heat or steam was standard practice for reusable medical equipment for many years, before ethylene oxide was introduced as an effective bactericidal and virucidal agent.[1] In the sterilising process, the chamber is first evacuated of air and then filled with ethylene oxide gas, which penetrates the load and destroys the organisms.[1] Proper operation of the equipment is required to avoid unintentional ignition or explosion. The liquid arrives in cylinders that must be stored like any container of flammable liquid or gas.[1]
Ethylene oxide sterilisers bring a flammable and toxic gas into a health care occupancy. In Allen's (2008) account of United States facilities, venting the steriliser outside the building is mandatory.[1] Ethylene oxide is not a medical gas in the sense that oxygen and nitrous oxide are, and it has no role in patient treatment. It is therefore not covered by the rules for the design and installation of a medical gas system.[1] Its safe storage, handling and use are covered by NFPA 560, which the NUREG-1805 list of NFPA documents gives in its 2002 edition.[1][21]
Other gaseous sterilants, such as chlorine, ozone, sulfur dioxide and formaldehyde gas, were used in the past. They are no longer used for medical sterilisation because of handling problems, their corrosive nature and the greater efficacy and safety of heat and ethylene oxide sterilisation.[1][22] Ethylene oxide is also used to treat medical waste and, during freeze or vacuum drying of water-damaged collections, to stop mould growth.[9][23]
Inerting
Inerting adds an agent to a fuel–air mixture until an ignition source can no longer cause an unacceptable pressure rise.[24] It is one way of controlling the wide flammable range of ethylene oxide. The handbook notes that ethylene oxide can be delivered mixed with other gases to reduce its flammability.[1] The 2004 Emergency Response Guidebook lists "ethylene oxide with nitrogen" alongside pure ethylene oxide under UN 1040.[25] Introduction to Fire Safety Engineering explains the principle with the fire triangle: if the oxygen concentration falls far enough, a fire stops spreading and may go out.[26]
For carbon dioxide, the handbook gives theoretical minimum concentrations from Bureau of Mines data, based on inerting the fuel–air mixture. For ethylene oxide this concentration is 44 percent, against 25 percent for methane, 41 percent for ethylene and 62 percent for hydrogen.[4] NFPA 12, as described by Wysocki (2008), sets the minimum design concentration at 20 percent above the theoretical minimum but never less than 34 percent.[4][27]
The quantity of agent then follows from the flooding expression that DiNenno and Taylor give for inert gases. They note that it is identical to the expression used in carbon dioxide system design and that it assumes free venting of the displaced atmosphere.[28][29] The logarithm reflects the assumption that the gas leaving the enclosure during discharge contains agent at a concentration rising from zero to the design value.[28]
| Symbol | Description | Unit |
|---|---|---|
| theoretical minimum carbon dioxide concentration for inerting | % by volume | |
| , | design concentration of the agent | % by volume |
| volume of agent required, at 21 °C (70 °F) | m³ | |
| net protected volume of the enclosure | m³ | |
| specific volume of the agent at the ambient temperature of the protected space | m³/kg | |
| specific volume of the agent at 21 °C (70 °F) | m³/kg |
The ratio of the enclosure volume to the specific volume gives a mass of agent, which the specific volume at 21 °C converts back into a gas volume.[28] The flooding expression treats the enclosure as freely vented and the agent as well mixed. It does not account for leakage after discharge, for local fuel-rich pockets or for a fire already burning.[29]
Worked example: carbon dioxide for an ethylene oxide hazard
The theoretical minimum carbon dioxide concentration for ethylene oxide is 44 percent. The design concentration is 1.2 × 44 = 52.8 percent, which is above the floor of 34 percent and is given in the table as 53 percent.[4][27] For an enclosure at 21 °C, the specific volumes and are equal and cancel. The agent volume per cubic metre of enclosure is then 2.303 × log10(100/47) = 0.755 m³.[28] For methane, with a design concentration of 34 percent, the same calculation gives 0.416 m³, so ethylene oxide needs about 1.8 times as much carbon dioxide.
After discharge, 47 percent of the enclosure atmosphere is still air. With air containing 21.0 percent oxygen by volume, the oxygen concentration falls to about 9.9 percent.[30] Carbon dioxide concentrations above 9 percent make most people lose consciousness within a short time, so every carbon dioxide system needs safety precautions for occupants.[4]
Halocarbon agents show the same pattern. HFC-227ea inerts ethylene oxide at 13.6 percent by volume, against 8.0 percent for methane.[31] An inerting concentration is the concentration that prevents an unacceptable pressure rise in a premixed fuel, air and agent mixture exposed to an ignition source. It is measured in small spheres and depends on the test apparatus, especially the ignition strength and the allowed pressure rise. Inerting concentrations are not appropriate for suppressing deflagrations or detonations.[24]
Transport and emergency response
The 2004 Emergency Response Guidebook gives initial isolation and protective action distances for ethylene oxide (UN 1040). For a small spill, responders isolate 30.5 m (100 ft) in all directions and protect persons downwind for 0.16 km (0.1 mi) by day and by night. For a large spill, the values are 61.0 m (200 ft), 0.48 km (0.3 mi) by day and 1.77 km (1.1 mi) by night.[25] These distances are much shorter than those for chlorine in the same table.[25]
In rail transport, thermal protection is used on some tank cars to protect the tank from flame impingement. It is designed to keep the tank metal below 800 °F (427 °C) for 100 minutes in a pool fire or 30 minutes in a torch fire. The handbook names the DOT-111J100W4 tank car for ethylene oxide as an example.[32] Elsewhere, the same chapter lists ethylene oxide among the products carried in pressure tank cars.[33]
When a tank of ethylene oxide is exposed to fire, the most important measure is to keep it wet with water spray. Without cooling, the vapours inside can be heated rapidly to their ignition temperature.[3] Fire fighters should be briefed in advance on the procedures for fires involving or exposing storage areas with unstable chemicals.[17] Because ethylene oxide is toxic, responders also face a toxicity hazard whenever it escapes.[1]
Limitations and misconceptions
An upper flammable limit of 100 percent can be misread as meaning that pure ethylene oxide burns like a fuel in air. Davenport explains that explosions above 80 percent are decompositions, which need no air at all.[3] The data sources also differ: the handbook text gives 3 to 80 percent, while the SFPE Handbook and the NFPA 53 data give 3.6 to 100 percent.[3][10][7] The SFPE property table prints a maximum flame speed of 11.35 cm/s, which does not agree with the burning velocity of 108 cm/s in the handbook.[5][12]
Ethylene oxide is found in hospitals but is not a medical gas, so the rules for medical gas systems do not cover it.[1] Inerting data are also easy to over-apply. Inerting concentrations depend on the test apparatus and must not be used to design explosion suppression.[24] The requirements cited here are United States documents as described in the 2008 handbook: NFPA 560, NFPA 12, NFPA 53 and the 2004 Emergency Response Guidebook.[1][27][7][25] The handbook gives no NFPA 704 rating and no hazard class for ethylene oxide, and the sources consulted give no toxicity limits.
See also
Notes
- ↑ 1.00 1.01 1.02 1.03 1.04 1.05 1.06 1.07 1.08 1.09 1.10 1.11 1.12 1.13 1.14 1.15 Allen (2008), p. 6-193.
- ↑ 2.0 2.1 2.2 DiNenno et al. (2002), p. A-38.
- ↑ 3.00 3.01 3.02 3.03 3.04 3.05 3.06 3.07 3.08 3.09 Davenport (2008), p. 7-49.
- ↑ 4.0 4.1 4.2 4.3 4.4 Wysocki (2008), p. 17-5.
- ↑ 5.0 5.1 5.2 5.3 DiNenno et al. (2002), p. A-35.
- ↑ 6.0 6.1 Kandola (2002), p. 1-2.
- ↑ 7.0 7.1 7.2 7.3 7.4 Rosales and Stoltzfus (2008), p. 9-230.
- ↑ 8.0 8.1 Milatovich (2008), p. 8-165.
- ↑ 9.0 9.1 Severson (2008), p. 7-64.
- ↑ 10.0 10.1 Beyler (2002b), p. 2-175.
- ↑ 11.0 11.1 Rosales and Stoltzfus (2008), p. 9-229.
- ↑ 12.0 12.1 Schwab (2008b), p. 18-82.
- ↑ Milatovich (2008), p. 8-166.
- ↑ Lemoff and Rivkin (2008), p. 7-41.
- ↑ Zalosh (2008), p. 2-99.
- ↑ 16.0 16.1 Zalosh (2008), p. 2-100.
- ↑ 17.0 17.1 17.2 Davenport (2008), pp. 7-48–7-49.
- ↑ Lemoff (2008), p. 6-166.
- ↑ Gray (2002), p. 2-224.
- ↑ Britton, as cited in Gray (2002), p. 2-224.
- ↑ Iqbal and Salley (2004), p. E-8.
- ↑ Allen (2008), p. 6-194.
- ↑ McDaniel (2008), p. 20-194.
- ↑ 24.0 24.1 24.2 DiNenno and Taylor (2008), p. 17-97.
- ↑ 25.0 25.1 25.2 25.3 2004 Emergency Response Guidebook, as cited in C. J. Wright (2008a), p. 13-136.
- ↑ Van Rossum (2027), §4.2.
- ↑ 27.0 27.1 27.2 Wysocki (2008), p. 17-6.
- ↑ 28.0 28.1 28.2 28.3 DiNenno and Taylor (2008), p. 17-113.
- ↑ 29.0 29.1 DiNenno and Taylor (2008), p. 17-114.
- ↑ Cholin (2008a), p. 14-100.
- ↑ DiNenno and Taylor (2008), p. 17-99.
- ↑ C. J. Wright (2008b), p. 21-125.
- ↑ C. J. Wright (2008b), p. 21-128.
References
- Allen, M. (2008). Medical gases. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-187–6-196). National Fire Protection Association.
- Beyler, C. L. (2002b). Flammability limits of premixed and diffusion flames. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-172–2-187). National Fire Protection Association; Society of Fire Protection Engineers.
- Cholin, J. M. (2008a). Gas and vapor detection systems and monitors. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 14-99–14-112). National Fire Protection Association.
- Davenport, J. A. (2008). Storage and handling of chemicals. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 7-43–7-55). National Fire Protection Association.
- DiNenno, P. J., Drysdale, D., Beyler, C. L., Walton, W. D., Custer, R. L. P., Hall, J. R., Jr., & Watts, J. M., Jr. (Eds.). (2002). SFPE handbook of fire protection engineering (3rd ed.). National Fire Protection Association; Society of Fire Protection Engineers.
- DiNenno, P. J., & Taylor, G. M. (2008). Halon and halon replacement agents and systems. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 17-93–17-121). National Fire Protection Association.
- Gray, B. (2002). Spontaneous combustion and self-heating. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-211–2-228). National Fire Protection Association; Society of Fire Protection Engineers.
- Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.
- Kandola, B. S. (2002). Introduction to mechanics of fluids. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 1-1–1-26). National Fire Protection Association; Society of Fire Protection Engineers.
- Lemoff, T. C. (2008). Gases. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-165–6-186). National Fire Protection Association.
- Lemoff, T. C., & Rivkin, C. H. (2008). Storage of gases. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 7-35–7-42). National Fire Protection Association.
- McDaniel, D. L. (2008). Library and museum collections. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 20-179–20-202). National Fire Protection Association.
- Milatovich, R. M. (2008). Electrical systems and appliances. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 8-127–8-173). National Fire Protection Association.
- Rosales, K., & Stoltzfus, J. M. (2008). Oxygen-Enriched atmospheres. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-225–9-243). National Fire Protection Association.
- Schwab, R. F. (2008b). Deflagration (explosion) venting. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 18-79–18-88). National Fire Protection Association.
- Severson, P. R. (2008). Hazardous waste control. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 7-57–7-69). National Fire Protection Association.
- Van Rossum, E. (2027). Introduction to Fire Safety Engineering. Fire Safety Academy.
- Wright, C. J. (2008a). Managing the response to hazardous material incidents. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 13-117–13-144). National Fire Protection Association.
- Wright, C. J. (2008b). Rail transportation systems. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 21-109–21-134). National Fire Protection Association.
- Wysocki, T. J. (2008). Carbon dioxide and application systems. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 17-3–17-15). National Fire Protection Association.
- Zalosh, R. (2008). Explosions. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 2-93–2-106). National Fire Protection Association.