== Formation from materials == | == Formation from materials == | ||
The NFPA handbook groups HF with hydrogen chloride and hydrogen bromide as halogen acids. Polymers containing fluorine, chlorine or bromine can generate the corresponding acids during thermal decomposition.<ref name="GB13" /> The acids form in the pyrolysis part of combustion and are not subsequently oxidised in the account given by Gann and Bryner. Flaming combustion is therefore not a prerequisite for their production.<ref name="GB13" /> | The NFPA handbook groups HF with hydrogen chloride and hydrogen bromide as halogen acids. Polymers containing fluorine, chlorine or bromine can generate the corresponding acids during thermal decomposition.<ref name="GB13" /> The acids form in the pyrolysis part of combustion and are not subsequently oxidised in the account given by Gann and Bryner. Flaming combustion is therefore not a prerequisite for their production.<ref name="GB13" /> | ||
[[File:fse-hydrogen-fluoride-v1.svg|thumb|upright=1.5|alt=Three source paths lead to airborne hydrogen fluoride, which can deposit on surfaces and droplets|Hydrogen fluoride may originate from fluorinated materials, halocarbon agents or a battery fire, then partly deposit. Based on Gann and Bryner (2008), pp. 6-13 and 6-16; DiNenno and Taylor (2008), p. 17-114; Van der Graaf et al. (2021/2023), p. 26.]] | |||
The amount produced is material dependent. The handbook describes formation efficiencies that can approach unity, but it also states that maximum possible concentrations are generally not reached.<ref name="GB13" /> Fluoropolymers are specifically identified as a major HF source. Fire-retardant additives containing halogens provide another route to halogen acids.<ref name="GB16" /> The presence of fluorine in a product is consequently a reason to investigate HF formation, not a calculation of the concentration an occupant will breathe.<ref name="GB13" /><ref name="GB24">Gann and Bryner (2008), p. 6-24.</ref> | The amount produced is material dependent. The handbook describes formation efficiencies that can approach unity, but it also states that maximum possible concentrations are generally not reached.<ref name="GB13" /> Fluoropolymers are specifically identified as a major HF source. Fire-retardant additives containing halogens provide another route to halogen acids.<ref name="GB16" /> The presence of fluorine in a product is consequently a reason to investigate HF formation, not a calculation of the concentration an occupant will breathe.<ref name="GB13" /><ref name="GB24">Gann and Bryner (2008), p. 6-24.</ref> | ||
| Line 29: | Line 30: | ||
== A nuclear-fire test comparison == | == A nuclear-fire test comparison == | ||
The US nuclear-fire methods report NUREG-1805 reproduces n-heptane tests of a 4% Halon 1301 discharge in the same enclosure. With the larger 10 ft² fuel pan, one test had a 25-second discharge, 20-second extinguishment and 1,907 ppm HF. Another had a 6-second discharge, 5.2-second extinguishment and 320 ppm HF.<ref name="ISB76">Iqbal and Salley (2004), p. B-76.</ref> The first measured concentration is about 5.96 times the second, but both discharge and extinguishment times changed. The comparison does not isolate the effect of either duration.<ref name="ISB76" /> | The US nuclear-fire methods report NUREG-1805 reproduces n-heptane tests of a 4% Halon 1301 discharge in the same enclosure. With the larger 10 ft² fuel pan, one test had a 25-second discharge, 20-second extinguishment and 1,907 ppm HF. Another had a 6-second discharge, 5.2-second extinguishment and 320 ppm HF.<ref name="ISB76">Iqbal and Salley (2004), p. B-76.</ref> The first measured concentration is about 5.96 times the second, but both discharge and extinguishment times changed. The comparison does not isolate the effect of either duration.<ref name="ISB76" /> | ||
[[File:fse-hydrogen-fluoride-v4.svg|thumb|upright=1.5|alt=Two bars show 1,907 and 320 ppm HF with their different discharge and extinguishment times|Two large-pan Halon 1301 tests gave different HF concentrations while both discharge and extinction times changed. Based on Iqbal and Salley (2004), p. B-76.]] | |||
The report also describes an industrial wool-bag-filter test after Halon 1301 extinguishment. In the unoccupied baghouse, HF was measured at 55 ppm during the first four minutes and 10 ppm between 20 and 24 minutes. Hydrogen cyanide and hydrogen sulphide were present too.<ref name="ISB74">Iqbal and Salley (2004), p. B-74.</ref> This is a particular fire and ventilation arrangement, not an expected concentration in other protected spaces. It shows that an extinguished flame and a cleared atmosphere are separate conditions.<ref name="ISB74" /> | The report also describes an industrial wool-bag-filter test after Halon 1301 extinguishment. In the unoccupied baghouse, HF was measured at 55 ppm during the first four minutes and 10 ppm between 20 and 24 minutes. Hydrogen cyanide and hydrogen sulphide were present too.<ref name="ISB74">Iqbal and Salley (2004), p. B-74.</ref> This is a particular fire and ventilation arrangement, not an expected concentration in other protected spaces. It shows that an extinguished flame and a cleared atmosphere are separate conditions.<ref name="ISB74" /> | ||
| Line 36: | Line 38: | ||
The handbook reproduces a table of potential effects in healthy people. At a two-minute exposure below 50 ppm, it lists slight eye and nasal irritation. At ten minutes below 50 ppm, it lists definite irritation of the eyes, skin and upper respiratory tract.<ref name="DT116" /> For ten minutes above 200 ppm, it lists escape impairment and says increasing concentrations can be lethal without medical intervention. The category covers a range of concentrations, not one exact injury threshold.<ref name="DT116" /> The longer exposure and the table's healthy-person scope are essential to interpreting these entries. | The handbook reproduces a table of potential effects in healthy people. At a two-minute exposure below 50 ppm, it lists slight eye and nasal irritation. At ten minutes below 50 ppm, it lists definite irritation of the eyes, skin and upper respiratory tract.<ref name="DT116" /> For ten minutes above 200 ppm, it lists escape impairment and says increasing concentrations can be lethal without medical intervention. The category covers a range of concentrations, not one exact injury threshold.<ref name="DT116" /> The longer exposure and the table's healthy-person scope are essential to interpreting these entries. | ||
[[File:fse-hydrogen-fluoride-v2.svg|thumb|upright=1.5|alt=Logarithmic HF concentration chart with distinct rows for healthy-person effects, escape models and animal lethality|Selected hydrogen fluoride criteria describe different endpoints and cannot be read as one safety threshold. Based on DiNenno and Taylor (2008), p. 17-116; Gann and Bryner (2008), pp. 6-16 and 6-18; Purser (2002), p. 2-121.]] | |||
The same 2008 chapter reports ten-minute emergency response planning guideline values of 50 ppm for ERPG-2 and 170 ppm for ERPG-3.<ref name="DT116" /> It describes the former as a point for measures such as evacuation and the latter as a maximum nonlethal concentration over that duration.<ref name="DT116" /> These historical planning descriptors must not be treated as a universal workplace limit or as a guarantee that everyone below a value will be unaffected.<ref name="DT116" /><ref name="PU121" /> The NFPA table itself already describes irritation at concentrations below 50 ppm.<ref name="DT116" /> | The same 2008 chapter reports ten-minute emergency response planning guideline values of 50 ppm for ERPG-2 and 170 ppm for ERPG-3.<ref name="DT116" /> It describes the former as a point for measures such as evacuation and the latter as a maximum nonlethal concentration over that duration.<ref name="DT116" /> These historical planning descriptors must not be treated as a universal workplace limit or as a guarantee that everyone below a value will be unaffected.<ref name="DT116" /><ref name="PU121" /> The NFPA table itself already describes irritation at concentrations below 50 ppm.<ref name="DT116" /> | ||
| Line 60: | Line 63: | ||
For example, a hypothetical sample with 50 µL/L HF and 100 µL/L hydrogen chloride gives 50/500 + 100/1,000 = 0.20.<ref name="GB16" /><ref name="GB24" /> Each gas contributes 0.10. This arithmetic is a two-gas illustration of the printed equation, not a measured fire atmosphere or a finding of safety. Other irritants, heat, obscuration and asphyxiant gases can govern conditions before this particular sum reaches 1.<ref name="GB24" /> Concentrations can also change as smoke moves and deposits on surfaces.<ref name="GB13" /> | For example, a hypothetical sample with 50 µL/L HF and 100 µL/L hydrogen chloride gives 50/500 + 100/1,000 = 0.20.<ref name="GB16" /><ref name="GB24" /> Each gas contributes 0.10. This arithmetic is a two-gas illustration of the printed equation, not a measured fire atmosphere or a finding of safety. Other irritants, heat, obscuration and asphyxiant gases can govern conditions before this particular sum reaches 1.<ref name="GB24" /> Concentrations can also change as smoke moves and deposits on surfaces.<ref name="GB13" /> | ||
[[File:fse-hydrogen-fluoride-v3.svg|thumb|upright=1.5|alt=Two labelled concentration-to-criterion fractions of 0.10 add to a partial irritant FEC of 0.20|A hypothetical two-gas example gives a partial irritant FEC of 0.20; other fire hazards remain outside it. Based on Gann and Bryner (2008), pp. 6-16 and 6-24.]] | |||
Purser uses a similar additive concept but assigns HF different escape-impairment and incapacitation values.<ref name="PU121" /> Both authors emphasise uncertainty in translating limited evidence into human escape criteria. Purser states that the thresholds cannot be verified precisely through human experiments and that the values are for an occupant's breathing zone rather than the fire source.<ref name="PU121" /> The numerical result above consequently cannot be substituted for a survey of the whole fire environment. | Purser uses a similar additive concept but assigns HF different escape-impairment and incapacitation values.<ref name="PU121" /> Both authors emphasise uncertainty in translating limited evidence into human escape criteria. Purser states that the thresholds cannot be verified precisely through human experiments and that the values are for an occupant's breathing zone rather than the fire source.<ref name="PU121" /> The numerical result above consequently cannot be substituted for a survey of the whole fire environment. | ||
Revision as of 08:22, 8 November 2026
Hydrogen fluoride (HF) is a halogen acid gas that can occur in fire effluent. Fluorine-containing polymers can release it during thermal decomposition, and a flame can produce it from fluorinated fire extinguishing agents. Both sources matter to Fire toxicity because HF irritates the eyes and airways and can impair escape.[1][2][3] The gas can also affect exposed electronics, although the extent of damage depends on the equipment and the exposure conditions.[4]
The same chemical occurs in several different fire situations. Fluoropolymers are a major source in ordinary material decomposition, while Halon 1301 and its halocarbon replacements produce HF when they encounter flame. A Netherlands Institute for Public Safety report also describes HF in smoke from burning electric-vehicle batteries.[2][5][6] These circumstances cannot be assigned one common emission rate or one common room concentration. Fire size, fuel, agent discharge, mixing and losses to surfaces all affect the result.[1][3]
HF concentration is expressed here as parts per million by volume (ppm), numerically equal to microlitres of gas per litre of air (µL/L). The response to HF depends on concentration, exposure duration and the endpoint being considered. An escape criterion, an emergency planning value and a laboratory animal lethal concentration therefore describe different questions.[2][7][4]
Formation from materials
The NFPA handbook groups HF with hydrogen chloride and hydrogen bromide as halogen acids. Polymers containing fluorine, chlorine or bromine can generate the corresponding acids during thermal decomposition.[1] The acids form in the pyrolysis part of combustion and are not subsequently oxidised in the account given by Gann and Bryner. Flaming combustion is therefore not a prerequisite for their production.[1]
The amount produced is material dependent. The handbook describes formation efficiencies that can approach unity, but it also states that maximum possible concentrations are generally not reached.[1] Fluoropolymers are specifically identified as a major HF source. Fire-retardant additives containing halogens provide another route to halogen acids.[2] The presence of fluorine in a product is consequently a reason to investigate HF formation, not a calculation of the concentration an occupant will breathe.[1][8]
Airborne concentration can change as effluent travels. The handbook says halogen acids can be removed rapidly by adsorptive surfaces and by water droplets below 100 °C.[1] A measured concentration close to a source need not persist throughout a building. Conversely, loss from the gas phase does not remove the substance from surfaces that have received deposits.[1][6] This distinction matters when comparing an emission measurement with a breathing-zone exposure.[9]
Hydrofluoric acid also exists as an aqueous solution, but its storage hazard is a different subject from HF generated in smoke. Davenport describes both anhydrous and aqueous hydrofluoric acid as noncombustible and notes severe injury on contact. Contact with metals can generate hydrogen.[10] Those properties do not imply that an airborne HF concentration is harmless simply because the acid itself is noncombustible.[10][4]
Formation during gaseous fire suppression
A Halocarbon clean agent is a fluorine-containing extinguishing agent used in a Gaseous extinguishing system. The agent and the HF produced when it reaches a flame are distinct substances.[11][5] The 2004 US Nuclear Regulatory Commission report explains that hydrogen available from water vapour or combustion can help form HF from decomposing Halon 1301; hydrogen bromide can form at the same time.[12]
The 2008 handbook describes halocarbon replacement agents as suppressing flame mainly by removing heat. Breaking fluorine-containing bonds absorbs energy but also contributes to agent decomposition.[13] Inert-gas agents work by a different mechanism and do not form agent thermal decomposition products. A large fire may still produce toxic smoke regardless of the agent used.[13][3]
For a given liquid-fuel test, the principal factors reported for HF production are the fire size when the system discharges, the time needed to establish an extinguishing concentration and the agent design concentration.[3] In the 2008 handbook's account, halocarbon systems had a maximum liquid-agent discharge time of 10 seconds, partly to limit decomposition. Vapour and nitrogen continued to leave the system after the liquid cleared the nozzle.[3] This is a description of the handbook's design context, not a statement of present requirements everywhere.
Tests summarised in that handbook produced approximately three to eight times as much HF from the examined halocarbon replacements as from Halon 1301 under comparable n-heptane fire conditions. The heptane pans were shielded from direct agent-jet contact.[3] An earlier SFPE handbook chapter reported a five- to tenfold range for its test set, again with baffled heptane pans.[14] The ranges describe different sets of experiments; neither is a factor for all agents, fuels or enclosures. The replacement compounds also vary in their chemistry, so HF is not the only possible decomposition product.[3][14]
Both peak and average concentration appear in the published tests. One handbook plot places peak HF against fire power divided by room volume, using enclosures from 1.2 to 972 m³. Another shows ten-minute averages for 1.2 and 29 m³ enclosures; those averages were half the measured peaks or lower.[15][3] A ten-minute mean must therefore not be presented as a peak. The plots do not determine a general concentration from room volume alone, because they combine different fire sizes, agents and tests.[3][15]
The same chapter says HF formation rose approximately linearly with discharge time in one test series; doubling that time gave roughly twice the HF. Longer discharge also lengthened extinguishment.[15] In a separate large liquid-fire experiment reported by the chapter, raising the HFC-227ea design concentration from 8% to 9.8% coincided with a fall in peak HF from 8,000 to 2,500 ppm.[16] These observations show why fire size, agent delivery and extinction time must be read together. They are not transferable prediction equations.[3][15]
A nuclear-fire test comparison
The US nuclear-fire methods report NUREG-1805 reproduces n-heptane tests of a 4% Halon 1301 discharge in the same enclosure. With the larger 10 ft² fuel pan, one test had a 25-second discharge, 20-second extinguishment and 1,907 ppm HF. Another had a 6-second discharge, 5.2-second extinguishment and 320 ppm HF.[17] The first measured concentration is about 5.96 times the second, but both discharge and extinguishment times changed. The comparison does not isolate the effect of either duration.[17]
The report also describes an industrial wool-bag-filter test after Halon 1301 extinguishment. In the unoccupied baghouse, HF was measured at 55 ppm during the first four minutes and 10 ppm between 20 and 24 minutes. Hydrogen cyanide and hydrogen sulphide were present too.[18] This is a particular fire and ventilation arrangement, not an expected concentration in other protected spaces. It shows that an extinguished flame and a cleared atmosphere are separate conditions.[18]
Effects on people
HF is an Irritant gas in fire toxicology. Eye and upper-airway sensory effects depend chiefly on the concentration present at the time. Lung irritation, inflammation and later injury depend on both concentration and exposure duration.[2] The handbook says evidence specifically for HF and hydrogen bromide is limited compared with hydrogen chloride, while suggesting broadly similar irritant effects at comparable concentrations.[2] Those qualifications limit the precision of any single threshold.
The handbook reproduces a table of potential effects in healthy people. At a two-minute exposure below 50 ppm, it lists slight eye and nasal irritation. At ten minutes below 50 ppm, it lists definite irritation of the eyes, skin and upper respiratory tract.[4] For ten minutes above 200 ppm, it lists escape impairment and says increasing concentrations can be lethal without medical intervention. The category covers a range of concentrations, not one exact injury threshold.[4] The longer exposure and the table's healthy-person scope are essential to interpreting these entries.
The same 2008 chapter reports ten-minute emergency response planning guideline values of 50 ppm for ERPG-2 and 170 ppm for ERPG-3.[4] It describes the former as a point for measures such as evacuation and the latter as a maximum nonlethal concentration over that duration.[4] These historical planning descriptors must not be treated as a universal workplace limit or as a guarantee that everyone below a value will be unaffected.[4][9] The NFPA table itself already describes irritation at concentrations below 50 ppm.[4]
Three further numbers describe different endpoints. Gann and Bryner report a 500 µL/L HF consensus input from ISO 13571 for modelling incapacitation from irritants.[2] Purser's SFPE table predicts escape impairment in half a population at 200 ppm and incapacitation in half at 900 ppm.[9] The 30-minute rat LC50 of 2,900 µL/L is a laboratory lethality result, not a human escape criterion.[7] Since ppm by volume and µL/L are numerically equal, the difference between 500 and 900 is a difference between models and endpoints, not units.[2][9]
NUREG-1805 reports an approximate lethal concentration of 2,500 ppm for a 15-minute exposure to HF among Halon decomposition products. Its table separately labels 50–250 ppm as dangerous for short exposure.[19] These historical descriptors cannot be substituted for the 30-minute rat LC50, the ISO model input or the ten-minute ERPG values. Each attaches a different duration, population or effect to its number.[19][7][4]
Estimating the irritant contribution
The handbook's ISO 13571 model treats the initial sensory effect of irritants as a concentration problem. It adds each gas's instantaneous concentration divided by a gas-specific incapacitation criterion. Asphyxiants are treated separately using an accumulated dose.[8] For a mixture containing only HF and Hydrogen chloride among the modelled irritants, the relevant two terms are:[8]
| Symbol | Meaning | Unit |
|---|---|---|
| instantaneous volume fractions of the two gases | µL/L | |
| model incapacitation criteria, respectively 500 and 1,000 | µL/L[2] | |
| sum of the two model fractions | dimensionless |
For example, a hypothetical sample with 50 µL/L HF and 100 µL/L hydrogen chloride gives 50/500 + 100/1,000 = 0.20.[2][8] Each gas contributes 0.10. This arithmetic is a two-gas illustration of the printed equation, not a measured fire atmosphere or a finding of safety. Other irritants, heat, obscuration and asphyxiant gases can govern conditions before this particular sum reaches 1.[8] Concentrations can also change as smoke moves and deposits on surfaces.[1]
Purser uses a similar additive concept but assigns HF different escape-impairment and incapacitation values.[9] Both authors emphasise uncertainty in translating limited evidence into human escape criteria. Purser states that the thresholds cannot be verified precisely through human experiments and that the values are for an occupant's breathing zone rather than the fire source.[9] The numerical result above consequently cannot be substituted for a survey of the whole fire environment.
Electronics, testing and interpretation
HF can damage exposed electronic equipment, but the 2008 handbook says there were insufficient data to predict the effect of a specified HF exposure on all equipment.[4] One cited NASA test found no failures in Orbiter electronics at 700 ppm HF and hydrogen bromide, while 7,000 ppm caused severe corrosion and some operating failures.[4] Separate multifunction-board studies found no loss of function after 15 minutes in a post-extinguishment atmosphere up to 5,000 ppm HF or after 30 minutes up to 550 ppm, with their specified follow-up periods.[4] These outcomes do not define a universal equipment tolerance. Humidity, other combustion products, enclosure and post-exposure treatment all mattered in the handbook's interpretation.[4]
The test method affects what a stated number means. The 2002 SFPE account describes Fourier-transform infrared measurements at about 1 m above the floor near the wall, with comparisons to grab samples and ion-selective electrode measurements.[14] The methods generally agreed, except for an HCFC blend where the treated grab sample gave a higher inferred HF value. The authors proposed that sample treatment altered how fluorine bound in the blend was measured.[14] Measurement method and sampling location therefore belong beside any test concentration.[14]
The NOAEL and LOAEL values in the 2008 handbook address direct exposure to an undecomposed clean agent. They derive from an adverse response to the agent itself and are tabulated as agent volume percentages.[20] They are not HF criteria. HF produced by a fire has to be considered alongside the agent exposure and the original fire effluent.[20][4]
Battery-fire context
A NIPV account of indoor car parks describes HF among the gases from burning electric-vehicle battery packs and associated materials.[6] It reports, from a study it cites, a range of about 20–200 mg HF per watt-hour of battery capacity. Applied arithmetically to a 100 kWh pack, the stated range is 2–20 kg; the account says the pack's state of charge affects the result.[21] This is an estimated emitted mass, not an airborne concentration or an individual inhaled dose.
The same NIPV report attributes a roughly 1.8-fold HF difference between tested electric and conventional vehicles to a comparative vehicle-fire study.[22] It does not show that every electric-vehicle fire has that ratio. The report also describes HF binding to particles and surfaces, with the airborne concentration falling by more than half within 10–20 minutes in the cited work. Such deposition transfers part of the contamination to walls, floors, ceilings and clothing.[23] The dates and secondary-source nature of these findings limit their use outside the reported tests.
See also
Notes
- ↑ 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 Gann and Bryner (2008), p. 6-13.
- ↑ 2.00 2.01 2.02 2.03 2.04 2.05 2.06 2.07 2.08 2.09 Gann and Bryner (2008), p. 6-16.
- ↑ 3.00 3.01 3.02 3.03 3.04 3.05 3.06 3.07 3.08 3.09 DiNenno and Taylor (2008), p. 17-114.
- ↑ 4.00 4.01 4.02 4.03 4.04 4.05 4.06 4.07 4.08 4.09 4.10 4.11 4.12 4.13 4.14 DiNenno and Taylor (2008), p. 17-116.
- ↑ 5.0 5.1 Harrington (2008), p. 17-134.
- ↑ 6.0 6.1 6.2 Van der Graaf et al. (2021/2023), p. 26.
- ↑ 7.0 7.1 7.2 Gann and Bryner (2008), p. 6-18.
- ↑ 8.0 8.1 8.2 8.3 8.4 8.5 Gann and Bryner (2008), p. 6-24.
- ↑ 9.0 9.1 9.2 9.3 9.4 9.5 Purser (2002), p. 2-121.
- ↑ 10.0 10.1 Davenport (2008), p. 7-52.
- ↑ DiNenno and Taylor (2008), p. 17-95.
- ↑ Iqbal and Salley (2004), p. B-72.
- ↑ 13.0 13.1 DiNenno and Taylor (2008), p. 17-96.
- ↑ 14.0 14.1 14.2 14.3 14.4 DiNenno (2002), p. 4-190.
- ↑ 15.0 15.1 15.2 15.3 DiNenno and Taylor (2008), p. 17-115.
- ↑ Sheinson, as cited in DiNenno and Taylor (2008), p. 17-115.
- ↑ 17.0 17.1 Iqbal and Salley (2004), p. B-76.
- ↑ 18.0 18.1 Iqbal and Salley (2004), p. B-74.
- ↑ 19.0 19.1 Iqbal and Salley (2004), p. B-73.
- ↑ 20.0 20.1 Harrington (2008), p. 17-132.
- ↑ Larsson et al., as cited in Van der Graaf et al. (2021/2023), p. 26.
- ↑ Lecocq et al., as cited in Van der Graaf et al. (2021/2023), p. 26.
- ↑ RIVM, as cited in Van der Graaf et al. (2021/2023), p. 26.
References
- Davenport, J. A. (2008). Storage and handling of chemicals. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 7-43–7-55). National Fire Protection Association.
- DiNenno, P. J. (2002). Halon replacement clean agent total flooding systems. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 4-173–4-200). National Fire Protection Association; Society of Fire Protection Engineers.
- DiNenno, P. J., & Taylor, G. M. (2008). Halon and halon replacement agents and systems. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 17-93–17-121). National Fire Protection Association.
- Gann, R. G., & Bryner, N. P. (2008). Combustion products and their effects on life safety. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-11–6-34). National Fire Protection Association.
- Harrington, J. L. (2008). Application of gaseous agents to special hazards fire protection. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 17-123–17-139). National Fire Protection Association.
- Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.
- Purser, D. A. (2002). Toxicity assessment of combustion products. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-83–2-171). National Fire Protection Association; Society of Fire Protection Engineers.
- Van der Graaf, J., Hessels, T., & Rosmuller, N. (2023). Fire safety of indoor car parks accommodating electrically powered vehicles. Nederlands Instituut Publieke Veiligheid. (Original work published 2021)