Acetylene cylinder exposed to fire. Where fitted, fusible plugs melt at about 100 °C; local heating above about 299 °C starts decomposition, which can rupture the cylinder minutes to hours later, even after 24 hours. Based on Lemoff (2008), p. 6-178.
Acetylene cylinder exposed to fire. Where fitted, fusible plugs melt at about 100 °C; local heating above about 299 °C starts decomposition, which can rupture the cylinder minutes to hours later, even after 24 hours.


Original illustration for [[Acetylene]].
Original illustration for [[Acetylene]].


* Source basis: Lemoff (2008), p. 6-178 ("Hazards of Acetylene Cylinders Exposed to Fire")
* Alt text: Flowchart: where fitted, plugs melt near 100 °C, with a possible torch flame; above 299 °C acetylene can decompose and rupture the cylinder hours later.
* Alt text: Flowchart: where fitted, plugs melt near 100 °C, with a possible torch flame; above 299 °C acetylene can decompose and rupture the cylinder hours later.


== Licensing ==
== Licensing ==
New drawing by Fire Safety Academy. © Fire Safety Academy.
New drawing by Fire Safety Academy. © Fire Safety Academy.

Latest revision as of 08:35, 8 November 2026

Summary

Acetylene cylinder exposed to fire. Where fitted, fusible plugs melt at about 100 °C; local heating above about 299 °C starts decomposition, which can rupture the cylinder minutes to hours later, even after 24 hours.

Original illustration for Acetylene.

  • Alt text: Flowchart: where fitted, plugs melt near 100 °C, with a possible torch flame; above 299 °C acetylene can decompose and rupture the cylinder hours later.

Licensing

New drawing by Fire Safety Academy. © Fire Safety Academy.